Professional Documents
Culture Documents
Discrimination Overview
The purpose of this presentation is to show how protection discrimination is achieved with the ADVC Controller. The following topics will be covered: Discrimination by time. Discrimination by current. Discrimination by time and current. Standard and non standard curves available on the ADVC. How protection curves can be modified to assist in achieving coordination and discrimination.
Schneider Electric < AUTHOR > <DATE> 2
Principle of Discrimination
Correct discrimination ensures that the faulty part of a power system only is isolated as quickly as possible, leaving all of the fault-free parts energised. Fault F1 may be detected by protection devices A, B, C and D. Time to Trip for D should be shorter than C which is shorter than B etc.
B
This ensures that only the circuit necessary to clear the fault is disconnected by either primary or back-up protection.
D F1
Discrimination Interval
The difference in operation time T between two successive protection devices is the discrimination interval. It takes into account -Breaking time Tc of the
downstream circuit breaker, which includes the breaker response time and the arcing time. -Time delay tolerances dT -Upstream protection unit overshoot time tr.
-A safety margin m.
dTB
30ms
TcB
50ms
m
60ms
trA
30ms
dTA
30ms
Discrimination Interval T
200 ms
Time to Trip
The time delay between Pickup and Trip is determined by the protection settings applied. The Time to Trip is dependant on whether the active trip is set to: Possible Active Trips
-Trip 1 -Trip 2 -Trip 3
-Definite Time
-Trip4
-Instantaneous Only
-Single Shot
-Inverse Time
-Work Tag
ENGINEERING MENU Protection menu Configuration menu Power quality Telemetry menu Automation menu Measurements menu
PROTECTION MENU Protection Global Protection Trip Settings Protection Control Directional Elements
PROT TRIP SETTINGS Trip 1, 2, 3, 4 (Reclose time, Protection & reset curve for P, E, SEF, NPS) Single Shot (SS reset time, Protection & reset curve for P, E, SEF, NPS) Work Tag (Protection & reset curve for P, E, SEF, NPS) Under Over Frequency (Under, Over, Normal Close, Low V inhibit, Bushing) Under Over Voltage (Under, Over, Config) Loss of Phase (On/Off/Alarm, Voltage, Timeout)
Types of Discrimination
Various means can be used by the ADVC controller to implement discrimination between devices. Time-based discrimination
-Definite Time
Current-based discrimination
-Instantaneous Only
Time-Based Discrimination
Time-Based Discrimination
Time-based discrimination consists of assigning different time delays to the overcurrent protection units distributed through the power system. The closer the relay is to the source, the longer the time delay. Advantages:
-Provides back-up -It is simple
DT = 1.1s
A
DT = 0.8s
DT = 0.5s
Drawbacks
-The longest fault clearance time occurs for faults closest to the source where the fault level is highest.
DT = 0.2s
D F1
10
1.0s
4.00
> 200A
11
1.0s
4.00
<0.010s 200-800A
> 800A
12
Current-Based Discrimination
13
Current-Based Discrimination
Current-based discrimination works on the principle that the further the fault is from the source, the lower the fault current will be. The threshold is set to a value lower than the minimum shortcircuit current caused by a fault in the protected section and higher than the maximum current caused by a fault in the next section.
IsA=960A
A
IsB=780A
IscAmin = 1000A
B
IscBmin = 800A IsC=490A
C F1
IscCmin = 500A
Each protection device should only pickup for faults located in the section of feeder immediately downstream.
Schneider Electric < AUTHOR > <DATE>
14
IsA=960A
F1
IscAmin=1250A
15
Time delays TA and TB are independent and TA may be shorter than TB Drawbacks:
-The upstream protection device (A) does not provide back-up for the downstream device.
TA=0.6s
IscAmin=1250A
TB=0.9s
-In practice it is difficult to define the settings for two cascading protection devices and still ensure discrimination unless there are transformers between sections.
Schneider Electric < AUTHOR > <DATE>
F1
16
A
IsA=960A
TA=0.6s
TB
IscAmin=1250A
TA
IscBmax 760A IsB=600A
TB=0.9s
I
IsB IscB IsA max
IscA min
F1
18
0.3
<0.010s
> 200A
19
0.3
0.30s
> 200A
20
21
In the example below device B uses Definite Time and device A uses Definite Time with an Instantaneous multiplier.
t B A Feeder 2
B
B is the Primary protection device for Feeder 2
A DT
T
B DT A Inst IsB IsA IscB IinstA IscA
22
10.0
1.0
0.1
-IEEE
Standard
0.01
-TCC
42
Non-standard curves
1 0
1 0 0
1 0 0 0
23
24
25
27
2.00
10.03s 2.97s
400A x2
2000A x10
28
2.00 0.20
20.06s
5.94s
400A x2
2000A x10
29
2.00 0.20
2.006s 0.59s
400A x2
2000A x10
30
2.00 0.20
0.80
2.006s 0.59s
400A x2
2000A x10
31
2.00 0.20
0.80 0.20
2.006s 0.80s
400A x2
2000A x10
32
2.00 0.20
0.80 0.20
2.206s 0.80s
400A x2
2000A x10
33
B
40A IEC255 SI
F2 2500A
F1 400A
Trip Time
Fault F1 400A
B E
X 10 X2 X 12.5
Fault F2 2000A
B
40A IEC255 SI
F2 2500A
F1 400A
Trip Time
Fault F1 400A
B E
X 10 X2 X 12.5
Fault F2 2000A
B
40A IEC255 SI
F2 2500A
F1 400A
Trip Time
Fault F1 400A
B E
X 10 X2 X 12.5
Fault F2 2000A
B
40A IEC255 SI
F2 2500A
F1 400A
Trip Time
Fault F1 400A
B E
X 10 X2 X 12.5
Fault F2 2000A
200A IEC255 SI
F2 3000A
Isc = 2400A
Current ACR Setting Multiple Trip Time Instantaneous Additional Minimum Time Time Multiplier X 14 Fault F2 3000A E X 15 2.52s <0.01s 1.0s <0.01s 2.0s 2.0s
38
39