Single Shot and Work Tag

On the ADVC Controller

With the flexVUE Operator Interface

Single Shot Mode


Single Shot Mode is used to provide an appropriate protection curve when non-reclosing operation is required. For example:

When Auto Reclose is OFF


When closing onto a fault.

Schneider Electric < AUTHOR > <DATE>

Single Shot Operation


In Single Shot Mode the controller Single Shot Mode is activated goes directly to lockout after one when: trip and will not Auto-Reclose.
-Auto-Reclose is turned off and Work Tag is not applied.
-The circuit breaker is closed by operator command irrespective of the state of Auto-Reclose.

Single Shot is de-activated when:


-Auto-Reclose is turned back on. -Work Tag is not active, and the Single Shot Timer expires without a protection pickup occurring.

Schneider Electric < AUTHOR > <DATE>

Single Shot Timer


The Single Shot timer starts when This may be disabled by setting the switchgear is manually closed the Single Shot reset time to zero. and runs for the preset number of seconds. When set to zero, auto-reclosing will always be enabled while Auto Reclose is ON.

Schneider Electric < AUTHOR > <DATE>

Single Shot Timer Indication

OPERATOR CONTROLS Lockout Single Shot Active ON LOCAL CONTROL

Schneider Electric < AUTHOR > <DATE>

Single Shot Timer initiated by Operator Close

Operator Close

Single Shot Timer Expires

Single Shot Timer Setting

SS Timer

CB Status

OPEN

CLOSED
t

Single Shot Mode

Auto Reclose Mode

Schneider Electric < AUTHOR > <DATE>

Protection Pickup during Single Shot Timing

Operator Protection Close Pickup

Single Shot Protection Trip

Pickup

Time to Trip

Single Shot Timer Setting

SS Timer

CB Status

OPEN

CLOSED

OPEN
t

Single Shot Mode

Schneider Electric < AUTHOR > <DATE>

Protection Reset during Single Shot Timing

Operator Protection Close Pickup Protection Reset

Single Shot Timer Expires

Pickup Single Shot Timer Setting

SS Timer

CB Status

OPEN

CLOSED
t

Single Shot Mode


Schneider Electric < AUTHOR > <DATE>

Single Shot Protection Settings in WSOS

Schneider Electric < AUTHOR > <DATE>

PROTECTION MENU PROT TRIP SETTINGS

GLOBAL CONTROL Global control (Display, Copy, Trips to lockout, Seq reset time, Max time, Auto restore, Auto reclose) Global pickup (Current & mult for Phase, Earth, SEF, NPS) Fault reset (FR time, Reset Threshold Mult for Phase, Earth and NPS, Start at Rst Thresh/Pickup)

PROT TRIP SETTINGS Trip 1, 2, 3, 4 (Reclose time, Protection & reset curve for P, E, SEF, NPS) Single Shot (SS reset time, Protection & reset curve for P, E, SEF, NPS) Work Tag (Protection & reset curve for P, E, SEF, NPS) Under Over Frequency (Under, Over, Normal Close, Low V inhibit, Bushing) Under Over Voltage (Under, Over, Config) Loss of Phase (On/Off/Alarm, Voltage, Timeout)

PROTECTION CONTROL Cold Load Pickup (On/Off, Time, Multiplier) Inrush Restraint (On/Off, Time, Multiplier) High Current Lockout (On/Off, Current, Trip) Dead Lockout On/Off Live Load Blocking On/Off Sequence Control On/Off

DIRECTIONAL ELEMENT Directional Blocking (Phase, Earth, SEF, NPS, System Voltage, High Vzps Alarm, balance) Directional Protection (Phase, Earth, SEF, NPS, System Voltage, High Vzps Alarm, balance)

Schneider Electric < AUTHOR > <DATE>

10

Single Shot - Summary


An ACR will always go directly to Lockout following a protection trip if it is in Single Shot mode. Providing the Work Tag has not been applied, an ACR will be in Single Shot mode if: Auto Reclose is OFF An operator has closed onto a fault. Providing:
-The Single Shot Timer has not been set to zero.

The timing of a trip that occurs when the ACR is in Single Shot mode is determined by dedicated Single Shot settings for the particular type of fault.
Schneider Electric < AUTHOR > <DATE> 11

Work Tag
Applying the Work Tag ensures that closing cannot take place at all, either by a local operator, a remote operator or automatically. The switchgear cannot close while the Work Tag is applied but Work Tag can be applied when the switchgear is closed providing nothing is inhibiting tripping. If a protection trip occurs while the Work Tag is applied, the switchgear will always go to lockout even if Auto Reclose is ON. The protection pickup and time to trip will be determined by the Work Tag protection settings and Work Tag Trip will be recorded in the Event Log.

Schneider Electric < AUTHOR > <DATE>

12

Selecting Work Tag ON in WSOS

Schneider Electric < AUTHOR > <DATE>

13

OPERATOR MENU OPERATOR CONTROLS 1 OPERATOR Alerts Active CONTROLS Work Tag Applied OFF

OPERATOR CONTROLS Local/Remote Autoreclose ON/OFF Earth SEF ON/OFF NPS Alarm/Trip/OFF Protection Group Active APGS Off/Auto Work Tag On/OFF Cold Load Battery health test manual start Radio supply On/Off Low Gas Inhibit on/off Demand Period Sequence

SWITCHGEAR STATUS Switchgear Info (Function, Type, Serial #, Rating, Software version) Switchgear Data (Pressure, Status, Operations Count, Contact Wear)

MEASUREMENTS System Measurements (AVG Current, Voltage, Frequency, Power Factor, 3 PH Power P and Q) Current (Phase, Earth Magnitude & Angle) Bushing Indication (Source and Load side Live/Dead) Maximum Demand Ind (Phase Max & time, Reset)

INDICATIONS Flags (O/C, E/F, SEF, LOP, UOV, NPS, EXT, FRQ) Operations Count

Schneider Electric < AUTHOR > <DATE>

14

Work Tag Protection Settings in WSOS

Schneider Electric < AUTHOR > <DATE>

15

PROTECTION MENU PROT TRIP SETTINGS

GLOBAL CONTROL Global control (Display, Copy, Trips to lockout, Seq reset time, Max time, Auto restore, Auto reclose) Global pickup (Current & mult for Phase, Earth, SEF, NPS) Fault reset (FR time, Reset Threshold Mult for Phase, Earth and NPS, Start at Rst Thresh/Pickup)

PROT TRIP SETTINGS Trip 1, 2, 3, 4 (Reclose time, Protection & reset curve for P, E, SEF, NPS) Single Shot (SS reset time, Protection & reset curve for P, E, SEF, NPS) Work Tag (Protection & reset curve for P, E, SEF, NPS) Under Over Frequency (Under, Over, Normal Close, Low V inhibit, Bushing) Under Over Voltage (Under, Over, Config) Loss of Phase (On/Off/Alarm, Voltage, Timeout)

PROTECTION CONTROL Cold Load Pickup (On/Off, Time, Multiplier) Inrush Restraint (On/Off, Time, Multiplier) High Current Lockout (On/Off, Current, Trip) Dead Lockout On/Off Live Load Blocking On/Off Sequence Control On/Off

DIRECTIONAL ELEMENT Directional Blocking (Phase, Earth, SEF, NPS, System Voltage, High Vzps Alarm, balance) Directional Protection (Phase, Earth, SEF, NPS, System Voltage, High Vzps Alarm, balance)

Schneider Electric < AUTHOR > <DATE>

16

Work Tag and Controller Mode


The controller is always in either Local or Remote mode. Only a local operator can apply/remove the Work Tag when the controller is in Local Mode. Only a remote operator can apply/remove the Work Tag when the controller is in Remote Mode. This means that for a local operator to remove the Work Tag which was applied by a remote operator, they must first put the controller into Local mode.

OPERATOR CONTROLS WORK TAG DENIED Work Tagto Applied SELECT - CHANGE TO continue LOCAL

Schneider Electric < AUTHOR > <DATE>

17

Single Shot and Work Tag Modes


Single Shot and Work Tag modes will both cause an ACR to go directly to Lockout if a protection trip occurs. i.e. -They both prevent automatic reclosing. Work Tag mode prevents manual closing as well. Single Shot and Work Tag trips occur according to their own respective settings. i.e. -In Single Shot mode the ACR will trip according to the Single Shot settings. -In Work Tag mode the ACR will trip according to the Work Tag settings. An ACR will always be in Work Tag mode if the Work Tag is applied regardless of the Single Shot status.
Schneider Electric < AUTHOR > <DATE> 18