Professional Documents
Culture Documents
By Y. k. Pandharipande.
High Speed Operation Selectivity Reliability Sensitivity Suitable for Use with moderate CT Ratings. Extendable to changes in Bus Bar configuration & addition of Circuits.
Relay Branch made High Impedance to limit differential current due to unequal CT saturation on external fault. Requires exclusive CT core of identical ratio and rating. Simple in design and execution.
Through current Bias increases differential pick-up on external fault to ensure stability. Tolerant to CT mismatch and can use shared core. Comparatively more complex in design and execution. Practical schemes provide CT saturation detectors to enhance stability.
If B CT fully saturates on external fault, Vs = If/n (Rct + 2Rl) Volts. Relay Branch Impedance = Vs/Is, where Is = Setting current of Relay. External Stabilising Resistor RST = Vs/Is VA /Is, where VA = Relay VA burden at setting current.
Vs = 20 (5 + 1) = 120V
Stabilising Resistor (RST) = 120/0.2 1.0/0.2 = 600 - 25 = 575 ,
(assuming relay VA burden = 1 VA)
Primary Fault Current setting (assuming number of circuits connected to Bus Bar, N=10) = CT Ratio (Is + N. Im) = 1000 (0.20 + 10 x 0.03) = 500A.
Peak Voltage across CT Secondary for Max. Internal Fault = 2 2 [Vk x (Vp Vk)] Vk = 240V, Vp = 20 (575 + 25) = 12000V Peak Voltage = 22 [(240 x (12000-240)] = 5300V
If Peak voltage exceeds 3000V threatening secondary insulation, Metrosils (Non-linear resistors) are used to limit voltage to safe value (within 1000V) on internal fault. Metrosil offers high resistance at lower voltage levels which drastically reduces at higher voltages, thereby quenching the voltage across relay branch. Typical Metrosil Equation V = C x I ( C = 900 , = 0.25)
Required to detect CT open circuit on load to prevent maloperation. Connected for alarm & short CT bus wires on operation. Time delayed to avoid operation on internal / external faults (3Sec) Voltage relay with sensitive setting (2 -14V) is used. Normally set to detect primary unbalance of 25A or 10% of least loaded circuit. Also should not operate with normal unbalance on load.
Provides local isolation when breaker gets stuck on fault. Ensures comparatively faster clearance than remote backup.
LBB CURRENT CHECK RELAY (50) Current Setting Range 20-320% or 5 -80%In (Recommended setting - 5% for Generator & 20% for Other Circuits) LBB TIMER (2/50) Range o.11.0 S (Recommended 0.20S)
TLBB = TCB + TDO + TM TPU, Where TCB = C.B. Trip Time, TDO = Current Check relay DO time, TM = Safety margin, TPU = Current Check relay PU Time
Normally,200ms delay recommended which is faster than remote backup and allows sufficient time for normal C.B. tripping.