Professional Documents
Culture Documents
Refrigerant Piping
Introduction
The tables and application data in this publication will help you to better apply split system cooling and heat pump systems to achieve maximum efficiency and performance, improved reliability, and greater customer satisfaction. This guideline includes information for:
General Guidelines
Support all refrigerant lines at minimum intervals (4 feet) with suitable hangers and brackets. Slope horizontal suction lines on cooling only systems approximately 1 inch every 20 feet toward the outdoor unit to facilitate proper oil return. Since the flow of refrigerant is bi-directional on heat pumps, horizontal vapor lines should be level.
Support lines
Every 4
Oil Traps
Outdoor above indoor, use traps as per guidelines Indoor above outdoor, use inverted trap
Oil Traps
Cooling or Heat Pumps Design
(2) 45 Degree Short Elbows (1) 90 Degree Short Elbow
Oil Trap
2-Short Ls 1-Long L
Inverted Trap
Whenever the Evaporator is Above the Condenser
Where inverted traps are not an option, a Liquid Line Solenoid Valve will help prevent refrigerant migration. NOTE: If a
high M.O.P. TXV is used, a LLSV is not necessary
Concerns:
A. Loss of Subcooling ? ? ?
B. Does the Metering Device Need Changed ? ? ?
Application Data
Application Data
Additional Refrigerant
In many applications, additional refrigerant will have to be added to the system. The actual amount of charge that must be added is determined by adding the following: 1. The indoor coil charge adjustment from the Product Tech Guide. This is always a predetermined amount based on the outdoor unit/indoor coil combination being used. 2. The additional charge required for the interconnecting piping. This is dependent on the type of unit being used (i.e., sweat or quick-connect ) and the size of the vapor and liquid lines. 3. Refer to Table #6 for both Suction and Vapor
Additional Requirements
If not provided as standard features, the following items are required when measured piping lengths exceed fifty feet:
1. Low Voltage Start Kit (2SA06701006) - single phase units on 208V application.
2. Off Cycle Timer (2TD08700124) - if item 1 is used. 3. Crankcase Heater (025-19961-001) - except units with a scroll compressor. On cooling only systems with measured piping lengths greater than seventy-five (75) feet, one of the accumulators in Table 8 must be field installed near the outdoor unit. The accumulator should be sized based on total system charge.