Professional Documents
Culture Documents
NEW #34, 2ND FLOOR, ST.MARYS ROAD, MANDAVELI, CHENNAI 600 028. PHONE: 044-2461 0789 / +9194443 03293
ABOUT 40 KLD SEWAGE TREATMENT PLANT REPAIR AND RENOVATION PROGRAMME @ THE STANDARD CHARTERED BANK, NUNGAMBAKKAM, CHENNAI.
DATE: 05.08.2013
OBJECTIVE
Purpose of this report is, justifying our proposal about existing sewage plant overhauling, repair and renovation. AIM The ultimate goal of this work is
Renovate the STP and also establish a system for reuse the treated water. Ensure the legal compliance of TNPCB Ensure cost effective solution, easy to operate and reduce the O & M Cost..
EFFLUENT CHARACTERISTICS
S.No. 1. 2. 3. 4. 5. pH BOD (Biological Oxygen Demand) COD (Chemical Oxygen Demand) TSS (Total Suspended Solids) Oil & Grease Description of the Parameter Raw Effluent 6.5 8.5 450mg/lit 500mg/lit 300mg/lit 50mg/lit Treated Effluent Characteristics (After Renovation) 6.5 8.5 <30mg/lit <250mg/lit <10mg/lit <10mg/lit
BACKGROUND The Standard Chartered Bank, located at Nungambakkam, produced per day maximum 40KLD domestic waste water from their domestic activity. Presently they have own system, that was not suitable for achieve the compliance of TNPCB and their reclamation water requirement. OBSERVATION
The time of our site visit, we are found and observe the following matters. EXISTING PLANT LAYOUT
OBSERVATION
PARAMETERS CAPACITY Treatment Type Collection cum Equalisation Tank Biological Activity Primary Filter Cacoo Filter Air blower Air Distribution System Cacoo Filter Media support Air Distribution System (Air Diffusers) Cacoo media (graded pebbles & sylex) Cacoo media Carbon Cacoo media Anthra cite Recirculation mechanism PRESENT CONDITION 40 KLD to 60 KLD Cacoo Filter method Collection tank Available, Tank capacity data not available Not adequate Available Available Available, but not adequate airflow (Time of observation) In fully damaged condition (Time of observation) In damaged condition Not working, fully damaged condition Not in adequate quantity, fully chocked condition Not in adequate quantity Not in adequate quantity Not available / damaged condition
-
ACTUALLY REQUIRED 40 KLD Cacoo filter method As per standard procedure minimum 2X of daily flow Must in Collection tank & Cacoo filter Primary Filter available, but not adequate in performance Minimum 50m3/hr @0.4kg/cm2 pressure
It is must for sewage treatment Minimum 1 to 1.25m height maintained Minimum 300 liters Carbon maintained Minimum 300 liters maintained Recirculation mechanism should be provide with 1HP pump with adequate plumbing
OBSERVATION CONTINUE REASONS: Strong strength sewage inflow with FOG. There is no control provision in existing system. Biological activity is disturbed, due to fat & oil. It is affected and damaged the Cacoo system. Aeration: - Blowers are not in working conditions. Present air distribution is not working. High inflow of BOD affect the Cacoo filter efficiency, lackness of recirculation system in the existing system. RECOMMENDATIONS: Improve the Aeration Efficiency Replace the existing blower and installed Aeration recirculation pump and sufficient diffusers for nutrient removal (BOD). Biological activity should be developed inoculate beneficial bacteria. Provide sufficient media in Cacoo system. PROPOSED REPAIR & RENEVATION STRATEGY:
The proposed STP renovation program is designed for utilizing maximum available facility and improve the treatment quality of the waste water (capacity of 40 KLD) through the installation of new blower, recirculation system with pump, Cacoo media replacement & installed the air distribution system with support and accessories.
YES
CONCLUSION:
The proposed scheme is help to produce the reclamation water(for Gardening) and conforming to the standards stipulated by Tamil Nadu Pollution Control Board. Ensure cost effectiveness, easy to operate and reduce the O& M Cost.