Daily, fires occur due to electrical problems: defective electrical device, circuit overloading, circuit overheating, explosions ignited by electrical spark, etc. Electricity is one of the most common causes of fire in the USA. Each year there are approximately:
1.6 million fires (all causes) reported, causing 3,600 fire deaths, 18,000 fire related injuries, $10.7 billion in property damage.
Grounding
What is Grounding?
Grounding a tool or electrical system means intentionally creating a lowresistance path that connects to the earth. This prevents the buildup of voltages that could cause an electrical accident. Grounding is normally a secondary protective measure to protect against electric shock. It will substantially reduce the risk of injury or death in case of shock, especially when used in combination with other electrical safety measures. An equipment ground helps protect the equipment operator. It furnishes a second path for the current to pass through from the tool or machine to the ground. This additional ground safeguards the operator if a malfunction causes the tools metal frame to become energized. The resulting flow of current may activate the circuit protection devices.
Protection
Overcurrent Protection
Fuses and circuit breakers open/break the circuit automatically when too much current flows through them. This is designed to protect the wiring/equipment from overheating and possible damage NOT THE USER
GFCI (Ground Fault Circuit Interrupter) Used in wet and other high-risk areas. Stops the flow of electricity when there is a difference between current leaving and returning from the outlet. Should be tested monthly Push test button and then the reset button
Extension Cords & Power Strips are for TEMPORARY use only! They may not be run through doorways, ceilings or windows Power Strips (Transient Voltage Surge Suppressors) FOR ELECTRONICS ONLY (Computer Equipment etc.) NOT FOR APPLIANCES (Refrigerator, Microwave Toaster, Coffee Pot, Water Cooler etc.)
Do not overload The number of outlets on the power strip does not indicate how many devices can be connected
12
Power taps
Grounding Cable
Proper grounding and bonding is used to address the dangers of static electricity. In order for grounding to protect, all surfaces must be bonded together and grounded to earth. Static electricity is thereby released to earth as it is generated, preventing the accumulation of dangerous charges that may ignite flammable / hazardous substances.
Responsibilities
Entire system must be properly bonded and grounded to the earth
Facilities Responsible for the system up to the wall outlet (all wiring and outlets) User Responsible for the condition of plug and cord of equipment Inspect equipment to ensure plugs and cords are not damaged. Do not break off third prong or use adaptors No Prong = Not Grounded
Background
Dr. X was conducting an experiment related to plant growth. He needed to expose the plants to light for specific time-periods each day. Accordingly, he had a portable fluorescent lighting rack constructed and mounted on a wooden frame. He also obtained an electric timer to automatically turn the lights on and off. The light fixture was plugged into the timer, which was plugged into the wall outlet. However, since the timer only accepted a two prong plug, an adapter was used to allow the three prong plug of the lighting rack to be used with the two prong outlet of the timer.
The Incident
Dr. X adjusted the timer so that the lights would be on and plugged the timer into a standard 3prong wall outlet. Then another person in the lab noticed Dr. X grasping the lighting rack and appearing to be rigid. A third person grasped Dr. X by the shoulders and pulled him away from the lighting rack. CPR was performed on him until EMS arrived. Dr. X was transported to a hospital where he was pronounced dead.
The Investigation
The investigation revealed the following details:
A potential difference of 397 volts was measured between the metal fluorescent light fixture and the adjacent stainless steel sink. (There should not have been any potential difference). Both the fixture and the wall outlet were found to be wired correctly. The light fixture was rated for 800 mA, but the lamps used were 1500 mA. The transformer in the ballast was found to have short circuited to the case.
If overrated lamps had not been used, the ballast would probably not have overheated and failed. If the ground wire connection between the light fixture and the plug not been interrupted by the "cheater" adapter and the two-prong timer, the fixture would have safely shorted to ground tripping the circuit breaker when the equipment was plugged in before Dr. X touched it. Had the standard outlet near the sink been Ground Fault Circuit Interrupter (GFCI) protected (as it should have been because it was near a sink), the GFCI would have tripped at the first flow of current through Dr. X immediately cutting off power to the fluorescent fixture and saving his life.
These electrical safety violations cost Dr. X his life. If any one of them had been corrected before the incident, Dr. X would still be researching plant growth.
continued
5) If you see a person being electrocuted, DO NOT TOUCH HIM! The electricity can go though you too. If possible, remove the power (pull plug or trip circuit breaker), or use a non-conductive item (e.g. wooden broom handle) to pry him away from the contact. 6) Above all, do not disable any electrical safety feature expecting that another safety feature will protect you. In the incident described above, if proper lamps were used, the ballast could still have been defective from other causes. Also, GFCIs can be defective. That is why they should be periodically tested. 7) Check that power cords are in good condition. 8) Do not use extension cords as a substitute for permanent wiring.
Electrical Work
Contact Facilities X4588 for ALL electrical work Do not attempt to fix on your own Attempting to repair equipment yourself may create a hazard
13
Conclusion
Know and follow safe work rules and practices NO EXTENSION CORDS AS PERMANENT WIRING POWER STRIPS ARE FOR ELECTRONICS ONLY Report all unsafe conditions to Facilities X4588 or EHS X4078