Fire and gas (F&G) detection systems are at the cornerstone of modern process plant safety
Alert staff to a developing hazard Enable executive action to ensure that the plant is placed into a safe state
F&G systems do not prevent a hazardous condition from occurring, but rather mitigate the effects of a hazard
Detector Placement
Methods for laying out flame and gas detectors are intended to maximize the potential for detection success in the event of a release
Source monitoring Volumetric monitoring Enclosure monitoring Perimeter monitoring
6
Source Monitoring
Source monitoring involves the placement of detectors around potential release sources
Applicable to detection of moderate and large releases of flammable materials Useful for the detection of large or catastrophic toxic releases that may migrate from the area
Assessment
Use computer modeling to evaluate target release Determine set back distance between potential source and sensors
Design Layout
Lay out sensors on plot plan using set back distances and sensor spacings Heavier-than-air gases will tend to move to low lying areas
Combination of point and open path infrared (IR) detectors Determine allowable may provide most economical distance between sensors approach for achieving reasonable probability of detection success
Example
6m 10% LEL
Figure 1
If open path detector alarms at 10% LEL-m, cloud must overlap one of the beams by at least 1 m
5m 6m
Figure 2
9
5m
Volumetric Monitoring
Volumetric monitoring is based on concept that greatest risk from flammable gas escapes is direct damage from explosions
Does not consider small releases as deemed impractical to detect reliably
Flame velocity
Congestion
10
Detonation
Ignited 6-m methane or propane cloud does not achieve flame speeds greater than 100 m/s in methane and 125 m/s in propane
Large unconfined volumes Confined volumes with blockage rations less than 0.3 or 0.4
5 6 m (16 19 ft)
11
Pressure differential is less than required to produce structural damage (approx. 2 psi or 150 mbar)
General Monitors 2012
Example
5m
12
Blockages
Structures within a space can prevent the dispersion of gas and produce localized pockets of high gas accumulations Structures can also generate enough resistance to a propagating flame front to generate a significant pressure front
13
Blockage Ratio
Blockage ratio is the ratio of obstructed area over total area
Considers each monitored volume a cube
Example: 11 x 55 m2 deck elevated by 15 m Solid area is 30% of square Three heat exchangers occupy base area of 30 m2
Deck area = 30% x (11 x 55) m2 Heat exchangers = 30 m2 Ground area = 11 x 55 m2 Total = 817 m2
Surface area of cube = 2 (11 x 55) + 2 (15 x 55) + 2 (11 x 15) = 3190 m2 Blockage ratio = 817 / 3190 = 0.26
14
Type
Small buildings
Large buildings
4 (13)
5 (16)* 4 (13)
* When an inerting system is present in compliance with NFPA 69 (Standard on Explosion Prevention Systems)
1,000 (35,000)
Considerations:
> 0.3
5 (16)
If volume does not contain a potential release source, apply source monitoring method or monitor the perimeter of the volume If gas is heavier than air and arises from a distant source, install detectors near ground or grade level (18 in or 0.5 m) along perimeter If gas is heavier than air and comes from a nearby source or of a neutrally buoyant gas, provide multiple levels of detection at 5 m (16 ft) vertical intervals along perimeter
16
0.3
0.3
10 (33)
5 (16)**
* Protection should be provided according to the detector deployment strategy for partially-enclosed volumes ** Detection should be capable of sensing the gas cloud of 5 m (16 ft) in diameter anywhere within the pockets
Open volumes (blockage ratio < 0.3) usually do not require combustible gas detectors
Install detectors if open space contains multiple congested areas
17
Use open path detection along perimeter if volume has no congested pockets with blockage ratios greater than 0.3 and hazard is gas migration from volume to other areas
Protection for life
For areas containing inventories of process fluids, which on loss of containment remain as liquids for a significant period, a threedimensional grid should be used
No more than 0.5 m (1.5 ft) above local deck or grade
18
Liquid Phase and Heavier-than-air Releases (Continued) For isolated sources (ex. transfer pumps, loading installations in open areas), detectors should be placed on a 5 m (16 ft) triangular grid around potential heavy gas release points
19
Enclosure Monitoring
Enclosures are commonly found in the process industries
Analyzer buildings Remote instrument enclosures (RIEs)
In certain applications, gas density relative to air has little effect on where gas will accumulate compared to stronger influences like release pressure and ventilation
If structure is mechanically ventilated ( 6 ACH), lay detectors according to expected path of gas travel
21
4 m (13 ft)
Gas detectors should be located 0.3 m (1 ft) within the ceiling if flat and 0.5 m (1.5 ft) within the apex
For naturally ventilated or mechanically ventilated spaces, detectors should be arranged according to the guidance for heavier-than-air gases
0.3 m (1 ft)
23
24
Perimeter Monitoring
Perimeter monitoring is sometimes used where heavier-than-air or naturally buoyant gases are present Most effective under the following conditions:
Process unit or storage is close to plant perimeter and there is high likelihood releases may cross the fence line Potential release sources are outside the coverage of local detectors
25
26
27
0.25 LEL-m
3m
Conclusion
F&G system effectiveness depends on the appropriate allocation and placement of detectors Several detector deployment strategies maximize the chances of detection in the event of a gas release Source monitoring involves the placement of detectors around potential leak sources
Useful for moderate to large releases of combustible materials and large or catastrophic toxic gas releases
28
Conclusion (Continued)
The volumetric method focuses on monitoring obstructed or congested spaces where flammable gases may accumulate
Uses a three-dimensional array of detectors to assure a gas cloud of a certain size cannot exist in a monitored space without contacting a sensor
Conclusion (Continued)
Perimeter monitoring is used to protect an area from migration of a gas plume into an area outside the owners control Sometimes mandated by regulatory agencies interested in providing increased protection from the public Most effective in detecting process gases that are heavier than air (ex. butane, carbon dioxide) Regardless of detector placement method used, a credible release may not necessarily be detectable with any degree of certainty Obstructions at a plant may change over time, rendering the allocation of sensors inadequate to address risks in certain areas Possible leak sources may not be identified during a preliminary hazard analysis
30
Conclusion (Continued)
Fixed flame and gas detectors should be part of several safeguards that prevent or mitigate the consequences of gas releases
31
Appendix
References
Continuous Monitoring for Hazardous Material Releases. 2009. Hoboken, New Jersey: John Wiley & Sons. ISA-TR84.00.07-2010, Guidance on the Evaluation of Fire and Gas System Effectiveness. 2010. Research Triangle Park, NC: ISA. Offshore Technology Report - OTO 93 002: Offshore Gas Detector Siting Criterion, Investigation of Detector Spacing. 1993. Croydon, UK: Health and Safety Executive. Zabetakis, M.G. 1965. Flammability Characteristics of Combustible Gases and Vapors. Bulletin 627. Washington, DC: U.S. Department of Interior, Bureau of Mines.