COLOURLESS BOTH AS A LIQUID AND A VAPOUR. LPG IS ODOURLESS, BUT USUALLY ADDED TRACE QUANTITIES OF ODORING AGENT(MERCAPTAN) TO ENABLE DETECTION BY SMELL. DENSITY: LIQUID LPG IS ONLY HALF THE WEIGHT OF WATER. : LPG AS A GAS IS TWICE THE WEIGHT OF AIR. EXPLOSIVE LIMIT : 1.8-9.6% VOL.IN AIR. IGNITION TEMPERATURE : 405-450 Oc. LIQUID TO GAS EXPANSION: 1:250 VAPOUR PRESSURE AT 37.5 deg. Cel = 7.7 kg/cm2(Appox) Igniting Minds... Energizing Lives Haldia Refinery Liquefied Petroleum Gas FIRE HAZARD: EXTREMELY FLAMMABLE GAS DANGEROUS WHEN EXPOSED TO HEAT OR FLAME. IT BURNS WITH A BLUE FLAME WHEN MIXED WITH CORRECT PROPORTION OF AIR. IF THE AIR SUPPLY IS INSUFFICIENT, THE FLAME BURNS YELLOW AT THE EDGES. NO SMOKE IS PRODUCE DURING BURNING. HEALTH HAZARD: LPG CONTAINS NO TOXIC COMPONENTS SUCH AS CARBON MONOXIDE AND IS THEREFORE NON POISONOUS. INHALATION: EXPOSURE TO HIGH CONC. OF LPG WILL PRODUCE UNCONSCIOUSNESS & SUBSEQUENT ASPHYXIATION. SKIN AND EYE CONTACT: IF LIQUID LPG COMES INTO CONTACT WITH UNPROTECTED SKIN AND EYES THEY WILL EVAPORATE QUICKLY AND THE COOLING EFFECT COULD PRODUCE FROST BITE OR COLD BURNS. TLV(TWA): 1000 PPM Igniting Minds... Energizing Lives Haldia Refinery
Liquefied Petroleum Gas
FACTORS AFFECT RATE OF EVAPORATION DURING LPG SPILL AMBIENT TEMPERATURE WEATHER CONDITIONS SLOPE OF THE GROUND CONDUCTIVITY OF THE GROUND SURFACE AREA OF THE SPILL (ANY OBSTRUCTIONS SUCH AS BOUNDARY WALLS WILL SLOW RATE OF EVAPORATION). IF WATER IS SPRAYED ONTO A LPG LIQUID SPILL, IT WILL ACT AS A HEAT SOURCE AND INCREASE THE EVAPORATION RATE. Igniting Minds... Energizing Lives Haldia Refinery Liquefied Petroleum Gas TYPES OF INCIDENTS ARISING FROM COMBUSTION A. NORMAL FIRES OFTEN RESULT FROM IMMEDIATE IGNITION FOLLOWING A SPILL. USUALLY BURNS WITH A DIFFUSED FLAME WITH NO EXPLOSION. RADIATION CAN IGNITE OTHER COMBUSTIBLES IN THE AREA SOLUTION: CUT OFF AIR/FUEL SUPPLY TO FLAME & APPLY COOLING B. FLASH FIRES IGNITION OF OVERRICH CLOUD OF FUEL IN AIR FLAME BURNS BACK AGAINST CLOUD GENERALLY NO EXPLOSION CAN IGNITE OTHER SOURCES OF FUEL Igniting Minds... Energizing Lives Haldia Refinery Liquefied Petroleum Gas BLEVE
A BOILING LIQUID EXPANDING VAPOUR EXPLOSION IS STARTED BY THE HEATING OF A VESSEL CONTAINING FLAMMABLE LIQUID BY AN EXTERNAL FIRE.
CONTENT IS HEATED ABOVE ITS BOILING POINT AND PRESSURE IN THE VESSLE INCREASES.
Igniting Minds... Energizing Lives Haldia Refinery Liquefied Petroleum Gas UVCE
AN UNCONFINED VAPOUR CLOUD EXPLOSION IS AN EVENT WHERE A FLAMMABLE FUEL/AIR CLOUD BURNS IN FREE SPACE, GENERATING SHOCK WAVES.
COMBUSTION MECHANISM STARTS FROM A POINT OF IGNITION SOURCE, WITH THE FLAME FRONT ACCELERATING FROM A LOW INITIAL VELOCITY TO SONIC VELOCITY.
Igniting Minds... Energizing Lives Haldia Refinery Liquefied Petroleum Gas LIQUEFIED PETROLEUM GAS (LPG) VAPOUR LIQUID HOT AREA RELIEF VENT OPENS AT 17.6 kg/cm2 UNEXPOSED SHELL SUPPORT SLOP TANK SHELL OVERHEATED ABOVE LIQUID LEVEL
MAGNITUDE OF BLEVE:
PIECES OF CONTAINER CAN SHOOT OFF SOME 1000 METRE OR MORE DISTANCE. DEATH FROM SUCH MISSILES MAY OCCUR UPTO 250 M. FIRE BALLS OF 30 METRE (HUNDRED FEET) DIAMETER IS NOT UNCOMMON. SEVERE BURN DAMAGE IN A 300-400 M RADIUS. A SHOCK WAVE FROM BLEVE CAN BREAK WINDOWS SEVERAL KILOMETER AWAY FLAME TEMPERATURES AS HIGH AS 1200 deg C.
REMEMBER: THERE IS NO SAFETY PERIOD, A BLEVE CAN OCCUR AT ANY TIME.`
Igniting Minds... Energizing Lives Haldia Refinery Liquefied Petroleum Gas
FIRE FIGHTING PROCEDURES-BLEVE SITUATIONS
WHEN THERE IS NO RISK TO LIFE OR PROPERTY, SERIOUS CONSIDERATION MUST BE GIVEN TO EMPLOYING A NON ATTACK STRATEGY. IF A DECISION IS MADE TO ATTACK THE FIRE THEN IMMEDIATE, MASSIVE WATER-COOLING MUST BE APPLIED CONCENTRATING ON EXPOSED VAPOUR SPACE. PERSONNEL SHOULD BE FULLY BRIEFED AND MADE AWARE OF THE DANGER CONFRONTING THEM. CHANGE FROM HAND HELD BRANCHES TO GROUND MONITORS.
Igniting Minds... Energizing Lives Haldia Refinery Liquefied Petroleum Gas
FIRE FIGHTING PROCEDURES-BLEVE SITUATIONS
USE OF WATER SPRAY ON EXPOSED CREW TO GIVE PROTECTION AGAINST FIRE EFFECTS. EVACUATION OF THE SURROUNDING ARES MIN. 1000 M. REMEMBER THAT RELATIVELY HIGH RISK AREA IS AN END ON DIRECTION. HOWEVER, FRAGMENTS AND MAJOR TANK SECTION CAN FLY IN ANY DIRECTION.
Igniting Minds... Energizing Lives Haldia Refinery Liquefied Petroleum Gas
WHEN LIGHT HYDROCARBONS LIKE NAPHTHA, MS OR FLAMMABLE GASES LEAK IT VAPOURISES AND FORMS AN EXPLOSIVE MIXTURE WITH AIR. WHEN THE LEAK IS HEAVY AN EXPLOSIVE CLOUD IS FORMED. THIS CLOUD IS KNOWN AS A VAPOUR CLOUD. WHENEVER THIS VAPOUR CLOUD COMES IN CONTACT WITH A SOURCE OF IGNITION IT CAN EXPLODE AND CAUSES FROM THE VEHICLES, SMOKING OR OTHER SOURCES OF IGNITION. FORMATION OF VAPOUR CLOUD 1. LEAKAGE FROM PIPELINES: IT MAY BE ON THE ROAD SIDE, INSIDE THE UNITS OR IN THE TANK FARM. 2. LEAKAGE FROM TANKS OR TANK OVERFLOW: IT MAY BE IN THE TANK FARMS OR FROM THE TANKS IN THE UNITS AREA. 3. LEAKAGE FROM TANKERS OR OVERFLOW OF TANKER: IT MAY BE IN WAGON LOADING GANTRY AREA. Igniting Minds... Energizing Lives Haldia Refinery Vapour Cloud 4. LEAKAGE OF LPG: IT MAY BE IN THE FOLLOWING AREAS; i) INSIDE PROCESS UNITS OR ALONG ROAD SIDE LINE LEAKAGE . ii) LEAKAGE FROM ROAD TANKER, WAGONS, FILLING HOSES, HORTON SPHERES OR FROM CONNECTING PIPES. iii) LEAKAGE FROM CYLINDERS, FILLING MACHINES, PUMPS OR CONNECTING PIPES. HOW TO IDENTIFY VAPOUR CLOUD: i) BY SMELL: IF IT IS EXTRA ORDINARY ON HIGHER SIDE. ii) BY MIST : IN MOST OF THE CASES MIST FORMATION TAKES PLACES. iii) BY LEAK: IF HYDROCARBON LEAK IS VISIBLE.
Igniting Minds... Energizing Lives Haldia Refinery Vapour Cloud IMPORTANT DOS AND DONTS IN CASE OF VAPOUR CLOUD:
DOS DONTS INFORM CONCERNED UNIT PERSONNEL AND FIRE STATION . NEVER ALLOW ANY VEHICLE TO ENTER IN THE AREA. DO NOT OPERATE ANY ELECTRICAL SWITCHES. CORDON-OFF THE AREA NEVER ALLOW ANY VEHICLE TO START IN THE AFFECTED AREA. GUIDE THE UNIT PERSONNEL/FIRE PERSONNEL IF VEHICLE IS ALREADY IN THE AFFECTED AREA, REMOVE IT BY PUSHING. IN CASE OF VAPOUR SMELL, TRY TO DETECT THE SOURCE OF LEAK DURING PATROLLING IF STRONG SMELL OF HYDROCARBONS OR ANY LEAK DETECTED STOP THE ENGINE IMMEDIATELY AND MOVE ON FOOT TO DETECT THE LEAK. STOP ALL HOT JOBS AND SMOKING BOOTHS NEVER SMOKE OR ALLOW THE SMOKING INSIDE THE BATTERY AREA. Vapour Cloud Igniting Minds... Energizing Lives Haldia Refinery
VCE B, 3m/s, L- 80, W-27 0.1 bar OPR.-150 E, 1m/s, L-149, W-60 0.1 bar OPR.-220 3 LPG tank truck catastrophic failure Fire ball 138 Stability Class Details: A- Very unstable C- Slightly Unstable E- Stable B-Unstable D- Neutral F- Very Stable
Igniting Minds... Energizing Lives Haldia Refinery Major Hazards: Petroleum Industry
UVCE AN UNCONFINED VAPOUR CLOUD EXPLOSION IS AN EVENT WHERE A FLAMMABLE FUEL/AIR CLOUD BURNS IN FREE SPACE, GENERATING SHOCK WAVES. Some Major UVCE Incidents Explosion at the Flixborough Plant (1974) UK. Piper Alpha Explosion (1988)- North Sea. Pasadena Texas (1989). HPCL- Vizag Refinery-1997.- India. Texas City Explosion (2005) USA. Jaipur Oil Terminal( 2009) India.
What Happens to a Vapor Cloud? Cloud will spread from too rich, through flammable range to too lean. Edges start to burn through deflagration (steady state combustion). Cloud will disperse through natural convection. Flame velocity will increase with containment and turbulence. If velocity is high enough cloud will detonate. If cloud is small enough with little confinement it cannot explode. Igniting Minds... Energizing Lives Haldia Refinery Major Hazards Factors Favoring High Over Pressures Confinement Prevents combustion products escaping, giving higher local pressures even with deflagration. Creates turbulence, a precursor for detonation. Terrain can cause confinement. Onsite leaks have a much higher potential for UVCE. Igniting Minds... Energizing Lives Haldia Refinery Major Hazards Cloud composition Highly unsaturated molecules are bad High flammable range Low ignition energy High flame speeds Most UVCE C 2 - C 6 light gases disperse readily, heavy materials do not form vapor .clouds easily Factors Favoring High Over Pressures Igniting Minds... Energizing Lives Haldia Refinery Major Hazards Weather Stable atmospheres lead to large clouds. Low wind speed encourages large clouds. Factors Favoring High Over Pressures Igniting Minds... Energizing Lives Haldia Refinery Major Hazards The annual mean wind speed at Haldia is around 1.9m/s. From Jan-March : 1-2m/s From April-June : 3m/s From July Sep. : 2m/s From Oct.- Dec. : 1m/s Stability Class Details A- Very unstable B-Unstable C- Slightly Unstable D- Neutral E- Stable F- Very Stable Factors Favoring High Over Pressures Source flashing liquids seem to give high overpressure vapor systems need very large failures to cause UVCE slow leaks give time for cloud to disperse naturally without finding an ignition source high pressure gives premixing required for large combustion equipment failures where leak is not vertically upwards increases likelihood of large cloud. Igniting Minds... Energizing Lives Haldia Refinery Major Hazards Unconfined vapour cloud Explosion
A vapour cloud exploding in open air Igniting Minds... Energizing Lives Haldia Refinery Major Hazards Confined Vapour Cloud Explosion
A cloud exploding in a confinement Igniting Minds... Energizing Lives Haldia Refinery Major Hazards Impact of Vapor Cloud 1 pound of TNT has a LHV of 1890 BTU/lb. 1 pound of hydrocarbon has a LHV of about 19000 BTU/lb. A vapor cloud with a 10% efficiency will respond like a similar weight of TNT. Igniting Minds... Energizing Lives Haldia Refinery Major Hazards Vapor Cloud impact depends on: Probability of finding ignition source Likelihood of generating any overpressure & its magnitude. Impact of Vapor Cloud Explosions on People
VCE B, 3m/s, L- 80, W-27 0.1 bar OPR.-150 E, 1m/s, L-149, W-60 0.1 bar OPR.-220 3 LPG tank truck catastrophic failure Fire ball 138 4 Crude tank failure Pool fire 50 (from edge bund) 5 Hydrogen bullet catastrophic failure Fire ball 85 6 FCCU De-butaniser Reflux drum BLEVE 102 7 PDA Propane bullet line failure VCE B, 3m/s, L- 207, W-225 0.1 bar OPR.-600 E, 1m/s, L-289, W-407 0.1 bar OPR.-550 Igniting Minds... Energizing Lives Haldia Refinery
On-site Disaster Scenarios based on QRA Toxic Gas leak Case
Sl. Risk Scenario Outcome Consequence dist. (m) to 1% fatality 8.a)
8.b) Ammonia bullet line rupture ROV upstream Ammonia transfer line LOB to Storage: Full bore rupture Ammonia Toxic cloud
Do B, 3m/s, L- 235, W-94 E, 1m/s, L-600, W-427 B 3m/s : L-101,W-40 E 1m/s :L236 W184 9 MCC of SRU - Leakage
SO2/H2S Toxic cloud B, 3m/s, L- 91, W-22 E, 1m/s, L-293, W-102 10 H2S line to SRU full bore rupture H2S Toxic cloud B, 3m/s, L- 91, W-22 E, 1m/s, L-293, W-102 11 Failure of CO duct in FCCU Bellow rupture CO Toxic cloud B, 3m/s, L- 25.6, W-5.4 E, 1m/s, L-151, W-8.8 12 Chlorine leakage from toner Cl2 Toxic cloud B, 3m/s, L- 91, W-22 E, 1m/s, L-293, W-102 Major Contributors to Public Risks LPG storage, Ammonia storage & Chlorine toner Igniting Minds... Energizing Lives Haldia Refinery Emergency Preparedness Basic information of Disaster. Scenarios. Organization charts. Roles & Responsibilities of various coordinators. Assembly Points & control of Visitors. Dos & Donts during Emergency. Overall plot plan List of Hazardous chemicals/products Communication system Alarms & detection system Reporting system to various agencies. Resources Mobilization (Men & Materials) etc. Igniting Minds... Energizing Lives Haldia Refinery On-site Disaster Organogram Overall coordinator - ED Alternate GM(Pj) Chief coordinator GM(T) Alternate GM (TS) Incident Controller DGM (PN) Alternate DGM (TS) Fire fighting Rescue, Repair & Salvage Security Work incident De contamination Medical Water supply Communication Engg. Finance Materials / Supply Transport, Welfare & Media Igniting Minds... Energizing Lives Haldia Refinery Activity flow chart during Emergency Reporting of Emergency
Response of plant, F&S, Medical & CISF
Assessment of situation
Declaration of Major Fire/Emergency
Blowing of Major Fire Siren
Intimation to Mutual-aid Partners & State Fire Service
Reporting at site by CPNMs, CPUM, CMNMs, CITM, DGM(PN) & DGM(TS) through group communication.
Assessment of situation by Fire Chief.
Feedback to GM(T) & Declaration of Onsite Disaster
Blowing of Disaster Siren
Igniting Minds... Energizing Lives Haldia Refinery Activity flow chart during Emergency Activation of Disaster Control Room
Intimation to HQ, Dist. Admn. & Statuary authority
Controlling of situation through DMP
Assessment of situation, feedback to Chief coordinator
Depending on situation declaration of Off-site Disaster by ADM
Controlling of situation by Dist. Authority through Off-site DMP
Situation controlled & Declaration of Normalcy
Blowing of All clear siren
De-briefing session Igniting Minds... Energizing Lives Haldia Refinery Resources available for Disaster Control Disaster Control Room ( 2 nd Floor of Admn bldg) is equipped with:
Walkie talkie base station Intercom & P&T Telephones Close Circuit TV Network PC All operating manuals / Safety manuals / Lay out & Plot plan Drawings Updated list of Disaster coordinators with contact numbers Updated list of Mutual aid coordinators with contact numbers, Neighboring industries & Dist. Admn. Seating arrangement for about 20 persons
Igniting Minds... Energizing Lives Haldia Refinery Resources available Fire Protection System: Designed to meet double fire contingency as per OISD norms. Maximum water flow requirement based on LPG HS & Process plant fire case Storage: 3 x 9000 m3 above ground tanks. Makeup water: PHE, Tube wells & ETP Fire Booster Pumps: 6 X1000 m 3 /hr. [El.-3+D-3] Jockey pumps: 2 X300 m3/hr.
Igniting Minds... Energizing Lives Haldia Refinery Resources available for Disaster Control Fire Protection System: Water spray and semi fixed foam system for storage tanks as per OISD norms. Auto / Manual water spray system for storage vessels, hot pumps, light HC pumps & Transformer. Auto / Manual water spray system for TT & TW loading gantry. Fire hydrants: 810 nos. Water monitors: 193 nos. HVLRM for crude tanks: 19 nos. CO2 flooding system for GTs & TGs Igniting Minds... Energizing Lives Haldia Refinery Resources available for Disaster Control Fire Vehicles: Foam Tender: 3 Nos. DCP Tender : 1 No. DCP Skid: 1 No. Fire Jeep: 1 No. Fire fighting foam: AFFF 100 KL
Igniting Minds... Energizing Lives Haldia Refinery Resources available for Disaster Control Communication System: Manual Call Points: 359 Nos. Smoke / Heat detectors: 524 Nos HC Detectors: 85 Nos Telephone: AUTO, CENTRAX & P&T PA & Group Communication System 7 Nos. Sirens at Refinery & 2 Nos. at Township Walkie talkie( Nine channels ) Igniting Minds... Energizing Lives Haldia Refinery Resources available for Disaster Control Medical: First aid Center at Refinery with round the clock service & Ambulance facility. 30 bed hospital at Township with Ambulance. Others: Mutual aid agreement with: HPL, HBCPL & MCCPTA SCBA sets: 30,Gas mask: 50 nos. Rescue cutter & lifting bags Fire Proximity Suit: 15 Emergency Chlorine kit : 3 Igniting Minds... Energizing Lives Haldia Refinery Emergency Mock Drills Fire drill : Monthly
Onsite Disaster drill: Quarterly
Offsite Disaster drill: Yearly (conducted by Dist. Authority) Glimpses of On-Site Disaster Drill at TTL Actual disaster site Oil installations in blaze