You are on page 1of 22

2012

Automated Overhead
Introduction &
Product Offer

2
Selamat Datang!
We are here to help you learn about the
new Schneider ADVC controller: the
panel, the software, and how to use both
of them, as well as the switchgear.
There are 2 of us, here for 2 days:
Shane Caddaye Training Manager
Dong Hoang Technical Specialist
Thank you for attending this training: we
hope you enjoy it and learn as well!
Shane
Dong
3
AUTOMATED OVERHEAD

BRISBANE HEAD OFFICE
80 Schneider Road
Eagle Farm QLD 4009
Australia
Tel: +61 7 3635 7500
Fax: +61 7 3635 7560

sers@au.schneider-electric.com

QLD
Australia
Part of Infrastructure Business
4
PLN Indonesia
Indonesia
Brisbane
Distance: 5,415km / 7 hours
Makassar
Surabaya
5
1981- The Beginning - Motor Control Centers
Creation of Nu-Lec Pty Ltd.
First recloser manufacturer with fully integrated electronic devices.
1989 - Established distribution products
MV Automatic Circuit Reclosers (N-Series).
(includes the recloser controller, PTCC).
Sectionalisers and Load Break Switches.
1992 first export order for N-Series (Indonesia).
1998 new solid epoxy reclosers (U and W-Series).
2000
Schneider Electric acquired Nu-Lec Group.
2008
Release of ADVC Controller Range.
Head Office & factory relocation to Eagle Farm, QLD.
2009
Nu-Lec Industries Pty Ltd. becomes the Automated Overhead unit of the
Infrastructure Business Division of Schneider Electric.
Company History
6
Production
The reclosers factory generally runs a single shift each day of the
week for 50 weeks of the year, and produces around 30% of the
world market in reclosers.
The Eagle Farm, Brisbane site houses around 500 people, with 200
of these directly involved in the sales, production & marketing of the
reclosers suite of products.
Schneider Electric won the Queensland Engineering Excellence
Award in 2010 for Research & Development for their
ADVC Controller Range.
7
ISO 9001 Manufacturing Facility
8
The product range
ADVC Range Controller:
Compact / Ultra cabinet
setVUE / flexVUE display
WSOS5 software
N-Series / U-Series / W-Series Recloser / ACR
RL-Series Sectionaliser / LBS
9
Medium Voltage Overhead Products
Automatic Circuit Reclosers vacuum interrupter
N-Series, provides intelligent switching, up to 38kV,
SF
6
insulating gas, CT/VT on all 6 bushings
U-Series, light-weight solution, solid-dielectric,
up to 27kV, CT/VT on 3 I-side bushings
W-Series, provides automation & remote control on one-phase, 24kV
Load Break Switch (LBS) SF
6
puffer interrupter
RL-Series, Load Break Switch / Sectionaliser, up to 38kV
N-Series
RL-Series
U-Series
W-Series
Switchgear Product Offer
10
N-Series recloser - range
N-Series
System Voltage 15kV 27kV 38kV 38kV
Fault Make (RMS) 12.5kA 16kA
Fault Break 12.5kA 16kA
Continuous Current 800A 800A
Mechanical Operations 10,000 10,000
Fully insulated bushing arrangement
316 marine grade stainless steel tank
Vacuum Interrupters
SF
6
Gas insulation medium
Single pole mounting < 200 kg /440lb
LV solenoid close and trip from stored energy charged
capacitors in the ADVC controller
Voltage measurement to a 2.5% accuracy on all
6 bushings
13
RL-Series sectionaliser / LBS - range
RL-Series
System Voltage 15kV 27kV 38kV
Fault Make (RMS) 12.5kA 16kA 12.5kA 16kA 12.5kA 16kA
Fault Break - - -
Continuous Current 630A 630A 630A
Mechanical Operations 10,000 10,000 10,000
Hook Stick Operated or motorised
316 grade Stainless Steel Tank
SF
6
gas puffer interruption
Single Pole Mounting < 120 kg / 265lb
Sectionalising capability
Motor-driven over centring spring mechanism powered
by the batteries in the ADVC controller
Manual mid-pole & down-pole accessories available
14
Sulfur hexafluoride (SF
6
)
SF
6
is an inorganic, colorless, odorless, non-toxic and non-
flammable man-made gas with excellent insulating and arc-
quenching properties used in Schneider Electrics N-Series ACR
(insulation only) and also the RL-Series LBS (insulation & puffer-
type arc quenching).
The current version of the Schneider Electric document Field Service Manual
CAPM4, 5 N00-XXX describes the process & equipment for SF
6
gas filling. The
document contains a reproduction of the Material Safety Data Sheet (MSDS) for SF
6

gas, as well as the method for calculating the adjustments to the default pressure
(N-Series: 35kPa / RL-Series: 105kPa)
SF
6
has 2.5 times the dielectric strength of air, increasing up to
10 times under pressure, and is not hazardous in normal use
Schneider Electric products emit negligible SF
6
as the gas is
contained in closed systems. An extremely dense gas 5 times
heavier than air - SF
6
will pool in enclosed spaces and displace
oxygen although it can be breathed without danger, breathing
ONLY SF
6
will eventually result in death by asphyxiation.
15
ADVC Controller Range

flexVUE operator interface
20 Status Lamps
12 Quick Action Keys
setVUE operator interface
Menu-driven 4-line display
4 Configurable Quick Keys
ULTRA cubicle
316 stainless steel
2 Accessory Trays
Optional 12Ah batteries
COMPACT cubicle
304 stainless steel
Compact option for limited space
1 Accessory Tray
Controller Product Offer
16
ADVC Compact cabinet
Great where space is an issue
2 x 7Ah battery: 26hr holdup
setVUE or flexVUE display
1 x accessory mounting plate
Cabinet rated IP44*
CAPE (Control and Protection Enclosure)
rated IP65*
Multiple communication ports
DNP3 / Modbus / IEC supported
Wide range of protection features
304 stainless steel - 2-point locking
*see slide: IP Rating explained
17
ADVC Ultra cabinet
More accessory space / larger
batteries
2 x 12Ah battery option: 44hr holdup
setVUE or flexVUE display
2 x accessory mounting plates
Cabinet rated IP44*
CAPE (Control and Protection Enclosure)
rated IP65*
Multiple communication ports
DNP3 / Modbus / IEC supported
Wide range of protection features
316 stainless steel - 3-point locking
*see slide: IP Rating explained
18
IP Rating:
A rating that specifies the strength of the enclosure that houses electronic equipment:
the first digit measures the degree of protection provided against solid object, the
second number measures the degree of protection provided against liquids.
IP (Ingress Protection) rating explained
19
ADVC setVUE display
Easy transition from
the previous PTCC
interface
Menu-driven
Large 4 line x 40
character LCD display
4 user-configurable
Quick Keys
Fully integrated with WSOS5 software & all of the Schneider
Recloser / Sectionaliser range
20
ADVC flexVUE display
Flexible, fully user-
configurable interface
20 user-configurable
Status Lamps
2 line x 20 character
LCD Display
12 user-configurable
Quick Action Keys
Dedicated Event Log key
Fully integrated with WSOS5 software & all of the Schneider
Recloser / Sectionaliser range
21
WSOS5 software
The Schneider Electric proprietary WSOS5
(Windows Switchgear Operating System) allows you to configure,
access & control all of your Schneider Reclosers & Sectionalisers.
Manage your whole network remotely via your own communications
links, or use a PC locally via USB, serial or ethernet
Configure protection & communication features, SCADA protocols
(DNP3 / IEC / Modbus), and data measurement
Organise your switchgear into logical groups using the Switchgear
Explorer feature
Trip & Close, view & retrieve Event Log information and much more!
22
The Windows Switchgear Operating System (WSOS) software package
supports a variety of communications protocols that can be configured and used
with the ADVC Range of controllers:

DNP3 balanced (both master and slave can initiate communications)
IEC 60870-5-101/4 can operate as balanced or unbalanced
MODBUS unbalanced (only master can initiate communications)
MITS unbalanced (only master can initiate communications)
Communications Protocols
2012
This completes the presentation
Thank you for your attention.
24

You might also like