OPERATING COSTS ARE REDUCED BY


CHANGING PRACTICES
Best practices to reduce operating costs are:
1) Using flowmeters designed to Eliminate
Impulse Lines to minimize the need for
maintenance

2) Using Non-Mechanical Meters to minimize


maintenance costs.

3) Utilizing Predictive Maintenance to complete


maintenance only on those meters that
require it

4) Minimizing Permanent Pressure Loss


29/11/2006

Flow Meters / Manisha Na

ELIMINATING MECHANICAL METERS REDUCES


DOWNTIME AND MAINTENANCE COSTS

Large Obstruction to Wear


Moving Parts

No Obstruction to Wear
No Moving Parts

Liquid Turbine Meter Blade Wear causes inaccuracy and eventually down-time.
Blade Replacement represents almost 1/2 the price of a new meter

29/11/2006

Flow Meters / Manisha Na

ELIMINATING IMPULSE LINES REDUCES


POTENTIAL LEAK POINTS OVER 50%
Traditional Installation

Potential Leak Points = 28Pot. Leak Points = Pot. Leak Points = 5Pot. Leak Points =
8

29/11/2006

2 /4

Flow Meters / Manisha Na

MINIMISING PRESSURE LOSS

Pressure Loss
Depends on the flow technology selected
Pressure drop ranking

1. Coriolis

4. Vortex

6. Averaging Pitot

2. Orifice/Nozzle
5. Venturi

7. Mag/Ultrasonic

3. Turbine

29/11/2006

Flow Meters / Manisha Na

MAGNETIC
INDUCTIVE
FLOWMETERS

29/11/2006

Flow Meters / Manisha Narvekar

MAGNETIC FLOW METERS


PRINCIPLE
WORKING PRINCIPLE FARADAYS LAW

U=KxBxVxD
K = instrument constant
B = magnetic field strength
V = mean flow velocity
D = electrode spacing

29/11/2006

Flow Meters / Manisha Na

29/11/2006

Flow Meters / Manisha Na

29/11/2006

Flow Meters / Manisha Na

THE CONSTRUCTION OF THE FLOW HEAD:

A measuring tube
A liner
A pair of electrodes
A pair of field coils
A magnetic shielding
A housing

29/11/2006

Flow Meters / Manisha Na

10

The signal voltage is picked up by electrodes that are in

conductive contact with process fluid & insulated from the


tube wall.
Flow rate is

The signal voltage Ui is converted by signal converter into


flow indication qi

And converted into standardized signals appropriate to the


process

29/11/2006

Flow Meters / Manisha Na

11

SELECTION OF MAG-METER OVER UFM

29/11/2006

Flow Meters / Manisha Na

12

SUITABLE INSTALLATION LOCATION

29/11/2006

Flow Meters / Manisha Na

13

MAGNETIC FLOW SENSOR


INSTALLATION GUIDELINES

29/11/2006

Flow Meters / Manisha Na

14

NEED OF GROUNDING

29/11/2006

Flow Meters / Manisha Na

15

Terms explained

29/11/2006

Flow Meters / Manisha Na

16

ADVANTAGES OF A MAGMETER
liner

No parts inside:

tube

Same diameter as mating


pipe:

Electrode

No moving parts:
With the liner we achieve..

29/11/2006

Flow Meters / Manisha Na

17

Contd...
The magnet field is present

flow strings

throughout the total


flowmeter.

VS
US

Result:
Excellent avaraging of the
flow profile allover the
complete pipe section.
Reduced effect of the
velocity profile onto the
measuring accuracy !

magnet field lines

29/11/2006

Short upstream straight


section required!

Flow Meters / Manisha Na

18

APPLICATION CRITERIA :
1)

Conductivity of the liquid.

2)

Effect of liquid operating temperature

3)

Magnetic flow meter must always be full

4)

Liquid should not contain entrained gases.

5)
Periodic cleaning is required if build-up is
there.
6)
Temperature limitation of a particular lining
material to be considered.
29/11/2006

Flow Meters / Manisha Na

19

CORIOLIS
FLOW METER

29/11/2006

Flow Meters / Manisha Na

20

MEASURING PRINCIPLE

The measuring principle is based on the


controlled generation of Coriolis Forces.
These forces are always present when
both translational and rotational
movements are superimposed.

29/11/2006

Flow Meters / Manisha Na

21

CHANGE IN PHASE SHIFT DUE TO TUBE


OSCILLATIONS

29/11/2006

Flow Meters / Manisha Na

22

CONSTRUCTION

29/11/2006

Flow Meters / Manisha Na

23

CHANGE IN PHASE SHIFT

29/11/2006

Flow Meters / Manisha Na

24

SELECTION OF CORIOLIS OVER ORIFICE

29/11/2006

Flow Meters / Manisha Na

25

PROCESS CONDITION

29/11/2006

Flow Meters / Manisha Na

26

ADVANTAGES :
1) A wide range of fluids that are often incompatible
with other flow measurement devices.
2) Independent of Reynolds number.
3) Coriolis flowmeters provide a direct mass flow
measurement .
4) Coriolis flowmeters have outstanding accuracy.
5) The rangeability of the flowmeters is usually on the
order of 20:1 or greater.
29/11/2006

Flow Meters / Manisha Na

27

Contd
5) A Coriolis flowmeter is capable of measuring
mass flow rate, volumetric flow rate, fluid density
and temperature - all from one instrument.

6) The operation of the flowmeter is independent


of flow characteristics such as turbulence and
flow profile.

7) Coriolis flow meters do not have internal


obstructions.
29/11/2006

Flow Meters / Manisha Na

28

LIMITATIONS :
1) Coriolis flowmeters are not available
for large pipelines.
2) Coriolis flowmeters are expensive.
3) Coriolis flow meters have difficulty
measuring the flow rate of low
pressure gas.

29/11/2006

Flow Meters / Manisha Na

29

ULTRASONIC
FLOW METER

29/11/2006

Flow Meters / Manisha Na

30

INTRODUCTION
1) Acoustic signals are transmitted and

received along a diagonal measuring path.

2) A sound wave going downstream with the


flow travels faster than a sound wave
going upstream against the flow.

3) The difference in transit time is directly


proportional to the flow velocity of the
liquid.
29/11/2006

Flow Meters / Manisha Na

31

THEORY OF OPERATION

Pulse transit times


measured
upstream &

Time difference t
downstream
proportional
to flow velocity V
Actual volume rate
from
V x cross-sectional
area
Pressure & Temperature inputs used to
compute ,
Standard Volume & Mass flow rates
Time over distance so timing and dimensions
are critical
to flow meter performance
29/11/2006

Flow Meters / Manisha Na

32

DIFFERENCE IN TRANSIT TIME

D = Pipe Diameter

Sensor
A

Transducer & Receiver of Acoustic Signals

Cm = Velocity of Sound

Flow velocity

Acoustic Signals

29/11/2006

Sensor
B

Flow Meters / Manisha Na

33

CALCULATION OF FLOW VELOCITY


Transit time = Distance
Speed
Transducer A
Downstream Sensor A to B

Cm
Vm

D
L

TA B

V cos

L
C + V cos

Upstream Sensor B to A

Transducer B
D =
L =
Vm =
Cm =

TBA

L
C - V cos

Pipe diameter
Acoustic path length
Flow velocity medium
Velocity of sound medium
29/11/2006

Flow Meters / Manisha Na

34

ULTRASONIC FLOW METERING-BY


METER TYPE
Flowmeters
Liquid

Gas / Steam

Wetted Clamp-on Portable

Wetted Clamp-on Portable

29/11/2006

Flow Meters / Manisha Na

35

ULTRASONIC FLOW METERING


THE ANATOMY: WETTED

Electronics or
Transmitter
Cables
Flowcell
Transducer
Preamplifiers (Gas
only)
29/11/2006

Flow Meters / Manisha Na

36

ULTRASONIC FLOW METERING


THE ANATOMY: CLAMP-ON

Electronics or Transmitter
Cables
Clamping Fixture
Transducer
Preamplifiers (Gas only)

29/11/2006

Flow Meters / Manisha Na

37

ULTRASONIC FLOW METERING-WETTED


INSTALLATION VS. CLAMP ON

Accuracy
Maintenance costs
Installation costs
Installation existing
pipes
Equipment costs
Temperature Range
Application to gas
Difficult Liquids
Leaks Paths
29/11/2006

Wetted

Clamp-On

<0.5%

1 2%

Near Zero

Low

Higher (Package)

Low

Tapping only

Yes no cutting
pipe

Higher

Lower

-200 to 600 deg C

-40 to 210 deg C

Straightforward

Challenging

Preferred
Yes
Flow Meters / Manisha Na

No
38

BWT TECHNOLOGY
Buffer Technology
Developed for:
High and Low Temperature
-200 to 600C
High Pressure
up to 500 bar
Attenuative fluids
High Viscosity up to
1000 cSt
Over wide range of
diameters

-200 to 600C

Piezoelemen
t
100C

Buffer

-200 to 600C
Traditional Buffer
Piezoelemen
t
100C

Buffer

Fiber Acoustics
29/11/2006

Piezoelement

Flow Meters / Manisha Na

-200 to 600C
Fiber acoustic Buffer

39

BWT TECHNOLOGY
The solution:
No Solid Rod but Fiber Acoustics named: BWT
Bundle Waveguide Technology System

Cool Piezoelement

Fiberacoustic Bundle
or waveguide

Hot Fluid

Sound

Flange
29/11/2006

Flow Meters / Manisha Na

40

BWT TECHNOLOGY
Signal Comparison
Solid Buffer
25.4 mm
Elongated Signal

Received Signals

Transmitted Signal

BWT buffer
Sharp Clean Signal

29/11/2006

Flow Meters / Manisha Na

41

SELECTION OF UFM OVER


ORIFICE

29/11/2006

Flow Meters / Manisha Na

42

PROCESS CONDITION

29/11/2006

Flow Meters / Manisha Na

43

SELECTION OF UFM OVER CORIOLIS

29/11/2006

Flow Meters / Manisha Na

44

ADVANTAGES
Non intrusive
No moving parts

- no wear
- no pressure loss
- no clogging
Fluid properties have no effect on performance
For conductive and non-conductive mediums
High accuracy over wide measuring range
High turndown ratio
Starts measuring from zero flow
Bi-directional
29/11/2006

Flow Meters / Manisha Na

45

SPECIFICATION SHEET FOR MAG-METER

29/11/2006

Flow Meters / Manisha Na

46

29/11/2006

Flow Meters / Manisha Na