Professional Documents
Culture Documents
Protection
Lecture-11
Dr. Muhammad Kamran
Lecture contents
Discrimination of fault
The advantage of this method of relay Coordination may be best illustrated by the
system shown in (Fig.a)
In order to carry out a system analysis, before a
relay co-ordination study of the system shown
in (Fig. a), it is necessary to refer all the system
impedances to a common base and thus, using
10 MVA as the reference base, we have:
Assignment / Solution
In order to carry out a system analysis, before a relay co-ordination
study of the system shown in (Fig. ), it is necessary to refer all the
system impedances to a common base and thus, using 10 MVA as
the reference base, we have: 4MVA transformer percentage
impedance on 10MVA base=7X (10/4) =17.5%
11 kV cable between B and A percentage impedance on10 MVA
base= (0.04 X 100 X 10) / 112= 0.33%
11 kV cable between C and B percentage impedance on 10 MVA
base
= (0.24 X 100 X10) /112 =1.98 %
30 MVA transformer percentage impedance on 10 MVA base
=22.5 X 10 / 30 =7.5 %
132 kV overhead line percentage impedance on10 MVA base
= (6.2x100x10)/ 1322 =0.36%
132 kV source percentage impedance on 10 MVA base= (100 x
10) /3500 =0.29%
Substation B
CT ratio 250/5A Relay over current characteristic
assumed to be extremely inverse, as for the type
CDG 14 relay. This relay must discriminate with the
200A fuse at fault levels up to:(10 x 100) /
(17.5+0.33+1.98+7.5+0.36+0.29) = 35.7 MVA
That is, 6260 A at 3.3kV or 1880 A at 11 kV. The
operating characteristics of the CDG 14 relay show
that at a plug setting of 100%, that is, 250 A and
4.76 MVA at 11 kV, and at a time multiplier setting
of 0.2, suitable discrimination with the 200 A fuse is
achieved
Substation C
CT ratio 500/5A Relay over current characteristic assumed
to be extremely inverse, as for the type CDG 14 relay. This
relay must discriminate with the relay in substation
B at fault levels up to:
(10 X 100) / (1.98 +7.5 +0.36 +0.29) = 98.7MVA
That is, 17,280 A at 3.3kV or 5180 A at 11 kV
The operating characteristics of the CDG 14 relay show
that at a plug setting of 100%, that is, 500 A and 9.52
MVA at 11 kV, and at a time multiplier setting of 0.7,
suitable discrimination with the relay at substation B is
achieved.
Substation D
CT ratio 150/1A Relay over current characteristic
assumed to be extremely inverse, as for the type CDG 14
relay
This relay must discriminate with the relay in substation
C at fault levels up to
(10 X 100) / (7.5 + 0.36 + 0.29) = 123 MVA
That is, 21,500 A at 3.3kV or 538 A at 132 kV. The
operating characteristics of the CDG 14 relay show that
at a plug setting of 100%, that is, 150 A and 34.2 MVA at
132 kV and at a time multiplier setting of 0.25, suitable
discrimination with the relay at substation C is achieved.
Substation E
CT ratio 500/1 A Relay over current
characteristic
assumed
to
be
extremely inverse, as for the type
CDG 14 relay
This relay must discriminate with the
relay in substation D at fault levels
up to:
(10 x 100) / (0.36+0.29) = 1540
MVA
Operating Characteristics
1 1
2 2
3 1 2
Directional Type
The directional type of current-balance
relay uses a current-current directional
element in which the polarizing quantity is
the vector difference of two currents, and
the actuating quantity is the vector sum of
the two currents
If we assume that the currents are in
phase, and neglect the effect of the control
spring, the torque is:
T=K1(I1+I2)(I1-I2)
Differential Relay
Differential relays take a variety of forms, depending
on the equipment they protect
The definition of such a relay is one that operates
when the vector difference of two or more similar
electrical quantities exceeds a predetermined
amount
It will be seen later that almost any type of relay,
when connected in a certain way, can be made to
operate as a differential relay
In other words, it is not so much the relay
construction as the way the relay is connected in a
circuit that makes it a differential relay
Next Lecture
Directional relay continued
Presentation on
assignment/discussion