Air Conditioning

Planning

Requirements
The job of a refrigeration plant is to cool articles or
substances down to, and maintain them at a temperature
lower than the ambient temperature. Refrigeration can be
defined as a process that removes heat.

Foodstuff conservation
Process refrigeration
Air conditioning plants
Drying plants
Fresh water installations
Refrigerated containers
Heat pumps
Ice production
Freeze-drying
Transport refrigeration

There are
countless
applications for
refrigeration
plants now.
Examples are:

Refg Cycle

Refrigerants
R134a, which is a substance
of the ethane group with
the formula CH2FCF3 and has
a normal boiling point of
26.1 C.
R22, which is a substance of
the methane group with the
formula CHF2CI and has a
boiling point of 40.8 C.
R404A/R507A (also known
as R507), which is a
mixture of the refrigerants
R125 (CHF2CF3) and R143a
(CH3CF3) with a boiling point
at (46.7 C) which is slightly
lower than for R22.

R407C, which is a mixture of


the refrigerants R32
(CH2F2), R125 (CHF2CF3)
and R134a (CH2FCF3) with a
boiling point at (43.6 C)
which is slightly lower than
for R22.
R410A, which is a mixture of
the refrigerants R32 (CH2F2)
and R125 (CHF2CF3) with a
boiling point at (51.4 C)
which is lower than for R22.
Its thermodynamic properties
make it suitable as a
refrigerant for medium and
high temperature applications
in residential and commercial
air conditioning.

Refg Cycle

Split AC

Central AC Plants
Direct
Expansi
on Type

Chilled
water
Type

Chilled Water AC Plant

AC Plant Description
Supply, install, test & commissioning of Microprocessor controlled Water-cooled screw Chiller
Type Air conditioning plant of capacity full load
not less than 160 TR and with 1 x 80 TR as
stand by to meet 50% of full load capacity of heat
load suitable for complete operation with
refrigerant R-22 with all equipments and
accessories complete for Service support centre
at AF Station x to meet the inside design
condition of temp 22 + 20C and relative humidity
60 + 10% and technical parameters as per
annexure D attached and comprises of the
followings :-

AC Plant Description

Note :- (i)The tenderer should ascertain the correctness of heat


load calculations and technical parameters given in Annexure D
based on the building plan outside/inside parameters and design
parameters as given in the tender and quote accordingly.
(ii)The tenderer shall be responsible for the plant to meet the
design condition round the clock on 24x7x365 basis irrespective of
the full load capacity given in the schedule, which is given on not
less than basis.
(iii) The tenderer should got the plant installed by any of the
original manufacturer viz Voltas/Blue star /carrier with their
recommended makes of complete components/items.
(iv)In case of any change in the technical parameter given in
.Annexure D, to provide the design parameters the tenderer
should furnish the same along with tender.

Chiller Plant Description


(A) Three Nos water cooled screw Chilling units complete and each comprising
of the following :(i) Screw compressor, hermetically
sealed type directly coupled with
refrigerant cooled squirrel cage induction motor to run on 3 phase 50 HZ
440 volt as per tech detail attached in annexure D complete with suction
and discharge piping, automatic capacity control with thermostat, suction
strainer, crank case heater, compressor oil, internal overload trip, safety
switch with gauge panels complete with HP/LP cutouts, anti freeze and
refrigerant cooled motor as specified.
(iii) One No shell and tube type water cooled condenser with MS shell and
integrally finned copper tubing, complete with safety valves, drain valve,
water inlet and outlet valves, hot gas inlet and liquid outlet isolating valves
thermometer and pressure gauges at inlet and outlet and purge valves all
as specified and as per technical specification attached in annexure D.
(ii)one No shell and tube type direct expansion chiller units having plain
copper tubes all as specified ad as per manufacturers design.
(iv) One no stand fabricated of suitable size duly painted with two coats of
black synthetic enamel paint over one coat of red oxide primer for
mounting compressor, motor, and condenser etc of above specification.

Chiller Plant Description


(vi) Refrigerant piping complete will all required fittings and
accessories with necessary bracket and support to interconnect
compressor, cooler, condenser and expansion valves including
insulation of suction lines with fire resisting insulating material of
adequate thickness as per manufacturers specifications.
(vii) Micro processor based control comprising for following
features :

(a) Automatic capacity control reducing energy consumption.


(b) Micro processor controlled pump down system.
(c) Micro processor based sequence of starting/stopping of equipment
with fixed time delays.
(d) Alarm history giving cause of tripping.
(e) Data scanner system including operating constitutions.
(f) Oil pressure failure cut out LP/HP cut out.
(g) Liquid line indicator.

Chiller

Compressor

Compressor

Expansion Valve

Expansion Valve

Cooling Tower

AHU & Ducts

AHU & Ducts