Seminar On Standby Batteries


2003, Exide Industries Limited. All rights reeserved.

Selection Of Batteries For Generating


Station And Substation

Exide Industries
Limited

Application :
Unit Battery
Substation Battery
PLCC
24/26v C & I Battery
UPS Battery
Battery for VHF set

September
9, 2015
2003, All rights reeserved.

Battery Is Considered To Be The


HEARTOf The Power Plant
Battery provides the ultimate and final DC backup for operating emergency equipments which
power the turbo generators (viz. emergency oil
pumps etc.)
DC power for operation of all switchgear,
protection relays, indicating lamps and facia
Power for emergency lighting within the
generating station building
Uninterrupted power for controlling C & I
equipment and associated ups systems
Power for vital communication equipment (plcc),
essential for resynchronising the unit with the grid
or for reviving the grid in the case of a major grid
failure

Exide Industries
Limited

September
9, 2015
2003, All rights reeserved.

What If The Battery Fails In An


Emergency ?

Exide Industries
Limited

Unit Battery
The emergency oil pump will not operate which
could lead to seizure of the rotor bearings
Loss of hundred of crores of rupees towards
repairing the rotor and generation revenue loss
while the unit is out of commission
Switchgear associated with generator may not trip
which could lead to generating transformer
damage
Failure of instrumentation and control
Total darkness in the powerhouse

September
9, 2015
2003, All rights reeserved.

What If The Battery Fails In An


Emergency ?

Exide Industries
Limited

Substation
Switchgear and relays will not operate causing
extensive damage to transformers and power lines

PLCC
Extremely difficult to resynchronise the unit with the
grid
Major setback in the process of reviving the grid in
the event of a regional grid failure
If the battery fails while the unit is in operation, it
may become essential to shutdown

September
9, 2015
2003, All rights reeserved.

The Single Most Important Feature Of


Batteries For Power Sector Application Is

Exide Industries
Limited

Reliability
Reliable standby power source
Deliver power as and when called for
Full capacity at any point of time in service life
Predictability

September
9, 2015
2003, All rights reeserved.

What Is A Battery ?

Exide Industries
Limited

A battery is an array of similar electrical


storage cells

September
9, 2015
2003, All rights reeserved.

What Is an Electrical Storage Cell ?

Exide Industries
Limited

An electrical storage cell consists of two dissimilar


electrodes immersed in an electrolyte.
It stores electrical energy in form of chemical
energy.
When the circuit is made between its positive &
negative electrodes, there is a chemical reaction
in the cell and it delivers electricity Direct
Current (D.C) through the circuit.

September
9, 2015
2003, All rights reeserved.

Family Tree Of Electrical Storage Cells

Primary Cell
Litihium
Oxide

Ammonium
Chloride

Exide Industries
Limited

Secondary Cell
Silver
Oxide

Alkaline
Cells
Ni Cad

Lead Acid
Cells
NiFe
SLI or
Industrial
Automotive

Standby

VRLA Fiat Pasted Tubular Plant

Motive Power

Traction
Lighting

Train
Starter

Diesel

EMU

10

September
9, 2015
2003, All rights reeserved.

What Is A Lead Acid Battery ?

Exide Industries
Limited

Basic electrochemical reaction participants :


_

LEAD DIOXIDE

SOFT LEAD

H2S04 - ELECTROLYTE

Positive Electrode

PbO2

Negative Electrode

Pb

Electrolyte

H2SO4

11

September
9, 2015
2003, All rights reeserved.

How Does A Lead Acid Battery Work ?

Charged
+ve

-ve

Pbo2 +

Pb

Lead
Spongy
Peroxide Lead

Exide Industries
Limited

Discharged
electrolyte
+ 2H2SO4
Dilute
SulphurAcid

+ve

-ve

PbSO4 + PbSO4 + 2H2O


Lead
Lead
Sulphate Sulphate

Water

12

September
9, 2015
2003, All rights reeserved.

Types Of Plates

Exide Industries
Limited

A. Positive

Plant Type :

Cast out of 99.99% pure Lead


has a fine lamaellar structure

Flat Pasted Type

Grid holds the active material and


carries the current

Tubular Type :

Red lead (Pb3O4) and Grey


oxide (PbO) mixture is filled
in tubes and spine of leadalloy runs through the centre of
entire tube length. Tube retails
the active material firmly and
spine carries the current

B. Negative

Flat pasted type always

13

September
9, 2015
2003, All rights reeserved.

Flat Pasted Plate - Morphology

Exide Industries
Limited

THE SUPPORT STRUCTURE IS IN


THE FORM OF A WIRE-MESH LIKE
GRID CAST OF A SUITABLE LEAD
ALLOY

THE ACTIVE MATERIAL IS PASTED


ON THE GRID STRUCTURE FROM
OUTSIDE

A CHEMICAL BONDING HOLDS THE


ACTIVE MATERIAL IN PLACE
THROUGHOUT THE SERVICE LIFE

14

September
9, 2015
2003, All rights reeserved.

Features Of Automotive Flat Plate

Grid
Active Material

Exide Industries
Limited

: (Current Collector) cast into a lattice


structure
: Pasted on to the lattice

Suited For :
High current discharge
Short backup time (Shallow) discharge
Non-cyclic application

15

September
9, 2015
2003, All rights reeserved.

Tubular Plate

Exide Industries
Limited

LUG

TUBE

BOTTOM BAR
CONSTRUCTION OF TUBULAR
POSITIVE PLATE

16

September
9, 2015
2003, All rights reeserved.

Cross-Section Of Tubular Plate

Exide Industries
Limited

RESIN SHEATH

SPINE

ACTIVE MATERIAL

TUBE

SPINE (LEAD ALLOY)

ACTIVE MATERIAL
(LEAD OXIDE)
TUBE
RESIN CURED
(TERYLENE GAUNTLET)

BOTTOM BAR

SECTION YY

SECTION XX

CONSTRUCTION OF TUBULAR POSITIVE PLATE (contd.)

17

September
9, 2015
2003, All rights reeserved.

Tubular Positive Structure

Exide Industries
Limited

THE SUPPORT STRUCTURE IS IN


THE FORM OF CAST ROD
ELECTRODES CALLED SPINES
JOINED AT THE TOP BY A BUS BAR
INDIVIDUAL SPINES ENGULFED IN
A MICROPOROUS PLURITUBULAR
GAUNTLET
ANNULAR SPACE BETWEEN SPINE
AND GAUNTLET FILLED WITH
ACTIVE MATERIAL (PbO2). BOTTOM
OF THE GAUNTLET SEALED WITH
A PLASTIC PLUG CALLED BOTTOM
BAR

18

September
9, 2015
2003, All rights reeserved.

Plante Positives Unique Structure

Exide Industries
Limited

PLANTE HAS THE MOST UNIQUE


STRUCTURE AMONGST ALL THE
VARIATIONS OF POSITIVE PLATES
CAST OF 99.99% PURE LEAD WITH
NO ALLOYING ELEMENT.
LAMELLAR GRID CONSTRUCTION
ENHANCES SURFACE AREA
LARGELY;
EFFECTIVE SURFACE AREA 12 TIMES
THAT OF GEOMETRIC SURFACE
AREA
NO EXTERNAL ADDITION OF ACTIVE
MATERIAL. GRID SURFACE
CONVERTED TO PbO2 THROUGH
CONTROLLED CORROSION
REACTION DURING PLATE
PROCESSING

19

September
9, 2015
2003, All rights reeserved.

Plante Positive Plate

Exide Industries
Limited

20

September
9, 2015
2003, All rights reeserved.

Plante Negative Plate

Exide Industries
Limited

21

September
9, 2015
2003, All rights reeserved.

SAN Container

Exide Industries
Limited

22

September
9, 2015
2003, All rights reeserved.

Plante .. Salient Features

Exide Industries
Limited

Excellent Discharge Profile


Very Low Maintenance
Fast Recharge and Possibility Of High Rate Of
Charging
No Loss In Capacity Throughout its Life Span
Long Life expectancy Of 15-20 Years In Float
Application
Transparent Container : Easy Visual Monitoring

23

September
9, 2015
2003, All rights reeserved.

Plante Low Maintenance

Low Topping Requirement Achieved Through


Antimony Free Ultra Pure Lead
Very low equilibrium float current
Very low water loss Low Topping Requirement
Achieved Through
No Leachable Impurity
No poisoning of negative
Negligible rise in equilibrium float current during
entire service life
Huge pool of electrolyte
Excellent thermal management
Makes up for lost water
TOPPING UP ONCE IN 12 18 MONTHS

Exide Industries
Limited

24

September
9, 2015
2003, All rights reeserved.

Plante - No Loss In Capacity

Exide Industries
Limited

Continuous regeneration of active material


Total Lead-di-oxide content fairly constant
throughout the life span indicating a constant
capacity output
Lowering of internal resistance due to thinning
Of parent material may expect higher capacity
Appreciation as the cell ages
Thus consideration of life factor in capacity
Not necessary as accepted by IEEE 485 : 1997

25

September
9, 2015
2003, All rights reeserved.

Plante Long Life

Exide Industries
Limited

Very thick positive enough


Cushion against corrossion
Low susceptibility to overcharge due to very low
equilibrium float current of the order of 1mA/AH
Under normal float condition
Low float current and high purity of lead
Lowers the corrossion rate
Life expectancy of around 15 years plus

26

September
9, 2015
2003, All rights reeserved.

Plante Easy Monitoring

Exide Industries
Limited

Transparent SAN (STYRENE ACRYLO NITRILE)


Container easy visual monitoring of cell inside
Any odd behaviour can be monitored and corrected
much before it shows up as a failure mode
Easy cleaning of cells from unavoidable sludge
deposition to avoid short circuit and related
troubles

Reliability - Reiterated

27

September
9, 2015
2003, All rights reeserved.

Exide Plant Range

Exide Industries
Limited

PLANT RANGE COMES IN 2V


CONFIGURATION ONLY

YAMP SERIES

16 Ah 64 Ah

YKP SERIES

75 Ah 400 Ah

YHP SERIES

535 Ah 2250 Ah

28

September
9, 2015
2003, All rights reeserved.

Plant Cells

Exide Industries
Limited

29

September
9, 2015
2003, All rights reeserved.

Maintenance

Exide Industries
Limited

Topping up
Charging
Checking and cleaning of terminals
In a lead acid battery, charging & cleaning /
checking of terminals cannot be avoided

30

September
9, 2015
2003, All rights reeserved.

Maintenance

Exide Industries
Limited

TOPPING UP

WATER LOSS

ELECTROLYSIS

EVAPORATION

DIRECTLY PROPORTIONAL
TO ANTIMONY CONTENT IN
THE PLATE

31

September
9, 2015
2003, All rights reeserved.

Low Maintenance

Exide Industries
Limited

How Is It Achieved ?
Low antimony alloy.
Less Electrolysis - low water loss
Microporous vent plug
Bigger Container with more electrolyte / high acid
head room

32

September
9, 2015
2003, All rights reeserved.

Microporous Ceramic Vent Plug

Exide Industries
Limited

33

September
9, 2015
2003, All rights reeserved.

Ceramic Dome

Exide Industries
Limited

34

September
9, 2015
2003, All rights reeserved.

What Is VRLA ?

Exide Industries
Limited

Valve regulated lead acid battery known to


common users as
Sealed maintenance free battery
Operates with a safety for escape of gasses
unavoidably generated during operation

35

September
9, 2015
2003, All rights reeserved.

SMF VRLA Batteries

Exide Industries
Limited

No free electrolyte. Electrolyte is kept absorbed in glass


mat separators
Insufficient buoyancy for oxygen gas to travel upward by
negative gravitation
Oxygen travels horizontally & reaches negative plate to
react with metallic lead

36

September
9, 2015
2003, All rights reeserved.

Venting Arrangement Of A VRLA Battery

Exide Industries
Limited

37

September
9, 2015
2003, All rights reeserved.

Why VRLA ?

Exide Industries
Limited

Sealed ! Can be kept in any orientation


No topping up required ever
A zero emission product
Battery comes charged
Compact

38

September
9, 2015
2003, All rights reeserved.

The Sealed Maintenance Free VRLA


Battery

Exide Industries
Limited

INHERENT
ADVANTAGES

Battery is delivered ready to use


No topping-up required ever
Zero emission under normal charging conditions
Compact
Low foot-print
Easy to handle

39

September
9, 2015
2003, All rights reeserved.

Vulnerabilities

Exide Industries
Limited

High temperature
Deep discharge
Cycling
Charge sensitive
Recovery from over discharge
Thermal Runaway and Dry out
Unpredictability

40

September
9, 2015
2003, All rights reeserved.

Selection Criteria Of A Battery

Exide Industries
Limited

Primary Factors

Current load
Backup time
Minimum voltage requirements of the system
The lowest excepted operating temperature

41

September
9, 2015
2003, All rights reeserved.

Selection Criteria Of A Battery

Exide Industries
Limited

Secondary Factors

Expected frequency of discharge


Depth of discharge
Ambient temperature
Method of charging, constraint if any
Limitation on space
Maintenance limitation
Floor loading

42

September
9, 2015
2003, All rights reeserved.

Technical Comparsion
Nominal

Voltage

Tubular

2V

VRLA

2V

Plant

2V

Ni-Cd

1.2V, 183 cells of Ni-Cd are required for a 220V


system where 110 cells of Lead Acid are

Exide Industries
Limited

used
Sensitivity to overcharge & undercharge
Tubular

Quite Sensitive

VRLA

Very Sensitive

Plant

Quite Sensitive

Ni-Cd

Moderately Sensitive

43

September
9, 2015
2003, All rights reeserved.

Technical Comparison

Exide Industries
Limited

RECHARGE
Tubular

Capable of quick recharge by boost


charging upto 2.7vpc and 0.14 C10
Amps recharge current

VRLA

Quick recharge limited to fast charging


upto 2.4vpc and 15-20% of limit current

Plant

Very fast recharge by boost charging


upto 2.7vpc and 0.25 C10 Amps
recharge current

Ni-Cd

Capable of very fast recharge,


however charge retention is relatively
poor

44

September
9, 2015
2003, All rights reeserved.

Technical Comparison

Exide Industries
Limited

SUSCEPTIBILITY TO HIGH TEMPERATURE


NDP Tubular

Satisfactory operations upto


48/500C electrolytic temperature

VRLA

Prolonged operation at high


ambient temperature curtail battery
life severely.

Plant

Satisfactory operations upto


48/500C electrolytic temperature

Ni-Cd

Satisfactory operations upto


48/500C electrolytic temperature

45

September
9, 2015
2003, All rights reeserved.

Technical Comparison

Exide Industries
Limited

Discharge At Float Operations


Tubular

Satisfactory

VRLA

Best

Plant

Satisfactory

Ni-Cd

Ni-Cd does not give full


capacity when discharged after
remaining on float for a long
time. In order to obtain the
desired capacity,the capacity of
the battery needs to be
increased by 35%

46

September
9, 2015
2003, All rights reeserved.

Technical Comparison

Exide Industries
Limited

MONITORING STATE OF CHARGE


Tubular

Can be done by measuring electrolyte


specific gravity

VRLA

Cannot be determined externally, acts as


a black box

Plant

Other than measuring electrolytic specific


gravity, battery condition can be
monitored visually through the transparent
containers

NI-CD

Cannot be determined externally, acts as


a black box

47

September
9, 2015
2003, All rights reeserved.

Technical Comparison

Exide Industries
Limited

AGEING
Tubular

Degrades gradually during service life &


falls to about 80% in 8-10 years. 25%
capacity has to be increased to
compensate for ageing

VRLA

Degrades gradually during service life &


falls to about 80% in 10-15 years. 25%
capacity has to be increased to
compensate for ageing

Plant
Ni-Cd

Plant capacity does not drop rather


increases in service life
Capacity remains almost constant during
service life

48

September
9, 2015
2003, All rights reeserved.

Technical Comparison

Exide Industries
Limited

RELIABILITY
Tubular

Quite reliable

VRLA

Generally reliable however prone to


unexpected malfunctioning

Plant

Most reliable in float operations

Ni-Cd

Reliable during routine duty cycles


however prone to unexpected
malfunctioning during
emergency requirement

49

September
9, 2015
2003, All rights reeserved.

Technical Comparison

Internal Resistance
NDP Tubular Highest
VRLA
Lowest
Plant
30-40%lower than
equivalent HDP
Tubular Cells
Ni-Cd
Low

Life Expectancy

15
10
5

TUBULAR

VRL
VRLA

Plante

Ni-Cd

Internal
Resistance

Life Expectancy
Tubular
10-12 years
VRLA
8-10 years
Plant
15-20 years
HDP Tubular 10-12 years
Ni-Cd
15-20 years

Exide Industries
Limited

TUBULAR

50
VRLA

Plante

Ni-Cd

September
9, 2015
2003, All rights reeserved.

Technical Comparison

Exide Industries
Limited

Topping Up Requirement
Tubular Topping up upto 3-4 times in a year
VRLA No topping up required

Plant Topping up once in 12-18 months


Ni-Cd

Topping up once a year. Existing


electrolyte needs to be changed every
7-8 years

Auto- Fill Systems Removes The Need Of


Topping Up
4

3
N o . o f tim e s / y e a r

Routine maintenance is
required for all categories
of batteries

51

September
9, 2015
2003, All rights reeserved.

Myths Of VRLA Batteries

Exide Industries
Limited

Myth 1 VRLA batteries require no maintenance


Reality
As per the Clause No. 5.7 of IEEE 1189-1996
By the very nature of the designs of VRLA cells,
specific gravity readings and water additions are
not practical. Consequently, the batteries are often
referred to as maintenance free. However, this is
true only with respect to the electrolyte. Otherwise,
VRLA battery maintenance is similar to that require
for flooded batteries.
There exists an IEEE standard (IEEE 1188-1996)
which is dedicated for maintenance and testing of
VRLA batteries

52

September
9, 2015
2003, All rights reeserved.

Myths Of VRLA Batteries

Exide Industries
Limited

Myth 2 VRLA batteries can be used in tropical


climate at high temperatures without any adverse
effects
Reality
As per Clause No. B.3 of annexure B of IEEE
1188-1996
As a general rule, continuous prolonged use at
elevated temperatures will reduce the batteries life
by approximately one-half for every 80C above 250
C that VRLA Batteries operate. This effect can be
mitigated to some extent by the use of temperature
compensated charges. Operation at elevated
temperatures can also lead to thermal runaway.

53

September
9, 2015
2003, All rights reeserved.

Myths Of VRLA Batteries

Exide Industries
Limited

Myth 3 VRLA batteries do not have the same


failure mechanisms as flooded
Reality
As per Clause No. 5.3 of IEEE 1189-1996
The familiar failure mechanisms of positive plate
corrosion and growth, active material failure, post
seal leakage and container / cover seal leakage
associated with vented cells are also present in
VRLA cells. However, in VRLA cell the effects of
leakage at the post and / or container cover seals
are more significant than in vented cells.
VRLA cells are susceptible to two failure modes
that are normally not associated with vented cells.
These are dryout and thermal runaway

54

September
9, 2015
2003, All rights reeserved.

Why Then VRLA ?

Exide Industries
Limited

Telecommunications & UPS applications product


attributes secondary requirement
Small Foot Print
No Emissions
No Maintenance

55

September
9, 2015
2003, All rights reeserved.

Power Stations

Exide Industries
Limited

Product Attributes Required


Reliability
Deliver power as and when called for and full
capacity at any point of time in service life

Predictability

Health
Impending Failure
Expected Time Of Replacement
Time Tested
Life

56

September
9, 2015
2003, All rights reeserved.

Application
Our Recommendation

Exide Industries
Limited

NDP TUBULAR

VRLA

Ideal for frequent


Charge /
discharge
cycling duties

For relatively
Short time backup
with moderate
depth of discharge
Plant
PLANTE

Ideal for meeting duty


cycle in float operation
HDP TUBULAR

NI-CD

Ideal for frequent


charge/discharge
cycling duties

Can be used in high


rate of discharge in
abusive conditions

57

September
9, 2015
2003, All rights reeserved.

The Trade-Off

Exide Industries
Limited

There is no lead acid battery with the best


product attributes in all the categories of
attributes
A trade-off has to be made for each
application segment considering the
requirements of that segments
Best battery for
power application PLANTE

Best battery for


Telecom application
- VRLA

58

September
9, 2015
2003, All rights reeserved.

JUNE 200

June 2003