Professional Documents
Culture Documents
Hot Temperature
No1 Killer: Dry out
No2 Killer: Grid
Corrosion
No3 Killer: Bulge
Rectifier faults
Description
Rectifier Setting
1
2
3
4
5
U1-Normal
U2-Boost
U3-Test
U4-Spare
AH Limit for Test
54.5
56.4
46
54.5
500
6
7
8
9
10
11
12
13
14
15
16
47.3
46
58.5
59.7
44
100
Enable
12hr
3 wk
2
Capacity Reconfirm
Make sure fully recharged!
Otherwise Boost charge with DG runs
for 12-24 hours
Conduct capacity test with shut off the
AC mains and drown 60% capacity out
of the batteries, or the average
voltage is lower than 1.95Vpc.
Feedback the results to BSB.