Professional Documents
Culture Documents
DESIGN
MOD 1
EARTHING
-contd-
-contd-
-contd-
-contd-
-contd-
-contd-
-contd-
TT system of earthing
TN system of earthing
TN system of earthing requires providing of
earth electrodes at regular intervals throughout
the installation. The effectiveness of protective
devices should be analyzed at the design stage
and should be confirmed by mandatory
measurements to confirm the effectiveness.
The TN-C system
The TN-C system may appear to be less
expensive because of the absence of as
separate protective conductor. The TN-S can
be used even with flexible conductors. They
also provide a clean PE conductor because of
the separation of neutral & PE conductor. They
are ideal for computer systems &similar loads.
IT System of earthing
IT System of earthing offers the best
continuity of service during operation. The
insulation monitoring devices provide
indication of the first insulation failure and
is followed by mandatory locating and
clearing. This ensures systematic
prevention of supply outages.
This system is generally suitable for
installation with private transformers and
with high levels of insulation in the network.
IT systems are usually applied in hospitals,
ships, rail vehicles, because they provide
higher operational safety and advance
information about a possible failure.
TYPES OF EARTHING
Usual methods of earthing are Strip or wire earthing,
Rod earthing, Pipe earthing, & Plate earthing.
Strip or wire earthing. In strip earthing, copper
strip of a minimum of 25 mm x 1.6 mm or
galvanized iron strip of 25 mm x 4 mm is laid
horizontally in trenches with a minimum depth of
500 mm. If circular conductors are used, then
minimum size is 3 mm2 for copper and 6 mm2 for GI
wire. The length of the wire or strip used should be
sufficient to provide the required value for earth
resistance. It shall however be not less than fifteen
meters. The trenches can be distributed over a
larger area in a circular fashion or several radial
trenches around the main earth pit. This type of
earthing is preferred in rocky areas where deep
excavation for earth pit is difficult.
Rod earthing
In this system of earthing, solid copper rods 12 mm
dia. are driven vertically down in to the soil and
the main earth lead is connected to the top end
of the rod. Resistance values can be improved by
adding more rods screwing one above the other
and driving successively. Copper clad iron rods
are also used which are economical as well as
efficient in harder soil conditions. Situations may
arise when one such earth pit is insufficient to
provide the required resistance. More earth rods
are then driven in nearby locations conveniently;
keeping the distance between them is more than
their length. These rods are connected by direct
buried bare conductors for improved resistance
values.
Pipe earthing
Pipe earthing or Plate earthing is preferred when the
expected earth current is larger and the protection required
in more precise. Pipe earthing is the best way of earthing
and it is cheaper. In this method, a cast iron pipe 100 mm
dia,2.5 M long or a galvanized and perforated iron pipe is
installed vertically in permanently wet ground. The standard
size of the GI pipe is usually 38 mm or 50 mm in dia. and
2.5 M in length. The earth pit is filled with alternate layers of
salt and coke for a minimum diameter of 400mm. to provide
an efficient and moist interface between the pipe and the
soil. A funnel is fixed on the top of the pipe to facilitate
watering at regular intervals. The pipe head is provided with
a terminal clamp welded to the pipe which accommodates
the system earth leads. The terminal clamp and funnel are
protected by a concrete block with a concrete cover.
Improvement of earth resistance using parallel earthings is
done similar to the rod earthing keeping a minimum of 2
meter between them.
Plate earthing
The figure shows a plate earthing using a cast
iron plate. The plate is of the size
1200x1200x12 mm which is covered with a
minimum thickness of 150 mm of charcoal and
salt mixture on both sides. Earth plates are
always installed with its face vertical with one or
two leads of copper strips leading to the earth
pit vertically above the plate. The earth pit is a
concrete block with provisions for a funnel for
watering in to the earth electrode and entry of
earth leads from the system earth point. All
under ground bolted connections are punched
to avoid loose contacts and covered with
bituminous compound. The electrical
connections in the earth pit are firmly braced.
Neutral Wire
Distribution transformer which
receives power at 11kV is fed
through its delta connected primary.
The secondary winding is star
connected and the output is star
connected for 230/400 V three phase
four wire system. All the four
conductors, three phases and the
neutral, are run on insulators all
along the LT feeder, though the
neutral of the transformer is directly
earthed.
Earth wire
-contd-
FUSES
Fuses are the simplest form of
protective element in an electrical
system. Fuses break a circuit by
controlled melting of the fuse
element when the current exceeds a
given value for a corresponding
period of time. Each type of fuse has
a current time relationship presented
in the form of a performance
characteristic.
CONTACTORS
A contactor is a solenoid operated switch which is held
closed by a current through a solenoid. Contactors
are designed to carry out numerous open/close
operations are commonly controlled locally or
remotely by ON OFF push buttons. The basic
properties of contactors as per IEC 60947-4-1 are:
1 the operating duration( eg 8 hrs, uninterrupted,
intermittent, temporary of 3,10, 30, 60 and 90
minutes)
2 Utilization category; (eg. AC3 for starting and
stopping of induction motors)
3 Start stop cycle: (eg. 1 to1200 cycles per hour)
4 Mechanical endurance: number of offload operations.
5 Electrical endurance: number of on load operations.
6 Rated making and breaking operations
CIRCUIT BREAKERS
-contd
Operation of ACB
-contd-
Advantages of VCB
MCB
-contd-
SERVICE CONNECTION
The electric supply authority provides electricity
to the consumer at a convenient location on
the outside wall of the house. The supply
authority will have an energy meter and a cut
out as a part of their outlet. The line bringing
electric power from the suppliers distribution
system up to the energy meter installed at the
consumers premises is called the service
connection. Service connection may be by
means of overhead bare conductors, insulated
cables called weather proof wires or by
underground cables. The consumer has to
arrange his own main switch, a distribution
box and necessary wiring in the house as
stipulated by the regulations in force.
-contd-
-contd-
-contd-
No
Equipment
Power
rating(watts)
Incandescent lamps
60
Fluorescent lamps
60
Ceiling/table fan
100
Socket outlet(ordinary)
100
Socket outlet(power)
1000