Sepam 1000+ Merlin Gerin

Simplicity and performance,


headed in the right direction.

More solutions
in the Sepam range!

DAES/PCR - S1ill_97E8.PPT - 04/2001

Sepam 1000+,
headed in the right direction

More solutions
More modularity
More performance
More simplicity

DAES/PCR - S1ill_97E8.PPT - 04/2001

More solutions

Sepam 1000+, more solutions


suited to your needs!

For industrial and


commercial sites
For public distribution
networks
For all voltage levels

DAES/PCR - S1ill_97E8.PPT - 04/2001

More solutions

Substation application
(S20 type)

Substation incomer and


feeder applications
Protection functions:
50/51, phase
overcurrent
50N/51N, earth fault
46, negative sequence /
unbalance
Logic discrimination
4-cycle recloser

DAES/PCR - S1ill_97E8.PPT - 04/2001

More solutions

Substation application
(S40/S41/S42 types)

Parallel incomers or closed


ring network
Isolated or compensated
neutral network
Protection functions:
50/51,50N/51N,46,50BF
67N/67NC,
directional earth fault
67, directional phase
overcurrent
32P, reverse power
I, U, P, E measurements

DAES/PCR - S1ill_97E8.PPT - 04/2001

More solutions

Transformer application
(T20 type)

Protection functions:
50/51, 50N/51N and 46
49RMS, thermal
overload
38/49T, temperature
monitoring
Treatment of faults detected
by Buchholz or transformer
thermostat

DAES/PCR - S1ill_97E8.PPT - 04/2001

More solutions

Transformer application
(T40/T42 types)

Parallel transformers
Isolated or compensated
neutral network
Protection functions:
50/51,50N/51N, 46,50BF
49RMS et 38/49T
67N/67NC, directional
earth fault
67, directional phase
overcurrent
I, U, P, E measurements

DAES/PCR - S1ill_97E8.PPT - 04/2001

More solutions

Motor application
(M20 type)

Protection functions:
50/51, 50N/51N and 46
49RMS and 38/49T
Specific functions:
37, phase undercurrent
48/51LR, excessive
starting time and rotor
locking
66, starts per hours

DAES/PCR - S1ill_97E8.PPT - 04/2001

More solutions

Motor application
(M41 type)

Isolated or compensated
neutral network
All of the M20 protection
functions, plus:
67N/67NC, directional
earth fault
32P, reverse power
27/59, 81L/81H,
Automatic load shedding
I, U, P, E measurements

DAES/PCR - S1ill_97E8.PPT - 04/2001

10

More solutions

Busbar application
(B21 type)

Voltage protection functions:


27/59, phase-to-phase
under/overvoltage
27S, phase-to-neutral
uncervoltage
59N, neutral voltage displacement
81L/81H, under/overfrequency
27D/47, positive sequence
undervoltage and phase rotation
direction check
27R, remanent undervoltage

DAES/PCR - S1ill_97E8.PPT - 04/2001

11

More solutions

Loss of mains application


(B22 type)

Voltage protection functions:


27/59, 27S, 59N
81L/81H
27D/47, 27R
Loss of mains protection
81R, rate of change of
frequency (ROCOF)
fast, reliable detection of
loss of mains
for substations with
generators in parallel
with the main network

DAES/PCR - S1ill_97E8.PPT - 04/2001

12

Sepam 1000+
Selection guide

More solutions

Selection criteria series 20


Measurements

series 40
U

Specific protection
functions
Applications

I and U

Loss of mains
(ROCOF)

series 20

series 40

Substation

S20

S40

Transformer

T20

T40

Motor

M20

Busbar

DAES/PCR - S1ill_97E8.PPT - 04/2001

I and U

I et U

Directional
earth fault

Directional
earth fault &
phase O/C

S41

S42
T42

M41
B21

B22

13

Sepam 1000+,
headed in the right direction

More solutions
More modularity
More performance
More simplicity

DAES/PCR - S1ill_97E8.PPT - 04/2001

14

More modularity

Sepam 1000+,
more modularity!
User Machine Interfaces
Logic Inputs / Outputs
Communication
Temperature acquisition
Analog output

To evolve in step with


your application!

DAES/PCR - S1ill_97E8.PPT - 04/2001

15

More modularity

Basic
User Machine Interface

Just what's needed to


operate your network!

DAES/PCR - S1ill_97E8.PPT - 04/2001

16

More modularity

Advanced
User Machine Interface

To manage your
installation locally!

DAES/PCR - S1ill_97E8.PPT - 04/2001

17

More modularity

Remote advanced
User Machine Interface

Module to be
flush-mounted
wherever you want
To improve
ergonomics
For easier
installation

DAES/PCR - S1ill_97E8.PPT - 04/2001

18

More modularity

SFT2841 software

To derive
maximum benefit
from your Sepam!

DAES/PCR - S1ill_97E8.PPT - 04/2001

19

More modularity

Sepam 1000+,
more modularity!
User Machine Interfaces

Logic Inputs / Outputs


Communication
Temperature acquisition
Analog output

To evolve with
your application!

DAES/PCR - S1ill_97E8.PPT - 04/2001

20

More modularity

Additional
Inputs / Outputs

Standard four logic outputs


A choice of two additional
logic I/O modules:
MES108: 4I/4O
MES114: 10I/4O

To enhance the
monitoring-control
functions

DAES/PCR - S1ill_97E8.PPT - 04/2001

21

More modularity

Sepam 1000+,
more modularity!
User Machine Interfaces
Logic Inputs / Outputs

Communication
Temperature acquisition
Analog output

To evolve with
your application!

DAES/PCR - S1ill_97E8.PPT - 04/2001

22

More modularity

Communication interfaces

Modules that are


ready to use
For fully secure
communication!

DAES/PCR - S1ill_97E8.PPT - 04/2001

23

More modularity

Sepam 1000+,
more modularity!
User Machine Interfaces
Logic Inputs / Outputs
Communication

Temperature acquisition
Analog output

To evolve with
your application!

DAES/PCR - S1ill_97E8.PPT - 04/2001

24

More modularity

Temperature
acquisition

Measurement
of 8 or 16
temperatures
By Pt100, Ni100 or
Ni120 temperature
sensors
For better motor
and transformer
protection!
DAES/PCR - S1ill_97E8.PPT - 04/2001

25

More modularity

Sepam 1000+,
more modularity!
User Machine Interfaces
Logic Inputs / Outputs
Communication
Temperature acquisition

Analog output
To evolve with
your application!

DAES/PCR - S1ill_97E8.PPT - 04/2001

26

More modularity

Analog output

A choice of formats
(4-20mA, 0-10mA
or 0-20mA)
For remote analog
measurements!

DAES/PCR - S1ill_97E8.PPT - 04/2001

27

More modularity

Your solution
at the best cost!

Sepam 1000+:
To specifically fit
your needs, from
the simplest to
the most
comprehensive
To evolve in step
with your
investments!
DAES/PCR - S1ill_97E8.PPT - 04/2001

28

Sepam 1000+,
headed in the right direction

More solutions
More modularity
More performance
More simplicity

DAES/PCR - S1ill_97E8.PPT - 04/2001

29

More performance

Sepam 1000+ ,
reliable and dependable
Benefits from more than 15 years of
experience acquired with the Sepam range
Design based on dependability study:
FMECA: Failure Mode, Effects and
Criticality Analysis
calculation of failure rates

DAES/PCR - S1ill_97E8.PPT - 04/2001

30

More performance

Sepam 1000+ ,
robust and compact
Case made of insulating material
light-weight
anti-corrosion
Excellent immunity to radiated fields
IP52 / NEMA12 on front panel
Class 2 mechanical robustness
(shocks, jolts, vibrations and earthquakes)
Operating temperature
from -25C to +70C

<100mm
DAES/PCR - S1ill_97E8.PPT - 04/2001

31

Phase protection
Earth fault protection

More performance

1 A

4 set points per protection

1 B

Switching between groups of settings


A and B
Logic discrimination
2 B
2 A

16 types of IDMT tripping curves


(IEC, IEEE and IAC curves)
Adjustable time reset

Earth fault protection insensitive to


I
transformer energizing

DAES/PCR - S1ill_97E8.PPT - 04/2001

32

More performance

Thermal overload protection


(patented model)
3 RMS phase currents (harmonic 17)
Compensated by ambient temperature
measurement
Switching between 2 groups of time
constants according to operating
conditions
Cold curve adjustable to match the motor
thermal withstand (patented)
Operating assistance with predictive
information:
time before overload tripping
waiting time after tripping

DAES/PCR - S1ill_97E8.PPT - 04/2001

33

More performance

Directional earth fault

2 set points per protection


Switching between 2 groups of settings
Logic discrimination
Protection suited all neutral earthing
systems:
impedant neutral
compensated neutral
or isolated neutral
Protection of closed ring networks

DAES/PCR - S1ill_97E8.PPT - 04/2001

34

More performance

Directional phase overcurrent


Directional power
Directional phase overcurrent protection:
for the protection of closed ring networks
or networks with parallel incomers
2 set points per protection function
switching between 2 groups of settings
3-phase, with voltage memory and
frequency tracking
16 types of IDMT tripping curves
adjustable time reset
Directional active power protection: for the
detection of motors operating as
generators

DAES/PCR - S1ill_97E8.PPT - 04/2001

35

More performance

Voltage protection functions

27, phase-to-neutral or phase-to-phase


undervoltage
27R, remanent undervoltage
27D, positive sequence undervoltage
47, checking of phase rotation direction
59, phase-to-neutral or phase-to-phase
overvoltage
59N, neutral voltage displacement

DAES/PCR - S1ill_97E8.PPT - 04/2001

36

More performance

Loss of mains protection


Rate Of Change Of Frequency

For loss of mains


detection:
Fast and sensitive
with slow change of
frequency
Reliable and stable
time-delayed to be
insensitive to transient
network disturbances
Easy to set

DAES/PCR - S1ill_97E8.PPT - 04/2001

37

More performance

Circuit breaker control

Suitable for all types of trip unit


Local or remote opening and closing
Recloser co-ordination
Trip circuit supervision and checking of
discrepancy
Inhibition of closing

A complete function,
dependable and ready to use!

DAES/PCR - S1ill_97E8.PPT - 04/2001

38

More performance

Recloser

4 cycles
Activation of cycles by:
phase and/or earth fault protection
instantaneous or time-delayed tripping
Co-ordination with circuit breaker control

A complete function,
dependable and ready to use!

DAES/PCR - S1ill_97E8.PPT - 04/2001

39

More performance

Logical equation editor

Logical operators
AND, OR, NOT
On logic inputs and
protection data

To adapt control
functions to suit
your needs!

DAES/PCR - S1ill_97E8.PPT - 04/2001

40

More performance

Metering

All the measurements are


available:
RMS and residual phase
currents
Peak demand and average
currents
Phase-to-neutral, phase-tophase and residual
voltages

E
Active+
= MW
Pmax=3,2
U21=
I1=
P=
2,1
178A
6,6
MW
kV
RMS
Io 755454
tore= 5,2A
MW.h
Qmax=1,0
MVAr
I2=
177A
RMS
Q=
900k
U32=6,6VAr
kV
E Active- =
0
50 6,6
100 150%Ino
I3=
178A
RMS
S=
2,3
U13=
kV
72MVA
MW.h

Active, reactive, apparent


power and power factor
Active and reactive energy

DAES/PCR - S1ill_97E8.PPT - 04/2001

41

More performance

Switchgear diagnosis

Continuous, comprehensive breaking device


monitoring:
Number of operations
Operating time
Charging time
Cumulative breaking current, overall and by
levels of fault current
and CT/VT supervision

For effective
preventive maintenance!
DAES/PCR - S1ill_97E8.PPT - 04/2001

42

More performance

Network diagnosis assistance

Disturbance recording
1 to 19 records in
COMTRADE format
max. memory: 20s
max. record: 10s
Phase unbalance
Tripping currents
Alarm history
Tripping context

For better
understanding!

DAES/PCR - S1ill_97E8.PPT - 04/2001

43

More performance

Remote operation

Modbus protocol
RS485 bus, 2-wire or 4-wire
Maximum transmission
rate: 38400 bauds
Response time < 15 ms

DAES/PCR - S1ill_97E8.PPT - 04/2001

44

More performance

Remote operation

All the data are available


Time-tagged events
1ms resolution
Modbus or external
synchronization
Dependable remote control
orders with select before
operate
Disturbance recording
Remote protection setting

DAES/PCR - S1ill_97E8.PPT - 04/2001

45

More performance

Ethernet connection
and Webserver
Integration of Sepam in your Ethernet
network
Ethernet/Modbus gateway
Modbus / TCP/IP multi-master protocol
fast transmission rate

Ethernet network

Ethernet/Modbus
gateway

Simple consultation of Sepam data


from a PC with internet/intranet browser
presented in Web/Sepam pages
embedded in the gateway

Sepam 1000+
on RS485
Modbus
network

DAES/PCR - S1ill_97E8.PPT - 04/2001

46

More performance

Integrated in
PowerLogic System

Industrial and commercial


network management
system, including:
Power management
software tools
Power quality measurement
and analysis products
Masterpact and Compact
communicating circuit
breakers
Sepam multifunctional
protection units

DAES/PCR - S1ill_97E8.PPT - 04/2001

47

Sepam 1000+,
headed in the right direction

More solutions
More modularity
More performance
More simplicity

DAES/PCR - S1ill_97E8.PPT - 04/2001

48

More simplicity

Simplified choice

A consistent product family, organized by


application
Universal power supply:
24 to 250 V DC and 100 to 240 V AC
Universal logic inputs
(all DC voltages)
1 temperature module for all sensors
(Pt100, Ni120, Ni100)
1 analog output module
(4-20mA, 0-10mA, 0-20mA)

DAES/PCR - S1ill_97E8.PPT - 04/2001

49

More simplicity

Easy to install

Compact, reduced depth


(< 100mm)
Engraved terminal
identification
Disconnectable
without any precautions
Plug-in input / output
module
Prewired remote modules

DAES/PCR - S1ill_97E8.PPT - 04/2001

50

More simplicity

Easy to commission

Standard control and


monitoring functions, ready to
use:
defined by application
delivered with the
parameters set
Simple to set protection
functions
with advanced UMI
with SFT2841 software

For fast, dependable


implementation!

DAES/PCR - S1ill_97E8.PPT - 04/2001

51

More simplicity

User Machine Interface


easy to use ...

Graphic LCD display


Clearly understandable
display of all data
Dedicated keys, identified
by icons

For
inituitive

DAES/PCR - S1ill_97E8.PPT - 04/2001

use!

52

More simplicity

DAES/PCR - S1ill_97E8.PPT - 04/2001

... in normal
operation ...

53

More simplicity

DAES/PCR - S1ill_97E8.PPT - 04/2001

... and for servicing,


after tripping.

54

More simplicity

Understood by all ...


... it speaks all languages!

Screen language may be


customized
Accommodates all
graphics:
typographical
characters
drawings
Texts in English remain
available

DAES/PCR - S1ill_97E8.PPT - 04/2001

55

More simplicity

SFT2841: a user-friendly,
powerful software tool

2 operating modes
unconnected
connected to Sepam
Windows

environment

On-line help
Available in 3 languages, customizable

To derive
maximum benefit
from your Sepam!

DAES/PCR - S1ill_97E8.PPT - 04/2001

56

More simplicity

SFT2841: use in
unconnected mode ...

Preparation of
Sepam parameters
protection settings
File management

To reduce
commissioning time!

DAES/PCR - S1ill_97E8.PPT - 04/2001

57

More simplicity

SFT2841: use in
connected mode ...

Loading of parameters and


protection settings
Current operation
Recovery of:
parameters and
protection settings
disturbance recording
records
alarm history

To facilitate
servicing operations!

DAES/PCR - S1ill_97E8.PPT - 04/2001

58

More simplicity

SFT2841: customization tool

Customization of control and


monitoring functions
Logical equation editor
Customization of alarm messages
on advanced UMI
Customization of signal lamp labels

To fit your needs!

DAES/PCR - S1ill_97E8.PPT - 04/2001

59

Sepam 1000+:
to win all across the board!

More solutions
More modularity
More performance
More simplicity

DAES/PCR - S1ill_97E8.PPT - 04/2001

60