Professional Documents
Culture Documents
PRESENTED BY:
* MD. NOMAN SABER KHAN
INTRODUCTION TO GROUNDING
1. Equipment grounds,
2. Static grounds,
3. Systems grounds,
4. Maintenance grounds,
5. Electronic grounds,
6. Lightning grounds.
EQUIPMENT GROUNDS:
STATIC GROUNDS:
SYSTEM GROUNDS:
MAINTENANCE GROUNDS:
LIGHTNING PROTECTION:
FACTORS TO BE CONSIDERED
IEC NOMENCLATURE
TN NETWORK
TN
TT NETWORK
IT NETWORK
PROPERTIES
SAFETY
In TN-S and TT systems (and in TN-CS beyond the point of the split), a
residual-current device can be used
as an additional protection. In the
absence of any insulation fault in the
consumer device, the equation
IL1+IL2+IL3+IN = 0 holds, and an
RCD can disconnect the supply as
soon as this sum reaches a threshold
(typically 10-500 mA). An insulation
fault between either L or N and PE
will trigger an RCD with high
EARTHING MATERIALS
Parts to be Earthed
Method Of Connection
Transformer tank
Surge Arrester
Support of bushing
insulators, lightning
arresters, fuse, etc..
Potential Transformer
Isolator
Current Transformer
Power Transformer
Grounding and bonding are the basis upon which safety and power
quality are built. The grounding system provides a low-impedance path
for fault current and limits the voltage rise on the normally noncurrent-carrying metallic components of the electrical distribution
system.
During fault conditions, low impedance results in high fault current
flow, causing overcurrent protective devices to operate, clearing the
fault quickly and safely. The grounding system also allows transients
such as lightning to be safely diverted to earth.
Bonding is the intentional joining of normally non-current-carrying
metallic components to form an electrically conductive path. This helps
ensure that these metallic components are at the same potential, limiting
potentially dangerous voltage differences.
Careful consideration should be given to installing a grounding
system that exceeds the minimum NEC requirements for improved
safety and power quality.
The IEEE Emerald Book recommends the use of equipmentgrounding conductors in all circuits, not relying on a raceway
system alone for equipment grounding. Use equipment
grounding conductors sized equal to the phase conductors to
decrease circuit impedance and improve the clearing time of
overcurrent protective devices.
Bond all metal enclosures, raceways, boxes, and equipment
grounding conductors into one electrically continuous system.
Consider the installation of an equipment grounding conductor
of the wire type as a supplement to a conduit-only equipment
grounding conductor for especially sensitive equipment.
The minimum size the equipment grounding conductor for
safety is provided in NEC 250.122, but a full-size grounding
conductor is recommended for power quality considerations.
2. ISOLATED GROUNDING
SYSTEM
3. BRANCH-CIRCUIT GROUNDING
4. GROUND RESISTANCE
4. GROUND RESISTANCE
5. GROUND RODS
5. GROUND RODS
6. GROUND RING
6. GROUND RING
7. GROUNDING ELECTRODE
SYSTEM
EARTHING DEFINITIONS- AS PER BNBCEARTH CONDUCTORS IN PANEL AND TO CIRCUITS MINIMUM CROSS-SECTIONAL AREA OF COPPER EARTH CONDUCTORS
IN RELATION TO THE AREA OF ASSOCIATED PHASE CONDUCTORS
Less than 16
16
35 or greater
NB- In case of
copper wire being
used as earth
conductors, the size
of the wire shall not
be less than half the
area of the largest
current carrying
conductor supplying
the circuit.
RestrictionAluminium or copper
clad aluminium (clad
(PP of clothe)
sojjito) conductors
shall not be used for
final connections to
earth electrodes
Earth Lead
Earth lead is the link which provides connection
between the earth conductor(s) and the earth
[alvaa]electrode(s). Earthing leads shall be run in
duplicate down to the earth electrode so as to
increase the safety factor of the installation. Copper
wire used as earthing lead must not be smaller than
8 SWG (12 mm).
In normal provision the earthing lead connects the
earth electrode to a bus bar called earth bus bar.
earth conductor is connected to Earth bus bar
Earth Electrodes
The earth electrode shall, as far as practicable,
penetrate into permanently moist soil preferably
below ground water table. The resistance of earth
electrodes shall not be more than one ohm. The
following types earth electrodes are recognized for
the purpose of Code -Copper rods, Copper plates,
Galvanized iron pipes. Copper rods shall have a
minimum diameter of 12.7 mm. Copper plates shall
not be less than 600 mm x 600 mm in size, with 6
mm thickness.GI pipes shall have a minimum
diameter of 50 mm. Earthing cable sizes should be
adequate with respect to the phase.
Below 4 rm
4 rm to 16 rm
25 rm and 35 rm
16 rm
35 above
THE END