Need for Life Safe Agent

Halon 1301 An Excellent Extinguishant


Used as a Favorite Agent in
Normally Occupied Areas
High Value Assets
Areas where Usage of Dry Chemical, Foam,
CO2, Water is NOT PRACTICAL
BUT.. Ozone Depletion Substance >>>>>>>

Legislative Issues
Montreal Protocol
Framework Convention
on Climate Change
EPA- SNAP Program
NFPA 2001

Contemporary Fire Triangle

People & Lives


Property

Environment

The Natural Choice For:


Cell Sites

Paging Facilities
Switch Facilities
Data/Tape Storage Areas
Microwave/Satellite Relays
Information System Centers

Inergen History
First Commercialized In Europe 1991.
Researched By NASA and NRl.
Approved In All Major Countries.
Accepted Under EPA SNAP Program.
U/L Listed-FM Approved.
Meets NFPA 2001 Requirements.

What Is Inergen
INERT GAS + NITROGEN
COMPOSITION
Nitrogen ................. 52%
Argon ..................... 40%
Carbon Dioxide ....... 8%
N2

Ar

CO2

Normal Atmosphere
COMPOSITION
Nitrogen .................. 78.0%
Oxygen ................... 21.0%
Argon ...................... 1.0%
Carbon Dioxide ..... 0.03%
N2

O2

Ar

CO2

How Does Inergen Work


Heat

Fuel

Oxygen
Gas Based Systems

How Does Inergen Work


21%
15% O2 LEVEL
REQUIRED FOR
COMBUSTION (FIRE)

12.5%
4%
< 1%
O2

CO2

NORMAL ATMOSPHERE

O2

CO2

INERGEN ATMOSPHERE

CO2 LEVEL
INCREASED TO
ACCELERATE
RESPIRATION

Inergen Extinguishing Agent


UNDERSTAND the BENEFITS
Documented Health/Human Testing + 40 years
Worldwide Acceptance +50 Countries
No Cardiac Sensitization Effects
Protects Human Life
Effective Against Fire
NO Thermal Shock
Wont Damage Equipment
Harmless to Environment

Advantages of CO2 in Inergen


Stimulates

Respiration
Enhances the Efficiency of Oxygen Transfer
Dilation of Blood Vessels
Shift in the Hemoglobin Dissociation Curve
Thus brings in to play all these above natural
mechanisms resulting humans to endure
lower oxygen levels for longer periods

Approvals & Testing


Testing Laboratories - UL, FM, ULC, etc.
Medical and Governmental Agencies
Worldwide.
Discharge Test Acceptance without any
restrictions.

The

EVERGREEN Warranty
ANSUL Will Provide the Recharge Agent
For INERGEN Systems For 10 Years
From the Date of Commissioning
REGARDLESS OF CAUSE
See warranty statement for complete details.

Lifetime Guarantee
GUARANTEED To Be Safe To Breathe.
GUARANTEED To Be Non-Corrosive.
GUARANTEED To Be Available/Unregulated.
GUARANTEED To Be Environmentally Safe.
GUARANTEED To be Non-Toxic.

INERGEN System Components


-CYLINDERS with CV98 VALVE
-MANIFOLD PIPING
-PRESSURE REDUCING ORIFICES
-ACTUATION ACCESSORIES
-SELECTOR VALVES
-NOZZLES & ACCESSORIES

INERGEN Cylinders
Capacities
2175 psi (150 bar) - 205,
266, 355, 429, 439 Cu Ft
DOT 3AA2300
UL, FM, ULC
2900 psi (200 bar) 572 Cu Ft
DOT 3AA3000
UL

CV-98 Valve
2175 PSI (150 Bar) or
2900 PSI (200 Bar)
0 F to 130 F
Maintenance Free
Guaranteed Leak Free

Cylinder Valve Ports


Pilot Port

Gauge Port

Relief Valve Port

Fill Port

Actuation Port

Outlet Port

HF Electric Actuator
Electric Actuator for CV-98
Valve
Used With the Booster
Actuator
Resettable
Stackable
Swivel Nut Allows Easy
Installation and Removal
12VDC, Includes 21.5 Ohm
Resistor

Booster Actuator
Used With HF Electric
Actuator
Stackable
Swivel Nut Allows
Easy Installation and
Removal

Booster Actuator
Resettable

Booster/HF Actuator Mounted on Valve

Actuator Assembles
to Actuation Port on
Top of Valve
1 or 2 Actuators Can
be Used in Series to
Operate System

Booster/HF Actuator Mounted on Valve

Must Include 21.5


Ohm Resistor in Series
with Actuator if One
Actuator is Used
Include In-Line
Supervisory Device if
Required by the
Control Panel

HF Lever Actuator

Used on
the HF
Actuator

HF Lever Actuator

Small Diameter
Pin

CV98 Lever Actuator


Similar to Previous
Lever Actuators
Swivel Nut Smaller
to Match CV-98
Valve Threads

CV98 Lever Actuator

Medium
Diameter Pin

Manifold Piping
150 Bar
Class 2000 or 3000
Fittings
Schedule 80 Pipe
(minimum- consult
INERGEN Manual)

Manifold Piping
200 Bar
Class 3000 Fittings
Sch 80/160 Pipe
(minimum- consult
INERGEN Manual)

Discharge
Hose
Provides Flexible
Connection
Between Cylinder
Valve & Manifold.
Special Threads
On Cylinder Valve
End.

Check Valves
Brass Globe Style.
Used In Manifold For
Main/Reserve and
Selector Valve
Systems.

Header Vent Plug


Used In Manifolded
Main / Reserve and
Selector Valve
Systems.
Vents Low Pressure
Gas.

Pressure Reducing Orifice


150 Bar
Controls Downstream
Pressure and Flow
Pipe Sizes:
1/2 to 2- Orifice Union
2 1/2 & 3- Orifice Nipple
2 1/2 to 4- Orifice Flanged

Pressure Reducing Orifice


200 Bar
Controls Downstream
Pressure and Flow
Pipe Sizes:
1/2 to 2- Orifice Union
2 1/2 to 4- Orifice Flanged
(Flanged assemblies different part
number for the 200 bar system)

Selector Valves
1/2 to 2 Sizes
UL, FM, ULC Listed
Electric, Pneumatic and
Manual Actuation

Selector Valves
Electric

Selector Valves
Pneumatic

Selector Valves
Manual

Selector Valves
(150 Bar Only)
2 1/2 to 4 Sizes
UL, FM, ULC Listed
Electric and Manual
Actuation

Selector Valves

Manual

Pneumatic Actuation
ANSUL AUTOMAN IIC Releasing Device
Supplies Pressure For
Operation.
Hose is attached
Directly to Pilot Port.
Must include a check
valve close to cylinder
valve.

Down Stream Piping


Pressure determined by
flow calcs. Class 300
Fittings (same as Halon
1301)
Schedule 40 Pipe
(minimum-consult
INERGEN Design
Manual)

Discharge
Nozzles
1/4

to 3 360 Degree
1/4 to 3 180 Degree
Sidewall
1/2 to 3 USCG
Approved Marine
Applications

Single-Cylinder Bracketing
Various Sizes.
Consists Of
Channel, Strap and
Bolts.

Multi-Cylinder Bracketing
Consists Of
Backframe
Assembly &
Cylinder Clamps.
Can Be
Configured In
Single, Double, or
Back-to-Back
Rows.

Multi-Cylinder Bracketing
Options Available:
Uprights
Feet
Center Upright Foot
Connectors
Weigh Rail Support

Pressure
Switch
Used To Shut-Down
or Startup Electrical
Equipment During
System Actuation.
Commonly Used To
Signal AUTOPULSE
Control Panel.

Main/Reserve Nameplates
Used To Identify
Main & Reserve
Cylinder Banks.
Aluminum Plates
With Sunken
Letters Painted
Black.

Warning Nameplates
Used To Inform
Personnel Upon
Discharge.
Need One At Each
Exit Doorway.
Aluminum Plates
With Sunken
Letters Painted
Black.

Alarm & Control Panels


Models
442R,
IQ-301,
and
IQ-396