CARRIER

COMFORT
NETWORK
BUS ARCHITECTURE

Copyright Carrier Corp. 2008

CCN BUS ARCHITECTURE

CCN PRIMARY BUS


(3 Conductor Shielded stranded wire cable 18 or 22 *ga .)

PLink

3V

Comfort
Controllers

PIC

CIO

(CCN)

(CCN)

Or FIDs (CCN)

For General CCN Type Devices: Theoretical Maximum of 239 Devices on any bus.
For CCS type Devices: A Maximum of 128 Zone Controllers or 8 Scanning Devices
(Linkage Coordinator) on any bus.
This is a Local Area Network (LAN) is now a Wide Area Network (WAN)
*Do not use 22 gauge wiring if using 38400 baud rate

Copyright Carrier Corp. 2008

COMM1
7
COMM1 or
COMM2
(-) BLK
(G) WHT
(+) RED

COMM1 or
COMM2

6
5

COMM1 or
COMM2

Current 6400 New Bridges


Data Collection III &
Chillervisor III CCNWeb
COMM1
Ethernet CCN
3V Devices

3 (-)

3 (G)

3 (-)

3 (-)

3 (-)

2 (-)

2 (G)

2 (-)

2 (G)

2 (G)

(G)

(G)

1 (+)

1 (+)

1 (+)

1 (+)

(+)

(+)

203 FID

Repeaters
& Older Bridges

CIOs
DataPort
DataLink
BACLink

PIC Is

PIC Is

Old Style
6400

RS -

RS+

(G) GRN

Typical
VVT/Temp

Copyright Carrier Corp. 2008

(+) RED

(-) BLK

PICs
Product Integrated Control
(Application Specific Controls)
Factory Mounted On Carrier
HVAC Equipment With Sensors

Copyright Carrier Corp. 2008

VAV Air Terminals


Air Handling Units
Chillers
Rooftop Units

PIC Architecture
CCN Primary Bus

Power
20 or 24V ac

SIO or LEN
Bus
M
A 12
I
N I
Local
Interface
Device
Or
Marquee
or
Navigator

Copyright Carrier Corp. 2008

B
O
A
R
D

6
o
u
t

E
X
S
P
A
N
S
I
O
N

E
X
S
P
A
N
S
I
O
N

FIDs
Field Installed Device
Is An All Purpose Controller For
Carrier Equipment without PICs
& Non- Carrier HVAC Equipment
In Addition Controls
Cooling Towers
Pumps
Lights
Boilers

Copyright Carrier Corp. 2008

6400 Comfort Controller


CCN Primary Bus
Power - 24 V ac

SIO Bus

Local
Interface
Device

Copyright Carrier Corp. 2008

P
R
O
C
E
S
S
O
R

16

16

16

P
O
I
N
T
S
I/O

P
O
I
N
T
S
I/O

P
O
I
N
T
S
I/O

CIO s
Communications Input /
Output
For System Level Control
Strategies
Chiller Plant Control
VAV Air Systems Control
Loadshed
Watersource Heatpump
Systems
Copyright Carrier Corp. 2008

CIO Modules
CCN Primary Bus
Power 20 or 24 V ac

Some CIOs:
Data Collection
Tent Billing
Auto Dial Gateway
Chiller Visor
Alarm Printer Interface
Loadshed Module
Flotronic System Manager

Copyright Carrier Corp. 2008

C
I
O
M
o
d
u
l
e

No Input or Outputs
All System Level Controls
Thru Communications.

Questions ??
?

Copyright Carrier Corp. 2008

10

CCN Addressing
The Key to the CCN BUS is Addressing:
An address is required of all devices on the bus.
No two devices on the same CCN system may ever
have the same address.
A CCN and CCS address consists of a 3 digit bus
number and a 3 digit device number.

Copyright Carrier Corp. 2008

11

Addressing Rules
CCN BUS is Addressing:
Example Address: ( 024 , 127)
Device Number

Bus Number

Legal bus numbers are 0 to 239 inclusive


The primary bus number is always 0
Note: All CCN device come from the factory at bus 0
Secondary bus numbers are 1 to 239 inclusive.

Legal device numbers are 1 to 239 inclusive.

A repeaters are not addressed.

Copyright Carrier Corp. 2008

12

CCN BUS
Addressing TEMP Devices
SIMPLE TEMP BUS
TEMP(T)
BUS NUMBER
ELEMENT NUMBER

000
008

TEMP

TEMP

TEMP

PLink

PLink

PLink

PLink

000
007

000
006

000
005

000
004

000
003

000
002

000
001

Wiring is daisy chained between control devices


For a simple and multiple TEMP system, the only addressing rule is
to never duplicate addresses.
For a simple TEMP and multiple TEMP system, bus communication
is at a minimum, and therefore usually a single bus is sufficient.

Copyright Carrier Corp. 2008

13

CCN BUS
GEN III VVT Devices
SIMPLE VVT BUS

MS(T)
BUS NUMBER
ELEMENT NUMBER

000
008

BC
000
007

ZC
000
006

ZC
000
005

ZC
000
004

ZC
000
003

ZC
000
002

ZC
000
001

For a simple and multiple VVT system, the only addressing rule is to
never duplicate addresses.
The bypass controller MUST be addresses one less than the
monitor stat.
Zone controllers must be addressed below the bypass controller.

Copyright Carrier Corp. 2008

14

CCN BUS
New 3V Devices
SIMPLE 3V BUS

BC
BUS NUMBER
ELEMENT NUMBER

000
008

LC
000
007

ZC
000
006

ZC
000
005

ZC
000
004

ZC
000
003

ZC
000
002

ZC
000
001

For a simple and multiple 3V system, the only addressing rule is to


never duplicate addresses.
The bypass controller MUST be addresses one higher than the
Linkage Coordinator.
Zone controllers must be addressed below the Linkage coordinator.

Copyright Carrier Corp. 2008

15

CCN BUS
USE OF REPEATERS
Repeater
BC

LC

ZC

ZC

BC

LC

ZC

ZC

60 DEVICES or 1,000 Feet

60 DEVICES or 1,000 Feet

Repeater
Repeater
TEMP

TEMP

PIC

CIO

6400

59 DEVICES or 1,000 Feet

TEMP

TEMP

60 DEVICES or 1,000 Feet

Use a repeater every 60 devices (Reflective degradation)


Use a repeater every 1,000 feet (Signal strength degradation)
Do not carry shielding bleed wire around repeaters
Ground each bus segment separately and only at one end.

Copyright Carrier Corp. 2008

16

TEMP

Copyright Carrier Corp. 2008

17

Copyright Carrier Corp. 2008

18

CCN Bridges
USE OF BRIDGES
PRIMARY BUS

BRIDGE

PIC

CIO

6400

BRIDGE

TEMP

SECONDARY BUS

BC

LC

ZC

TEMP

TEMP

SECONDARY BUS

ZC

BC

LC

ZC

A secondary bus may only be created from the primary bus.


A CCN may be expanded to have up to 239 secondary buses.
All wiring rules same as primary bus

Copyright Carrier Corp. 2008

TEMP

19

ZC

Bridge BUS is Addressing:


Bridge Address: ( 000 , 075)
Bridge Number

Bus Number

Secondary bus numbers is the Bridge Number


Secondary bus numbers are 1 to 239 inclusive.
Legal device numbers are 1 to 239 inclusive.
Example Address: ( 075 , 001)
Secondary
Bus Number

Copyright Carrier Corp. 2008

20

Device Number

CCN Secondary BUS


USE OF BRIDGES
PRIMARY BUS
BUS SEGMENT (60/1000)

BRIDGE

PIC

CIO

BUS SEGMENT (60/1000)

Repeater

6400

ADGW

TEMP

TEMP

TEMP

SECONDARY BUS
BUS SEGMENT (60/1000)

6400

PIC

CIO

BUS SEGMENT (60/1000)

Repeater

6400

TEMP

TEMP

TEMP

TEMP
Repeater

BUS SEGMENT (59/1000)

PIC

PIC

Copyright Carrier Corp. 2008

CIO

6400

BUS SEGMENT (60/1000)

Repeater
TEMP

21

TEMP

TEMP

TEMP

CCN BUS Communications

Communications Point To Point


Repeater
MS(T)

BC

ZC

ZC

MS

BS

ZC

Communication

ZC

Repeater

Repeater
TEMP

TEMP

PIC

CIO

6400

Communication Packet

Address of Receiver
Address of Sender
Communication
Message
CRC (BIT Check

Copyright Carrier Corp. 2008

Acknowledge

22

TEMP

TEMP

TEMP

CCN BUS Communications

Communications Broadcast
Repeater
MS(T)

BC

ZC

ZC

MS

BS

ZC

Broadcast

ZC

Repeater
Repeater

TEMP

TEMP

PIC

CIO

6400

Copyright Carrier Corp. 2008

TEMP

TEMP

Communication Packet

Broadcast Acknowledgement

TEMP

Special Address Code Meaning This package is to be received by


All Nodes on the Network
Address of Sender
Communication Message
CRC (BIT Check

23

CCN BUS Broadcast

Broadcast Communications Rules


*

Many CCN devices may broadcast information over the network such as time of day or point
values like outdoor air temperature, or relative humidity.

Broadcast information is sent (or made available) to all Network Devices.

Every BUS should have one device configures as a the Broadcast Acknowledger

The Broadcast Acknowledger acts as a spokes person for the entire Bus by acknowledging
back to the sender that a successful broadcast was received.

Time broadcaster's send their internal clock time and holiday status twice a day at 1:00 AM
and 1:00 PM, as well as when requested to send time by another Network Device.

Copyright Carrier Corp. 2008

24

Questions ??
?

Copyright Carrier Corp. 2008

25

PremierLink

Analog Sensor
Inputs

Discrete Sensor
Inputs
4 to 20 ma
Analog Output
24 volt Power

Communication
s

Power supply: 2-wire, 24 VAC 15% at 40 va, 60 Hz


Power consumption: Normal operating supply range is 18 to 32 VAC with minimum of 10 VA

Copyright Carrier Corp. 2008

26

(6) Digital
Outputs

PremierLink Installation
Fan, Cool, Heat & RV/EF Outputs

Required for
Economizer
control!

4-20ma Economizer Output

Must have RAT or SPT


in space for standalone
operation in case of
Linkage com failure

SAT always Required!


Analog Sensor
Connections
Optional Discrete
Inputs
24vac Power
CCN Com Bus
Copyright Carrier Corp. 2008

27

Questions ??
?

Copyright Carrier Corp. 2008

28

3V Zone Controller

Sensor Inputs

Communication

Power

Power supply: The power supply is 24 vac 10% at 40 va (50/60 Hz).


Power consumption: Water valves are limited to 15 va. The fan contactor is
limited to 10 va (holding).
Copyright Carrier Corp. 2008

29

3V Zone Controller without Reheat

Copyright Carrier Corp. 2008

30

Optional
Reheat Board

3V Zone Controller with Reheat


Copyright Carrier Corp. 2008

31

Fan
Heat Stage 3

Heat Stage 2
Heat Stage 1

Optional Reheat Board


Copyright Carrier Corp. 2008

32

ZC Wiring Figure 5

Copyright Carrier Corp. 2008

33

ZC wiring Figure 5 for Linkage Co.


DAT

Optional
Not for use
w/Reheat!

PAT
Optional for Linkage
Coordinator Only!

Copyright Carrier Corp. 2008

34

ZC Wiring Figure 26

Copyright Carrier Corp. 2008

35

ZC Wiring Figure 28

Copyright Carrier Corp. 2008

36

Questions ??
?

Copyright Carrier Corp. 2008

37

3V Bypass Controller

Sensor Inputs

Communication

Power

Power: 40 va at 24 vac/vdc 10% (50/60 Hz)

Copyright Carrier Corp. 2008

38

Sensor Inputs
Pressure Sensor

Communication

Actuator Power

3V Bypass Controller
(built in pressure sensor see Figure 9)
Copyright Carrier Corp. 2008

39

Power

Bypass Pressure Filter


Remove cap on low side!
P2
Low

P1
High

Strongly Recommend using


inline filter on high side
RCD# KH10MZ001

Copyright Carrier Corp. 2008

40

Bypass Wiring Figure 7

Copyright Carrier Corp. 2008

41

Bypass Wiring Figure 8

Copyright Carrier Corp. 2008

42

Bypass Wiring Figure 9

Copyright Carrier Corp. 2008

43

Bypass Wiring Figure 10

Copyright Carrier Corp. 2008

44

Questions ??
?

Copyright Carrier Corp. 2008

45

Communication
CCN
Power
+ G - + - G

Power Requirements:
24 vac at 6 va (18 to 32
vac)
(50/60 Hz)

System Pilot
Copyright Carrier Corp. 2008

46

System Pilot
Back Plate

24 vac at 6 va
(18 to 32 vac)

System Pilot Wiring Details


Wire to ZC COMM2 for Local sensor

ZC COMM1 for
system access

24vac HOT + PIN 1


PIN 2
24vac COM PIN 3

May be wired in
PARALLEL ONLY w/ZC
(or UC)!

Copyright Carrier Corp. 2008

47

Bus Wiring/Addressing
PremierLink Controller
Address 0,31

Linkage Coordinator
Address 0,140

Address
0,141

Bypass

System Pilot
Address
0,235
Copyright Carrier Corp. 2008

Address 0,139

Address 0,138

ComfortID

System Pilot
Local Connect

48

System Pilot Local Wiring Details

Local Bus
Wiring is
COMM 2 on
Zone Controller
only
Dedicated for
System Pilot
only
COMM 2: 3wire, Stranded
Shielded 18 to
20 gauge

COMM 1

Zone
Controller

COMM 2

Local Bus

Copyright Carrier Corp. 2008

49

System Pilot
Local Connect

Communication

Temp Sensor

T-56 Space Sensor


Copyright Carrier Corp. 2008

50

T55/T56 Wiring

Copyright Carrier Corp. 2008

51

Temp Sensor
24 Volt Power
Input Voltage :\
24 Vac, 2 VA
Thermistor Type:
10K Type II (CP/MCI)

T-59 Space Sensor


with Digital Display
Copyright Carrier Corp. 2008

52

T59 Wiring Details

Temp Sensor
24 Volt Power

Copyright Carrier Corp. 2008

53

T-56 Space Sensor

with CO2 Sensor

CO2 Sensor

24 Volt Power

Temp Sensor
Communication
s

Copyright Carrier Corp. 2008

54

T56 with CO2 wiring Details


J1
24vac HOT + PIN 1
24vac COM - PIN 2
PIN 3

0-10vdc

May be wired in PARALLEL ONLY w/ZC!

J4
CO2 Sensor

J1
24 VAC

Temp Sensor

J5

Copyright Carrier Corp. 2008

55

Comm
J6

8 Configurable inputs
Discrete inputs can be dry contact or pulsed dry
contact
Analog inputs can be 4 to 20 mA or 0 to 10 vdc

8 Inputs

Temperature inputs can be 5K or


Type II and Type III 10K ohm thermistors
8 Configurable outputs
Discrete outputs are 24 vdc at 80 mA
Analog outputs are 4 to 20 mA or 0 to 10 vdc

8 Outputs

(varies with point type)


Power Requirements
60 va at 24 vac 15%
(1.5a at 33 vdc 15%)
The power terminal is 1 & 2 not 2 & 3
Opposite Comfortable Controller

Copyright Carrier Corp. 2008

o
olt P
V
4
2

w er

Universal Controller
56

Communication
s
Bus

CARRIER
COMFORT
NETWORK
BUS ARCHITECTURE

Copyright Carrier Corp. 2008

57