SYSTEM
PMI Revision 00
PURGE PERMISSIVES
All HFO nozzle valves closed
All pulverisers OFF
All feeders OFF
No MFT condition present
All scanners senses no flame
All Auxiliary Air dampers modulating
TO
FSSS
PMI Revision 00
MFT
RELAY
PMI Revision 00
Air flow less than 30% and boiler load not greater than 30%
Arming:
Always armed
Logic:
Purpose:
Protection Delay:
0 sec INSTANT.
Protection Check:
PMI Revision 00
Arming:
Always armed
Logic:
Purpose :
Protection Delay:
0 sec INSTANT.
Protection Check:
Simulate the signals from FD Fans Electrical Switchgear
November 27, 2016
PMI Revision 00
Arming:
Logic:
All LFO cut off AND All HFO cut off AND All Feeders OFF
Initiation of a mandatory purge cycle to restore furnace
Purpose:
Backup protection to trip remaining equipment (eg. PA
Fans)
0 sec INSTANT.
Protection Check:
Keep oil manual isolating valves in any one elevation any
one corner (done by OPN), simulate status of manual
valve (done by C&I), then give sequence start command
November
2016 corner
PMI Revision 00
7
to27,that
Arming:
4. FLAME FAILURE
Logic:
Protection Delay:
0 sec INSTANT.
Protection Check:
PMI Revision 00
Logic:
Purpose:
0 sec INSTANT.
Protection Check:
PMI Revision 00
Logic:
Purpose:
Protection Delay:
0 sec INSTANT.
Protection Check:
PMI Revision 00
10
Always armed
2 out of 3 logic derived from hydrastep-left-1, hydrastepright-1 and drum level transmitter > 250 mm
Purpose:
Protection Delay:
10 sec.
Protection Check:
PMI Revision 00
11
Logic:
2 out of 3 logic derived from hydrastep-left-2, hydrastepright-2 and drum level transmitter < -375 mm
Purpose:
Protection Delay:
5 sec.
Protection Check:
PMI Revision 00
12
Arming:
Always armed
Logic:
Purpose:
Protection Delay :
10 sec.
Protection Check :
PMI Revision 00
13
Arming:
Always armed
Logic:
Purpose:
Protection Delay:
5 sec.
Protection Check :
Actual.
PMI Revision 00
14
Logic :
All BCW OFF (OR) 2/3 running BCW DP < 0.68 ksc
Purpose:
Protection Delay:
5 sec.
Protection Check:
Equalizing DP transmitters to simulate DP low.
PMI Revision 00
15
PMI Revision 00
16
Logic:
Total Air Flow (Primary Air + Secondary Air) < 30% of full load
air flow (30% of 1800 Tph = 540 Tph)
Purpose:
Protection Delay :
0 sec - INSTANT.
Protection Check :
Actual.
PMI Revision 00
17
PMI Revision 00
18
Logic:
Purpose:
Protection Delay:
10 sec.
Protection Check:
Actual.
November 27, 2016
PMI Revision 00
19
PMI Revision 00
20
PMI Revision 00
21
Arming :
Always armed
Logic:
Purpose:
Protection Delay :
0 sec INSTANT.
Protection Check :
By 24V breaker simulation in MFT panel.
PMI Revision 00
22
Arming:
Always armed
Logic:
Purpose:
Protection Delay:
2 sec.
Protection Check:
By 220V breaker in MFT panel.
PMI Revision 00
23
Logic:
Purpose:
Protection Delay :
0 sec - INSTANT.
Protection Check:
By actually creating frozen output state in processors.
PMI Revision 00
24
Always armed
Logic:
Purpose:
Protection Delay:
0 sec - INSTANT.
Protection Check:
By actually isolating network connections of the processors.
November 27, 2016
PMI Revision 00
25
Arming:
Always armed
Logic:
Purpose:
Protection Delay :
0 sec - INSTANT.
Protection Check :
By actually operating push buttons/through PC.
November 27, 2016
PMI Revision 00
26
Boiler not firing fuel for 5 min (MFT may or may not be reset)
Logic:
If furnace pressure very high > 150 mmwc OR very low < -175
mmwc (AND)
Air Flow > 30% THEN
TRIP all ID Fans and FD Fans
Purpose:
Protection Delay :
Protection
Check:
By simulation at source.
November 27, 2016
PMI Revision 00
27
Logic:
If any major auxiliary (eg. ID, FD, PA, BFP) trips and standby is
not available, unit load is automatically reduced according to
the new capability
Mills are tripped one by one starting from top running mill, at 2
sec delay, until 4 running mills from bottom remain.
Purpose:
Protection Delay:
Protection Check:
PMI Revision 00
28
PMI Revision 00
29
THANK YOU
QUESTIONS ?
PMI Revision 00
30
START PERMISSIVES
PMI Revision 00
31
TRIPS
(3 min)
PMI Revision 00
32
PA FAN
START PERMISSIVES
TRIPS
Fan bearing temperature very high.
Trip from FSSS (MFT).
Discharge damper fails to open.
PMI Revision 00
34
ID FAN
START PERMISSIVES
Hyd. coupling Scoop position minimum.
Inlet guide vane position minimum.
Bearing temperature not high.
Oil temp. and oil level in Hyd. coupling OK.
Lube oil pressure adequate.
Both inlet and outlet dampers closed.
Other ID fan not running or Any FD fan running.
PMI Revision 00
35
TRIP CONDITION
Fan/Motor bearing temperature very high.
Lube oil pressure very low.
Post purge furnace pressure Hi/Low from FSSS.
Discharge dampers/ suction damper fail to open
within specified time (3 min.)
Hydraulic coupling bearing temp. very high
Hydraulic coupling oil temp. very high.
November 27, 2016
PMI Revision 00
36
PERMISSIVES
Discharge valve 1 open.
Discharge valve 2 open.
Motor cavity temp. not high.
Pump cavity suction manifold differential
temp. not high.
Motor cooling water flow adequate.
November 27, 2016
PMI Revision 00
37
TRIPS
PMI Revision 00
38
PMI Revision 00
39
PMI Revision 00
40