Professional Documents
Culture Documents
va= +V
Mode Il is present when S1 is on and S2 is open. The armature
current flows through D2 and S1 and
va= 0
Mode III occurs when S1 is open and S2 is closed. The armature
current flows through S2 and D1, and
va= 0
Mode IV is present when both S1 and S2 are open. The armature
current flows through D2, V, D1 Here
=-V
For 0.5 < < 1, S1, and S2 cannot be open simultaneously(v a is +ve
or 0)
For 0< < 0.5, S1 and S2 cannot be closed together (va is 0 or ve)
Va
Four-Quadrant Control
Method-I :
i) S2 gets closed continuously and S1 and S4 are controlled.
Motor control achieved in Quadrant I and II.
ii) S3 gets closed continuously while S1 and S4 are controlled.
Motor control is in Quadrant III and IV
Minimum switching speed determines minimum voltage and minimum speed.
Method-II
i) Switches S1 and S2 with diodes D1 and D2 provides control in quadrants I and IV
ii) switches S3 and S4 with diodes D3 and D4 gives motor control in quadrants II and III
Zero output voltage is obtained when both switches are on for a period of T. Hence no
limitation in getting low voltage and low speed.
Choppers pairs are controlled separately.
Method-III
Similar to method II but chopper pairs are controlled simultaneously.
Time period for each switch is T.
Dual Converters:
In the simultaneous control, commonly known as
circulating current control, both rectifiers operate
simultaneously.
In the non simultaneous control, also known as
circulating-current-free control, only one rectifier
operates at any given time and another is blocked.
Since the two rectifiers work in different modes, one in rectification and
another in inversion, their instantaneous voltages are not equal.
Closed-Loop Control of DC
Drives
CURRENT CONTROL
Vc to realisation
and
PI - controller
PI controller with error
detector and limiter;
v* and v are reference
and feedback signals respectively.
Converter
A four-quadrant controlled DC
drive
Induction Motor
BRAKING
1. Regenerative braking.
2. Plugging or reverse voltage braking.
3. Dynamic or rheostatic braking
With a positive sequence voltage across the motor terminals, the
operation above synchronous speed gives the regenerative
braking operation (portion BAE).
Similarly, with a negative sequence voltage across the motor
terminals, regenerative braking is obtained for speeds above the
synchronous speed in the reverse direction (portion bae).
Regenerative braking
For regenerative braking to take place, the motor's
speed should be greater than synchronous speed. When
the motor is fed by a fixed frequency source,
regenerative braking is possible only for speeds greater
than synchronous speed.
When the motor is fed by a variable frequency source,
the source frequency can be adjusted to give a
synchronous speed less than the motor speed for any
motor speed; and therefore regenerative braking can be
obtained up to nearly zero speed
Plugging
An induction motor operates in the plugging mode for slips
greater than l. For positive sequence voltages, a slip greater
than 1 is obtained when the rotor moves in the reverse
direction (portion CD)
Since the relative speed between the rotating field and the
rotor remains positive, the motor torque is positive and the
motor draws power from the source. Since the motor is running
in the reverse direction, a positive torque provides the braking
operation.
With negative sequence voltages, plugging takes place on
portion cd, shown by the chain-dotted line. When running in
the forward direction, the motor can be braked by changing
the phase sequence of the motor terminal voltages by simply
interchanging the connections of any two motor terminals.
DC Dynamic Braking
The flow of direct current through the stator windings sets up
a stationary magnetic field. The relative speed between the
stationary stator field and the moving rotor is now negative.
Consequently, 3-phase voltages of reverse polarity and
phase sequence (compared to the motoring in the same
direction) are induced in the rotor.
The resultant three-phase rotor currents produce a rotating
field, moving at the rotor speed in the direction opposite to
that of rotor, thus giving a stationary rotor field.
Since both stator and rotor fields are stationary and rotor
current flows in the reverse direction, a steady braking
torque is produced at all speeds.
SPEED CONTROL
1. Variable terminal voltage control.
2. Variable frequency control.
3. Rotor resistance control.
4. Injecting voltage in the rotor circuit.
FOUR-QUADRANT CONTROL
CLOSEO-LOOP CONTROL
For a frequency f
Then
To get operation at a nominal value of 1mfor all values of per-unit
frequency a, with Is remaining fixed at Is 1.
PWM Inverters
Because of a low harmonic content in the inverter
output voltage, the drive has smooth low-speed
operation, free from torque pulsations and cogging, and
with a lower derating of the motor and higher efficiency.
Current Sources
, no load speed is
No load speed:
Above eqn shows that the no-load speed can be changed
from synchronous to standstill by varying Vr from 0 to (E/a T1).
Further, if Vr is reversed, s will be negative and the motor noload speed will be higher than the synchronous speed.
The relative speed between the stator field and the rotor will
now be the opposite of that for speeds less than the
synchronous speed.
Hence, the phase sequence and direction of the rotor induced
voltages will also be opposite.
Thus, for operation above synchronous speed, both the
polarity and the phase sequence of the injected voltage will
have to be changed.
where V is the stator phase voltage and aTI is the stator to rotor turns
ratio.
The dc output voltage of the line commutated inverter is given by
Torque
Synchronous Motors
Self control
In self-control, as the rotor speed changes, the armature
supply frequency is also changed proportionately so the
armature field always moves at the same speed as the
rotor.
This ensures that the armature and rotor fields move in
synchronism for all operating points.
Consequently, a self-controlled synchronous motor does not
pull out of step and does not suffer from the hunting
oscillations and instability associated with a step change in
torque or frequency when controlled from an independent
oscillator.
Self-control ensures that for all operating points the
armature and rotor fields move exactly at the same speed.
Consequently, the motor cannot adjust the torque angle ('
or ) mechanically as in conventional operation
where ids, and iqs, are the q and d axes currents in the
synchronous reference frames that are obtained by
projecting the stator current phasor on the q and d axes
respectively.
The current phasor magnitude remains the same
regardless or the reference frame chosen to view.
The current phasor is produces the rotor flux r, and the
torque Te.
The component of current producing the rotor flux
phasor has to be in phase with r,.
Therefore resolving the stator current phasor along r,
reveals that the component if is the field-producing
component.
The perpendicular component iT is hence the torqueproducing component.
Vector control schemes arc classified according to how the field angle is
acquired.
If the field angle is calculated using terminal voltages and currents or Hall
sensors or flux-sensing windings. then it is known as direct vector Control.
The field angle can also be obtained by using rotor position measurement
and partial estimation with only machine parameters but not any other
variables such as voltages or currents.
Using, this field angle leads to a class of control schemes known as
indirect vector control.
Algorithm
(i) Obtain the field angle f.
(ii) Calculate the flux-producing component of current if * : for a required rotor flux
linkage r*; By controlling only this field current the rotor flux linkages are controlled.
It is very similar to the separately- excited dc machine
(iii) From r* ; and the required Te*;. calculate the torque-producing component of stator
current iT *; Controlling the torque-producing component current when the rotor flux linkages
phasor is constant gives an independent control of electromagnetic torque. Steps (ii) and (iii)
enable a complete decoupling of flux- from torque-producing channels in the induction
machine.
(iv) Calculate the stator-current phasor magnitude is*. from the vector sum of iT* and if*.
(v) Calculate torque angle From the flux- and torque-producing components of the stator-current
commands.
(vi) Add T and f and to obtain the stator current phasor angle s.
(vii) By using the stator-current phasor angle and its magnitude the
required slator-current commands are found by going through
the
qdo transformation to abc variables:
rotor currents
From all the stator and rotor currents torque, the flux and field angle
can be computed as
MAR - Magnitude
and Angle Resolver
block
INDIRECT VECTOR-CONTROL
IMPLEMENTATION OF AN INDIRECT
VECTOR-CONTROL SCHEME
The flux is kept at rated value up to rated speed: above that. the
flux is weakened to maintain the power output constant.
The rotor position is measured with an encoder/synchronous
resolver and converted into necessary digital information for
feedback
1. Slip Calculation
Speed can be calculated from slip frequency sl from the
relation
r = e - sl , where e = stator frequency ( rev/s)
EK
F
NN based control