Todd Brown
Business Development Manager - Chillers
AGENDA
Low temperature, low flow
Primary-Secondary vs Variable Primary Flow
Chillers in Series-Series Counterflow
Chiller-Tower Optimization
Goal:
Without Sacrificing:
Reliability, Efficiency, & Comfort
Design
(ECWT): 85 F(29.4C)
Evaporator and
condenser
temperature
differences: 10 F
(5.6C)
T
P
M
U
S
S
A
S
N
IO
Consumption:
256 kW (0.569 kW/ton)
Evaporator
pressure drop: 21.0 ft
Condenser
pressure drop: 21.3 ft
Power rating:
30 hp
Tower static head:
10.0 ft
Design Formulas
gpm x PD
hp =
3960 x pump efficiency
0.746 x hp
kW =
motor efficiency
T
P
M
U
S
S
A
S
N
IO
System conditions
System head: 80 ft
Bundle head: 21.0 ft
Flow rate: 1080 gpm
Pump power
36.7 hp
29.5 kW
System conditions
Pump power
26.0 hp
20.8 kW
Total kW
330.4
Chiller
Chilled Water Pump
Condenser Water Pump
Cooling Tower
Total kW
ARI
42, 16dT
44 F, 14dT
44 F, 14dT; 83.3 F
42 F, 16dT
2.4/3.0
256.0
29.5
20.8
24.1
1.5/3.0
268.0
16.2
20.8
24.1
1.7/2.0
288.0
19.0
11.3
16.0
1.7/2.0
269.0
19.0
11.3
24.1
1.5/2.0
296.0
16.2
11.3
16.0
330.4
329.1
334.6
323.4
339.5
Cooling tower kW
T
P
M
U
S
S
A
S
N
IO
Tower energy at part load based on being linear with speed reduction
Decoupled Systems
Variable Flow Systems
moving to
Primary
Secondary
58.0F
design
58.0F
857 gpm
(each)
58.0F
857 gpm
857 gpm
857 gpm
44.0F
44.0F
44.0F
primary
pumps
2571 gpm
58.0F
58.0F
2571 gpm
bypass
(decoupler)
secondary
pumps
44.0F
2571 gpm
Variable
Primary
58.0F
58.0F
857 gpm
857 gpm
44.0F
44.0F
design
58.0F
857 gpm
44.0F
P
typical)
2571 gpm
58.0F
58.0F
2571 gpm
44.0F
2571 gpm
off
56.0F
1050
44.0F
P
typical)
1050 gpm
56.0F
56.0F
1050 gpm
44.0F
1050 gpm
56.0F
525
56.0F
525
44.0F
P
typical)
1050 gpm
56.0F
56.0F
1050 gpm
44.0F
1050 gpm
Primary
Secondary
design
off
51.2F
857 gpm
(each)
51.2F
857 gpm
857 gpm
44.0F
44.0F
primary
pumps
44.0F
51.2F
56.0F
1050 gpm
1714 gpm
664 gpm
secondary
pumps
44.0F
1050 gpm
Simplified Control
Unfetters chillers from
flow-based control
Operates distribution pumps
to transport water
not to start/stop chillers
Improved Reliability
VFP systems:
Reduces total annual plant energy 3-8%
Reduces first cost 4-8%
Reduces life-cycle cost 3-5%*
*Relative to conventional Decoupled chilled-water systems.
VPF System
More information
unsuited for
moving to
Series Evaporator
Systems
89.6F
96.63F
57F
103.82F
48.96F
96.63F
48.96F
VFD
89.6F
41F
103.82 F
96.63 F
Single
Compressor
Chiller
Lift
62.82 F
Upstream Chiller
Downstream Chiller Lift
Lift
55.63 F
54.86 F
Series-Counter flow
Arrangement
48.96 F
41 F
41 F
ChillerTower Optimization
Do It Right!
chillertower optimization
The Question
kW
chillertower optimization
On the building!
chillertower optimization
In Summary
First Operating
Cost
Cost
Questions or Comments?