System functions
s
Pow
Trai er
ni
Cen ng
Power Transmission and Distribution Serviceter
Overview
The Solution:
SICAM PAS,
Power Automation System for Power
Automation
Areas of Application
Decentralize Substation Automation System with IEC 61850
Decentralize Substation Automation System with Profibus
FMS
Serial interface of IEDs and substations,
with e.g. IEC 60870-5-103, IEC 60870-5-101
Local visualization, archiving and logging
using the SIMATIC WinCC Features
SICAM PAS CC
Remote visualization, archiving and logging
using the SIMATIC WinCC Features
SIMATIC Web Navigator based on SICAM PAS CC
Communication to control centers
Serial interface with IEC 60870-5-101 and DNP V3.0 (Level
2)
Data transmission over LAN/ WAN with Ethernet TCP/IP and
IEC 60870-5-104
Automation with CFC (and structured text)
Data exchange using OPC
Data acquisition and data transmission
under real-time conditions
Copyright SIEMENS AG PTD SE 2004. All rights reserved.
Areas of Application
Gateway function
Data input e.g. IEC 60870-5-103
Data output data base or OPC - Client
Data input e.g. with IEC IEC 60870-5-103
Data output IEC 60870-5-104
The application options of
SICAM PAS combined with SICAM PAS CC
and PC technology provide an optimal opportunity to
Participate in innovations
At the same time, they take into account the
requirements
concerning power system operation (logs, performance
demands etc.)
Unique Features
Modular and scalable
in price and function basic package and options
Flexible
Option automation
Realization of functional, project-specific applications
Option OPC - client
Communication with automation systems (SIMATIC)
Basis for development of third party IED protocols
Package with integrated operation & configuration properties
Online switching to configuration mode is possible at anytime.
Modifications and expansions can be carried out online.
No generation and loading of configuration data into a separate
runtime system necessary.
Distributed System Full Server / DIP-architecture*)
Distributing the system functionality among several**) PCs due to
technical (system load) or topological considerations
Copyright SIEMENS AG PTD SE 2004. All rights reserved.
RunTime RunTime
SICAM PAS UI
Configuration
Optional packets
Protocols for connection of IEDs and substations
IEC 61850
Profibus FMS (SICAM/SIPROTEC-specific protocol) Options
IEC 60870-5-103
IEC 60870-5-101 Master
DNP V3.00 Master
Profibus DP
Modbus
ILSA
Protocols for connection to higher level control centres
IEC 60870-5-101 Slave
IEC 60870-5-104
DNP V3.00 Slave
Open communication e.g. for data exchange with SIMATIC (and 3rd party devices)
OPC Client
Automation with CFC and Structured Text (ST)
OPC-Client - Communication
OPC
Data exchange and communication with OPC Server
Client
using the OPC Client
The communication partner OPC Server can be located
on the same PC or on another PC connected with TCP/IP (Ethernet)
The open communication can especially be used for the data exchange with
automation devices e.g. SIMATIC
Example
A Simatic S7-400 is connected to a SICAM PAS Station Unit through a CP1613
and via the Ethernet. The communication used between the S7-400 and the
CP1613 is the S7 protocol. An OPC server for the CP1613 card is available
from SIMATIC. In this way data can be exchanged with the SICAM PAS OPC
Client.
Ethernet, S7-Protocol
Station Unit S7-400
SICAM SIMATIC
CP
PAS
1
OPC OPC OPC 6
Client Server 1
3
Automation - CFC
The Automation within SICAM PAS is implemented
with a SoftPLC. Automation
Automation functions are configured with function
blocks (CFC = Continuous Function Chart) or with
Structured Text (ST).
In addition to the
standard function
blocks, an extensive
library of specific,
system tested PAS
function blocks is also
available
Automation - CFC
CFC function blocks for typical substation automation tasks are
available
Command processing
Command execution and Command derivation Automation
Signal processing
Signal derivation
Signal filtering
Signal inversion and conversion
Grouping of signals into one
Transformer taps- and bit pattern comparison
Interlocks
Measured- and counter value processing
Non linear conversion
Limit value monitoring
Drag indicator
Calculation of averages
Blocks for arithmetic and comparisons
Switching sequences
Control Authority
The control authority defines which level (bay, station or SCADA) is
authorized for switchgear operation
In addition to the local / remote setting on the bay device, it is also
possible to switch between local and remote control at the station level
Furthermore, the control authority can also be configured to be channel
specific, e.g. TC2 is authorized for operation and the other TC channels
and the local control is not.
SICAM
PAS CC
Station Unit
TCC1 TCC2 TCC3
DSI
Auto
Bay Blocking
In the case of maintenance works it may be useful to interrupt
the data flow from the respective bay to the system
(in command and monitoring direction). For the Operators, the
bay status appears as frozen.
The bay blocking can be activated device specific
SICAM
PAS CC
Station Unit
TCC1 TCC2 TCC3
DSI
Auto
Telecontrol Blocking
LikeBay Blocking, in case of maintenance works, it may
be useful to interrupt the data flow to the SCADA system
while keeping the full functionality at the station level
Furthermore, it is possible to configure the station
blocking for specific channels, while keeping others fully
functional
Telecontrol Blocking SICAM
disabled PAS CC
Station Unit
TCC1 TCC2 TCC3
DSI
Auto
Time Synchronization I
Use of a time-synchronization module in the Station Unit
Hopf card (DCF77 or GPS)
The Station Unit accepts the time synchronization signal
for the connected devices (if the communication protocol supports
it) and, if used
for the HMI PC connected via Ethernet (SICAM PAS CC)
SICAM
PAS CC
Antenna
Ethernet (TCP/IP)
Station Unit
IEC 61850
T103
T101
Profibus FMS
Time Synchronization II
A separate time master for Ethernet can be used
especially in configuration with the Ethernet station bus
(IEC 61850). It is the SNTP-Server (Simple Network Time
Protocol). It synchronizes all connected devices (SNTP-
Clients), incl. the Station Unit
Meinberg or Siemens SICLOCK
Also in this case, the Station Unit is the time master
for all devices which are connected via usual
communication protocols.
Antenna
Station Unit
SICAM
PAS CC
Fault Recording I
Fault recording of protection devices connected with
IEC 60870-5-103, Profibus FMS and IEC 61850
Automatic transmission of fault records
Automatic archiving of fault records in communication-specific folders on the
Full Server or DIP
Evaluation of fault records with SICAM Recpro
SICAM Recpro Explorer
for clear navigation of the fault recording archives
selectable display of the technical structure or the station topology
SICAM Recpro Collector
for the superior level archiving of fault records of several station units
on a central station unit
after transmission of fault records to the superior level station unit, the
fault records may be deleted in the original archive (optional, in
particular in connection with embedded systems with little disc space)
Comtrade Viewer
Program delivered within the scope of SICAM Recpro for visualisation
of fault records)
The SIGRA 4 software can be used for a more sophisticated analysis of fault
records (not included in the delivery)
Copyright SIEMENS AG PTD SE 2004. All rights reserved.
Fault Recording II
Ethernet TCP/IP
IEC 61850
IEC 60870
Profibus FMS -5-103
Redundancy I
Redundancy Level1
Redundant usage of the SICAM
PAS Station Unit
Useable for the connection of
IEDs with communication
interfaces
IEC 61850
Profibus FMS
Based on the function
Software Redundancy SICAM
PAS CC works with one Station
Unit at any time
Redundancy II
Redundancy Level2
on top of a redundant SICAM
PAS Station Unit SICAM PAS
CC works as a redundant
server application with
several clients for one or
more substations or
independent substation parts
redundant SICAM PAS
Station Unit
redundant SICAM PAS CC
Server
SICAM PAS CC in
Client/Server architecture
Copyright SIEMENS AG PTD SE 2004. All rights reserved.
Platform
Operating Systems
Windows XP professional
Windows XP embedded
Windows 2000 professional
Windows 2000 Server
System requirements
Pentium III Processor 800 MHz
256 Mbyte RAM
512 Mbyte harddisk capacity
VGA card for 1280 x 1024 resolution
CDROM drive
If used together with SIMATIC WinCC, the system requirements for
SIMATIC WinCC must also be observed!
System limits
Interfaces to IEDs / substations
Profibus FMS
Max. 2 CP5613 per Station Unit max. 30 devices each
Profibus DP
We recommend max. 2 CP5613 max. 30 devices each to one
Full-Server or DIP
IEC60870-5-103, IEC60870-5-101, DNP V3.00, Modbus
For enhanced performance it is recommended to use COM
expanders (e.g.Rocket Ports) or serial hubs
Max. 2 Rocket Ports 32 interfaces each
Max. 100 devices to one Full Server or DIP
IEC 61850
Max. 100 devices to one Full Server or DIP
max. 100 devices to one PAS Full Server / max. 5000
variables
max. 100 devices to one PAS DIP / max. 5000 variables
max. 150 devices to one PAS system
(Full Server and DIP) / max. 10000 variables