You are on page 1of 40

ECE 476

Power System Analysis


Lecture 19: Short Circuit Analysis

Prof. Tom Overbye


Dept. of Electrical and Computer Engineering
University of Illinois at Urbana-Champaign
overbye@illinois.edu
Announcements
Please read Chapters 7 and 8
HW 7 is due today
HW 8 is 7.6, 7.14, 7.20, 7.29, 8.3; it will be covered
by an in-class quiz on due on Thursday Nov 3 (hence
you will not need to turn it in)
Exam 2 is during class on Tuesday November 15
Final exam is on Monday December 12, 1:30-4:30pm

2
Fault Analysis
The cause of electric power system faults is
insulation breakdown
This breakdown can be due to a variety of different
factors
lightning
wires blowing together in the wind
animals or plants coming in contact with the wires
salt spray or pollution on insulators

3
Fault Types
There are two main types of faults
symmetric faults: system remains balanced; these faults
are relatively rare, but are the easiest to analyze so well
consider them first.
unsymmetric faults: system is no longer balanced; very
common, but more difficult to analyze
The most common type of fault on a three phase
system by far is the single line-to-ground (SLG),
followed by the line-to-line faults (LL), double
line-to-ground (DLG) faults, and balanced three
phase faults

4
Lightning Strike Event Sequence
1. Lighting hits line, setting up an ionized path to
ground
30 million lightning strikes per year in US!
a single typical stroke might have 25,000 amps, with a
rise time of 10 s, dissipated in 200 s.
multiple strokes can occur in a single flash, causing the
lightning to appear to flicker, with the total event
lasting up to a second.
2. Conduction path is maintained by ionized air after
lightning stroke energy has dissipated, resulting in
high fault currents (often > 25,000 amps!)

5
Lightning Strike Sequence, contd
1. Within one to two cycles (16 ms) relays at both
ends of line detect high currents, signaling circuit
breakers to open the line
nearby locations see decreased voltages
2. Circuit breakers open to de-energize line in an
additional one to two cycles
breaking tens of thousands of amps of fault current is no
small feat!
with line removed voltages usually return to near normal
3. Circuit breakers may reclose after several seconds,
trying to restore faulted line to service
6
Worldwide Lightning Strike Density

Units are Lightning Flashes per square km per year; Florida is


top location in the US; very few on the West Coast, or HI, AK. This
is an important consideration when talking about electric reliability!
7
Source: http://science.nasa.gov/science-news/science-at-nasa/2001/ast05dec_1/
Fault Analysis
Fault currents cause equipment damage due to both
thermal and mechanical processes
Goal of fault analysis is to determine the
magnitudes of the currents present during the fault
need to determine the maximum current to insure devices
can survive the fault
need to determine the maximum current the circuit
breakers (CBs) need to interrupt to correctly size the CBs

8
RL Circuit Analysis
To understand fault analysis we need to review the
behavior of an RL circuit

v(t )
2 V cos( t )

Before the switch is closed obviously i(t) = 0.


When the switch is closed at t=0 the current will
have two components: 1) a steady-state value
2) a transient value
9
RL Circuit Analysis, contd
1. Steady-state current component (from standard
phasor analysis)
2V cos(t )
i ac (t )
Z
where Z R 2 ( L)2 R 2 X 2
V
I ac
Z

10
RL Circuit Analysis, contd

2. Exponentially decaying dc current component


t
i dc (t ) C1e T

where T is the time constant, T L R


The value of C1 is determined from the initial
conditions:
2V t
i (0) 0 i ac (t ) i dc (t ) cos(t Z ) C1e T
Z
2V
C1 cos( Z ) which depends on
Z
11
Time varying current

12
RL Circuit Analysis, contd
Hence i(t) is a sinusoidal superimposed on a decaying
dc current. The magnitude of i dc (0) depends on when
the switch is closed. For fault analysis we're just
2V
concerned with the worst case: C1
Z
i (t ) i ac (t ) i dc (t )
2V 2V t T
i (t ) cos(t ) e
Z Z
2V t
(cos(t ) e T )
Z
13
RMS for Fault Current

2V t
The function i(t) (cos(t ) e T ) is not periodic,
Z
so we can't formally define an RMS value. However,
as an approximation define
2 2
I RMS (t ) iac (t ) idc (t )
2t
2 2 T
I ac 2 I ac e
This function has a maximum value of 3 I ac
Therefore the dc component is included simply by
multiplying the ac fault currents by 3
14
Generator Modeling During Faults
During a fault the only devices that can contribute
fault current are those with energy storage
Thus the models of generators (and other rotating
machines) are very important since they contribute
the bulk of the fault current.
Generators can be approximated as a constant
voltage behind a time-varying reactance

'
Ea
15
Generator Modeling, contd

The time varying reactance is typically approximated


using three different values, each valid for a different
time period:
X"d direct-axis subtransient reactance
X 'd direct-axis transient reactance
Xd direct-axis synchronous reactance

16
Generator Modeling, contd
For a balanced three-phase fault on the generator
terminal the ac fault current is (see page 386)
1 1 1 t
Td'

' e
X d X d X d
i ac (t ) 2Ea' sin(t )
t "
1 1 Td
"
' e
X d X d
where
"
Td direct-axis subtransient time constant ( 0.035sec)
Td' direct-axis transient time constant ( 1sec)
17
Generator Modeling, cont'd
The phasor current is then
1 1 1
t
Td'

' e
X d X d X d
I ac Ea'
t "
1 1 Td
X " X ' e
d d
The maximum DC offset is
2 Ea' t
TA
I DC (t ) "
e
Xd
where TA is the armature time constant ( 0.2 seconds)
18
Generator Short Circuit Currents

19
Generator Short Circuit Currents

20
Generator Short Circuit Example
A 500 MVA, 20 kV, 3 is operated with an internal
voltage of 1.05 pu. Assume a solid 3 fault occurs
on the generator's terminal and that the circuit
breaker operates after three cycles. Determine the
fault current. Assume
X d" 0.15, X d' 0.24, X d 1.1 (all per unit)
" '
Td 0.035 seconds, Td 2.0 seconds
TA 0.2 seconds

21
Generator S.C. Example, cont'd
Substituting in the values
1 1 1 t 2.0

1.1 0.24 1.1 e
I ac (t ) 1.05
1 1 e t 0.035
0.15 0.24
I ac (0) 1.05 7 p.u.
0.15
500 106
I base 3
14,433 A I ac (0) 101,000 A
3 20 10
t
I DC (0) 101 kA 2 e 0.2 143 k A I RMS (0) 175 kA
22
Generator S.C. Example, cont'd
Evaluating at t = 0.05 seconds for breaker opening
1 1 1 0.05 2.0

1.1 0.24 1.1 e
I ac (0.05) 1.05

1 1 e 0.05
0.035
0.15 0.24

I ac (0.05) 70.8 kA
0.05
I DC (0.05) 143 e 0.2 kA 111 k A
I RMS (0.05) 70.82 1112 132 kA

23
Network Fault Analysis Simplifications

To simplify analysis of fault currents in networks


we'll make several simplifications:
Transmission lines are represented by their series
reactance
Transformers are represented by their leakage reactances
Synchronous machines are modeled as a constant voltage
behind direct-axis subtransient reactance
Induction motors are ignored or treated as synchronous
machines
Other (nonspinning) loads are ignored

24
Network Fault Example

For the following network assume a fault on the


terminal of the generator; all data is per unit
except for the transmission line reactance

generator has 1.05


terminal voltage &
supplies 100 MVA
with 0.95 lag pf
19.5
Convert to per unit: X line 2
0.1 per unit
138
100 25
Network Fault Example, cont'd

Faulted network per unit diagram

To determine the fault current we need to first estimate


the internal voltages for the generator and motor
For the generator VT 1.05, SG 1.018.2
*
1.018.2 '
I Gen 0.952 18.2 Ea 1.1037.1
1.05 26
Network Fault Example, cont'd
The motor's terminal voltage is then
1.050 - (0.9044 - j 0.2973) j 0.3 1.00 15.8
The motor's internal voltage is
1.00 15.8 (0.9044 - j 0.2973) j 0.2
1.008 26.6
We can then solve as a linear circuit:
1.1037.1 1.008 26.6
If
j 0.15 j 0.5
7.353 82.9 2.016 116.6 j 9.09

27
Fault Analysis Solution Techniques
Circuit models used during the fault allow the
network to be represented as a linear circuit
There are two main methods for solving for fault
currents:
Direct method: Use prefault conditions to solve for the
internal machine voltages; then apply fault and solve
directly
Superposition: Fault is represented by two opposing
voltage sources; solve system by superposition
first voltage just represents the prefault operating point
second system only has a single voltage source

28
Superposition Approach

Faulted Condition

Fault is represented
by two equal and
Exact Equivalent to Faulted Condition opposite voltage
sources, each with
a magnitude equal
to the pre-fault voltage

29
Superposition Approach, contd

Since this is now a linear network, the faulted voltages


and currents are just the sum of the pre-fault conditions
[the (1) component] and the conditions with just a single
voltage source at the fault location [the (2) component]
Pre-fault (1) component equal to the pre-fault
power flow solution
Obviously the
pre-fault
fault current
is zero!

30
Superposition Approach, contd

Fault (1) component due to a single voltage source


at the fault location, with a magnitude equal to the
negative of the pre-fault voltage at the fault location.

I g I (1) I g(2) Im I m(1) I m(2)


g

I f I (1)
f I (2)
f 0 I (2)
f
31
Two Bus Superposition Solution
Before the fault we had E f 1.050,
I (1) 0.952 18.2 and I m(1) 0.952 18.2
g

Solving for the (2) network we get


(2) Ef 1.050
Ig j7
j0.15 j0.15
(2) E f 1.050 This matches
Im j 2.1
j0.5 j0.5 what we
calculated
I (2)
f j 7 j 2.1 j 9.1 earlier
I g 0.952 18.2 j 7 7.35 82.9
32
Extension to Larger Systems
The superposition approach can be easily extended
to larger systems. Using the Ybus we have
Ybus V I
For the second (2) system there is only one voltage
source so I is all zeros except at the fault location
M
0 However to use this

I I f approach we need to
first determine If
0
M 33
Determination of Fault Current
Define the bus impedance matrix Z bus as
1
Z bus @ Ybus V Z busI

M V1
(2)

(2)
Z11 L Z1n 0 V2

Then M O M I f M

Z n1 L Z nn 0 Vn(2) 1

M (2)
Vn
For a fault a bus i we get -If Zii V f Vi(1)

34
Determination of Fault Current
Hence
Vi(1)
If
Zii
Where
Zii @ driving point impedance
Zij (i j ) @ transfer point imepdance
Voltages during the fault are also found by superposition
Vi Vi(1) Vi(2) Vi(1) are prefault values

35
Three Gen System Fault Example

For simplicity assume the system is unloaded


before the fault with
E g1 Eg 2 E g 3 1.050
Hence all the prefault currents are zero.
36
Three Gen Example, contd

15 10 0
Ybus j 10 20 5

0 5 9
1
15 10 0
Zbus j 10 20 5

0 5 9
0.1088 0.0632 0.0351
j 0.0632 0.0947 0.0526

0.0351 0.0526 0.1409
37
Three Gen Example, contd
1.05
For a fault at bus 1 we get I1 j 9.6 I f
j 0.1088
0.1088 0.0632 0.0351 j 9.6
V (2) j 0.0632 0.0947 0.0526 0

0.0351 0.0526 0.1409 0
1.050
0.600

0.3370

38
Three Gen Example, contd

1.050 1.050 0 0
V 1.050 0.606 0 0.444 0

1.050 0.337 0 0.713 0

39
PowerWorld Example 7.5: Bus 2 Fault

One Five Four Three


7 pu 11 pu

slack

0.724 pu 0.579 pu 0.687 pu


0.000 deg 0.000 deg 0.000 deg
0.798 pu
0.000 deg

0.000 pu Two
0.000 deg

40

You might also like