Professional Documents
Culture Documents
Power Transmission
and Distribution
Siemens AG 2009
7SS52
Distributed Busbar and Breaker Failure Protection
Page 2 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Directory
Introduction
Function overview
Protection algorithms
Page 3 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Introduction
Page 4 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Need for busbar protection
power concentration
Page 5 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Need for busbar protection
A busbar is
a point of convergence of many circuits
a concentration of power
high, destructive fault currents result !
A busbar fault
endagers the stability of the grid
a fast and selective fault clearance is required (200
100ms incl. CB operation)
a high degree of availability/ dependability is a demand
(EHV: redundant BBP main1/main2)
leads to serious damages of the switchgear
fastest and selective fault clearance is required
may endanger human live
fastest fault clearance is required >
Page 6 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Reasons and probability of a busbar fault
Reasons
mechanical problems (isolators, CTs)
insulation problems (pollution, flash over)
human errors (switch-onto-fault)
Probability
ca. 1 fault / 10 years
but: the effects can be tremendous!!
(outage, cost)
Page 7 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Fundamental terms
Each electrical node is processed by the basic equation of 1st Kirchhoffs law
(the sum of all currents must be zero in a fault free condition)
The limits of an electrical node are given by the current transformers >
Page 10 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Relevant elements
for a busbar protection configuration
Mandatory:
Busbars
BB-disconnectors
current transformers
Optional:
Line isolators
Circuit breaker
Page 11 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS50/51/52 Family highlights
Page 14 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Why a numerical busbar protection?
Page 15 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Why a distributed busbar protection?
Page 19 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Distributed system
1,5 km
2 fibre optics
bay unit
50 50 50 50
Page 21 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Function overview
Page 23 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
The 4 S of a perfect substation protection
Page 24 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS52 Protection function overview
Page 25 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS52 Overview (1)
Page 26 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS52 Overview (2)
end fault protection for faults between CB and CT for each feeder
breaker failure mode low current (e.g. with Buchholz protection trip) >
Page 27 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS52 Overview (3)
Page 28 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Maximum substation configuration
Page 29 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Hardware and function
splitting
Page 30 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
System structure (1)
central unit
ZPS ZPS ZPS modular system
(BSZ1) (BSZ2) (BSZ3) EAZ D-CPU PS
DPR DPR DPR
ZPS
few types of
(SBK) components
DPR DPR DPR DPR DPR DPR
ZPS
(SK1)
ZPS
(SK2)
ZPS
(SK3)
ZPS
(SK4)
ZPS
(SK5)
ZPS
(SK6)
easy to assemble
1 2 8 48
easy to extend >
bay 1 bay 2 bay 48
Page 31 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
System structure (2)
central unit
ZPS ZPS ZPS D-CPU
(BSZ1) Calculation (BSZ2) Calculation (BSZ3) Calculation
Master
System checkzone even odd
DPR DPR DPR DPR
control samples samples
ZPS
(SBK)
1 2 8 48
bay 1 bay 48
Page 32 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS522 Central unit (front)
Page 33 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS522 Central unit (rear)
Page 34 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Jobs of the central unit
Page 35 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS522 Central unit: connection diagram
Page 36 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS523 Bay unit
Page 37 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS525 Bay unit
Page 38 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Jobs of the bay unit
Page 39 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS523 Bay unit: connection diagram
4 current inputs
20 binary inputs
9 trip contacts
1 alarm contact
2 live contacts (NC)
Binary I/0
configuration
is examplary
Page 40 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS525 Bay unit: connection diagram
4 current inputs
10 binary inputs
8 trip contacts
1 alarm contact
1 live contact (NC)
Binary I/0
configuration
is examplary
Page 41 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Communication and
Configuration
Page 42 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Centralized and local operation
DIGSI 4
operation of
el. RS 232 bay unit
DIGSI 4
operation of
central unit
and bay units
2 optical fibers
el. RS 232
Page 43 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Local operation of bay unit 7SS523
indication of
diff and stab currents
local currents IL1, IL2, IL3, IE
disconnector positions, trip, status
Page 47 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Busbar and disconnector configuration,
online visualisation
configuration and
operation of 7SS52 with
DIGSI 4
configuration as with
display editor
library of static and
dynamic symbols, user
defined possible as well
connection of the
dynamic symbol with the
respective device (i.e.
CB, disconnector),
measured value
standard typicals are
provided, new typicals
can be stored
online visualisation
Page 48 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Fault record
Page 49 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Security measures
Page 50 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Measures to detect external failures
Page 51 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Security against overfunction
3-out-of-3 trip control for the trip relays of each bay unit
trip relay
L- L+
Bay unit
Page 52 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Measures to handle internal failures
Page 53 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
tripping characteristic
Idiff
tripping
area
stabilizing
area
Istab*
Page 54 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
tripping characteristic (ext. fault/ load)
Idiff
external fault
external fault or Idiff = 0
operation
Istab = |I1|+|I2|+...|In|
condition
Istab*
Page 55 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
tripping characteristic (CT errors)
Idiff
CT errors CT errors
Idiff ~ CTerrors
Istab = |I1|+|I2|+...|In|
Istab*
security for
CT errors
Page 56 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
tripping characteristic (CT saturation / k-factor)
A B Istab*
Page 57 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
tripping characteristic
Istab*
security for
CT errors and
CT trouble
Page 58 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Selective zones
selective
zone 1
selective
zone 2
Page 59 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Checkzone = overall protection
checkzone
Page 60 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Selective zones + checkzone
selective
zone 1
selective checkzone
zone 2
Page 61 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Disconnector replica
status evaluation (1)
Page 62 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
Disconnector replica
status evaluation (2)
NO NC comment reaction
0 1 disc. open
0 0 running time start of supervision
(=> disc. closed) timer
1 0 disc. closed
0 0 dc fail (0/0 all "old position" resp.
discs of a bay) disc. closed" *
1 1 disturbance "old position" resp.
disc. closed" *
*) settable
Page 63 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
End fault protection (EFP) for feeders
Page 64 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
End fault protection EFP (CT lineside)
2) with EFP
feeder current is removed from bus A measurement
+ no unnecessary trip of bus A
intertrip signal by O/C function of bay unit to trip
CB at remote line side
+ fast fault clearance
Page 65 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
CT layout parameters
no numerical limit of max/min-CT ratio, but the weakest CT must fulfill the
requirements
Page 67 Oct-07
Siemens
Power Transmission AG 2009
and Distribution
7SS52 Busbar Protection
Power Transmission
and Distribution
www.siprotec.com
Siemens AG 2009