HOSE REEL
BREAK TANK
PUMP SYSTEM
High 400 40
D = 19 mm D = 25 mm
18 18
23 23
30 24
37 30
40 37
Riser size:
Diameter, D Building
)mm( height (m)
50 15
64 15 <
Hf = q2*25*L*105/d5
08/23/17 BUILT ENVIRONMENT 48
Design of Hose Reel System
Taking L= 1.5 L physical= 1.5*15 = 22.5 m
(up-feed)
= 1.5*3 = 4.5 m (down-feed)
Hf = q2*25*L*105/d5 = 0.18 m
(up-feed)
= 0.04 m (down-feed)
08/23/17 BUILT ENVIRONMENT 49
Design of Hose Reel System
Total head is then:
Htotal =HA + H f + Hstatic
=30.6+0.18+15=45.78 m
(up-feed)
=30.6+0.04-3.0 = 27.64 m
(downfeed)
Thus the system specifications are:
HOSE REEL
BREAK TANK
PUMP SYSTEM
Sprinkler Heads
Arrangements
08/23/17 BUILT ENVIRONMENT 53
Design of Sprinkler Installations
8 Piping network diameters Table 12, p. 59 Tables 13&14, p. 64 Table 15, p.66
9 Flow rate in the riser (l/min) 1890-2830 2650-3780 b
Basic information:
Max number of sprinklers per branch is 8.
Steel Copper
1 in. 2 sprinklers 1 in. 2 sprinklers
11/4 in. 3 sprinklers 11/4 in. 3 sprinklers
11/2 in. 5 sprinklers 11/2 in. 5 sprinklers
2 in. 10 sprinklers 2 in. 12 sprinklers
21/2 in. 30 sprinklers 21/2 in. 40 sprinklers
3 in. 60 sprinklers 3 in. 65 sprinklers
31/2 in. 100 sprinklers 31/2 in. 115 sprinklers
4 in. See NFC 4 in. See Section 5-2
For SI units, 1 in. = 25.4 mm.
Steel Copper
1 in. 2 sprinklers 1 in. 2 sprinklers
11/4 in. 3 sprinklers 11/4 in. 3 sprinklers
11/2 in. 5 sprinklers 11/2 in. 5 sprinklers
2 in. 10 sprinklers 2 in. 12 sprinklers
21/2 in. 20 sprinklers 21/2 in. 25 sprinklers
3 in. 40 sprinklers 3 in. 45 sprinklers
31/2 in. 65 sprinklers 31/2 in. 75 sprinklers
4 in. 100 sprinklers 4 in. 115 sprinklers
5 in. 160 sprinklers 5 in. 180 sprinklers
6 in. 275 sprinklers 6 in. 300 sprinklers
8 in. See Section 5-2 8 in. See Section 5-2
For SI units, 1 in. = 25.4 mm.
Steel Copper
21/2 in. 15 sprinklers 21/2 in. 20 sprinklers
3 in. 30 sprinklers 3 in. 35 sprinklers
31/2 in. 60 sprinklers 31/2 in. 65 sprinklers
For SI units, 1 in. = 25.4 mm.
Note: For other pipe and tube sizes, see Table 8-
5.3.2(a).
Solution:
Floor area is calculated to be A =471 m2
Number of sprinklers on the floor= 471/15 = 31 sprinklers.
According to Table 3 the following sizes are selected for a steel
piping:
Line A-B: there are 16 sprinklers. The diameter DA-B = 65 mm
Line B-C: there are 12 sprinklers. DB-C = 65 mm
Line C-D: there are 8 sprinklers. DC-D = 50 mm
Line D-E: there are 4 sprinklers. DD-E = 40 mm
Branches: each branch has 4 sprinklers, 2 on each side. Thus,
DB-F =DC-G ==DE-I =25 mm
The riser size supplying the floor; 100 mm
8 Piping network diameters Table 12, p. 59 Tables 13&14, p. 64 Table 15, p.66
9 Flow rate in the riser (l/min) 1890-2830 2650-3780 b
Riser-Hose-Real
Riser-Hose-Real
and
Sprinkler Systems
Sprinkler Systems
08/23/17 BUILT ENVIRONMENT 71
Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems)
Community Water Supply System