REB500 Presentation content
Introduction
Central Unit Architecture & Hardware
Arrangements
Protection functions
Users interface
Event & disturbance recording
Communications interfaces
References
Bay Unit Bay Unit
ABB Switzerland Ltd. - 2
2007-05-01 / Ch. Pinzon
ABB
A Substation ...
empowerment
of a country
ABB
To run a substation bears some risk for...
Industry
sensitive processes require uninterrupted power
Utilities
have to guarantee the delivery of power all the time
have contracts with the industry
ABB
A fault in a substation might cause ...
cascading trips
can be avoided by selective Tripping of a busbar
keep the power loss time short
selective fault isolation prevent extensive outages
ABB
Minimising impacts of black-outs
Example : Black-out in Brazil on March 11, 1999
no busbar- / breaker failure protection installed
CO
VE
The resulting disruptions and losses caused by a busbar fault
EC
no selective tripping
NE
PE NBR Result: cascading trip
BO
SE
PY
CH
S
UR
Tripped main transmission lines 4 x 400 kV
AR
Disruption duration 4h, 20 min.
Energy not served 24500 MWh
Inhabitants left in the dark 100 Mio
Overall loss 10 Mio $
Assumption:
ABB Switzerland Ltd. - 7
Selective tripping would have ensured that half of the power could still be
2007-05-01 / Ch. Pinzon
delivered.
Result:
5 Mio $ Revenue saved in only one day
with a Busbar Protection System ABB
Numerical busbar protection...
ABB
Typical substation layouts
Double busbar
Single busbar T1 Q0
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
1 breaker system
Triple busbar Q1
Q2
Q3
ABB
Q02 Q02 Q02 Q02 Q02
Possible faults in a feeder
Feeder
double busbar 1 Busbar fault Protection Solutions
Busbar protection
2 Fault between breaker and current transformer
Endfault protection
Q1 Q2
3 Line fault / Transformer fault
4 Line protection / Transformer protection
5 Q0
4 Breaker fails to open after trip command
6 Breaker failure protection
T1 T5
5 Breaker opens / closes not 3 pole
Pole discrepancy protection
3
ABB Switzerland Ltd. - 10
Trip re - direction
ABB
Conventional arrangement of protection devices
High cost by
expensive engineering
expensive commissioning
expensive maintenance
space requirement (main-
and backup protection
requires several cabinets )
long copper cabling for the
process to protection devices
cabinets for interposing CTs
ABB Switzerland Ltd. - 11
2007-05-01 / Ch. Pinzon
ABB
Central arrangement of protection devices
Reduction of cost by
less engineering
simpler commissioning
simpler maintenance
less space requirement
simple retrofit (existing
cables can be used)
simple function adaptation
via SW
ABB Switzerland Ltd. - 12
2007-05-01 / Ch. Pinzon
ABB
De - central arrangement of protection devices
Reduction of cost by
less engineering
simpler commissioning
simpler maintenance
low space requirement
simple function adaptation
via SW
ABB Switzerland Ltd. - 13
2007-05-01 / Ch. Pinzon
ABB
Advanced numerical decentralized arrangement
Reduction of cost by
less engineering
simpler commissioning
simpler maintenance
low space requirement
less copper cabling,
since devices are
located near the
process
simple function
adaptation via SW
ABB Switzerland Ltd. - 14
2007-05-01 / Ch. Pinzon
V7.40
07-04-20
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
ABB Switzerland Ltd. - 16
Q0 Q0 Q0 Q0 Q0 Q0
2007-05-01 / Ch. Pinzon
T1 T1 T1 T1 T1
ABB
Definition: numerical busbar protection
100% integrated functionality
100% settings / adjustments via SW
No external auxiliary relays to build logic's
No interposing current transformers necessary (ratio - adjustment via SW)
Decision based on numerical data
Input via A/D - converter & filter => SW - calculations
Two independent protection algorithm based on two different principles
Numerical signal processing
Optical fibres replace mostly copper cable => de-central arrangements
Additional functionality without any further hardware
Changes do not requires any external wiring changes => signal
arrangements via SW
ABB Switzerland Ltd. - 17
2007-05-01 / Ch. Pinzon
system monitoring
2007-05-01 / Ch. Pinzon
fault evaluation
2007-05-01 / Ch. Pinzon
ABB
REB500 Presentation content
Introduction
Central Unit Architecture & Hardware
Arrangements
Protection functions
Users interface
Event & disturbance recording
Communications interfaces
References
Bay Unit Bay Unit 1 1/2 breaker solutions
ABB Switzerland Ltd. - 20
2007-05-01 / Ch. Pinzon
ABB
De-central Protection concept with distributed
REB500 Functionality & HW functionality and intelligence in the bay units
1
2
Bay Protection - Functions
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
phasor &
Fourier Filter
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
Q0 Q0 Q0
T1
Q0 Q0 Q0 Q0 Q0
Central Unit Protection - Functions
T1 T1 T1 T1 T1 T1 T1
Installations: Applications:
1 4 busbars incl. transfer bus solidly grounded networks
1 breaker configuration isolated networks
60 bay units BU03 - 32 protections zones resistive grounded networks
ABB Switzerland Ltd. - 21
Compensated networks
Hardware Options:
2007-05-01 / Ch. Pinzon
bay unit and central unit with optional redundant power supply Fast selective protection of busbars
central unit with optional 2nd I/O board in HV, MV and EHV substations
Abbreviations:
BBP = busbar protection Protection of outdoor, indoor and GIS switchgear
ABB
PD = pole discrepancy protection
BFP = breaker failure protection I0 = neutral current detection
DR = disturbance recorder Com = communication
ER= event recording HMI = human machine interface
EFP = end fault protection
OC = over current protection
REB500 Hardware central unit 03
19 Rack
12 Binary inputs (+12 as option)
9 Binary outputs (+9 as option)
Redundant power supply module
Binary inputs Binary outputs
as option
U
Starcoupler modules
OC
1
1
OC01 2
2
OC02 CR01 3
3 CR02 4
CPU boards
OC03
CR03 5
4
5
OC04 Front HMI with programmable
LEDs
6
6
CR04
7 7
OC05
8
9
OC06
CR05
8
9
Connection facilities for:
OC07
10
10
11
OC08 11
PC (serial or TCP/IP)
12
CR06 12
ABB Switzerland Ltd. - 22
13
13 Remote communication
OC09
2007-05-01 / Ch. Pinzon
14
15
CR07
16
OC11
CR08
16
17
monitoring system as option
OC12
ABB
17
18 CR09 18
500BIO01
REB500 Hardware central unit 03
Starcoupler
Serial Port
GPS
modem
TCP/IP Port
Redundant
Power supply Power supply
ABB Switzerland Ltd. - 23
2007-05-01 / Ch. Pinzon
Communication
Master CPU board
ABB
interface
12 Binary in
Slave CPU board
9 Binary out
REB500 Hardware Bay Unit BU03
Current
Optical Connection
Inputs to Central Unit 1/3 19 Rack I 1
Transformers
1
5
1 2 I1
A OC01
0
2 3
OC02
3 1
Voltage
4 U 5
Transformers 5 I2
5 1
0
OC03 6
6 U1 1
OC04 0 7
7 2
Local HMI Interface 8
5
I3
8 4 0
9
9
OC05 U2
10 Outputs 0 10
1
OC06 5
11 11 5
I0
12 7 0
12
13
OC07
Inputs U3
1
1 C 0
14 B OC10 CR01 2
8
OC08
15 2
OC11 3 10
16 3 4
17 4
OC12 Outputs 0
U4
OC09 CR02 5 11
18 5
6 Power Supply
13
6 +
OC13 1 7 P 1
D -
7 2 CR03 8 U5 2
OC14 0
CR08 14
8 3 9
OC15
9 CR09 10
4 Redundant Power
10 CR04 Supply (option)
CR10 11
11
5
CR05 +
4 CTs 1 or 5 A
OC16 6 12 R 1
12 13 2
- Ratio adjustable
OC17 7
13 CR11 8
CR06
14 via SW
ABB Switzerland Ltd. - 24
OC18
14 CR12 9
CR07 15 &
5 VTs
2007-05-01 / Ch. Pinzon
15
16
CR13 10 Power supply
OC19
11 Ratio adjustable
17
18
OC20 12 via SW
CR14 13
&
CR15
ABB
14
CR16 15
Red. Power Supply
20 Binary Inputs
48 250 VDC 16 Binary Outputs
Adjustable via SW
REB500sys Local HMI03 with 20 programmable LEDs
At the central unit and bay unit,
the local HMI allows a quick reading of
Alarms
CU03 Events
BU03
LHMI03 Settings / Adjustments
Measurements
ABB
REB500 bay unit 03
ABB
REB500 Presentation content
Introduction
Central Unit Architecture & Hardware
Arrangements
Protection functions
Users interface
Event & disturbance recording
Communications interfaces
References
Bay Unit Bay Unit 1 1/2 breaker solutions
ABB Switzerland Ltd. - 27
2007-05-01 / Ch. Pinzon
ABB
REB500 De-central / central arrangement
Central unit
Bay unit
ABB Switzerland Ltd. - 28
2007-05-01 / Ch. Pinzon
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1 T2 GIS
Q0
Q0 Q0 Q0 Q0
or
T1 T1 T1 T1
AIS
T2 T5 T2 T2 T5 T2
Marshalling
cabinets
M1 M1 M1 M1
M2 M2 BBP M2 M2
ABB Switzerland Ltd. - 29
BFP
2007-05-01 / Ch. Pinzon
ABB
TCS TCS TCS TCS TCS
Images
Currents
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1 T2 GIS
Q0
Q0 Q0 Q0 Q0
or
T1 T1 T1 T1
AIS
T2 T5 T2 T2 T5 T2
Marshalling
cabinets
M1 M1 M1 M1
M2 M2 BBP M2 M2
ABB Switzerland Ltd. - 30
BFP
2007-05-01 / Ch. Pinzon
ABB
TCS TCS TCS TCS TCS
Images
Currents
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1 T2 GIS
Q0
Q0 Q0 Q0 Q0
or
T1 T1 T1 T1
AIS
T2 T5 T2 T2 T5 T2
M1 M1 M1 M1
M2 M2 M2 M2
BBP
BFP
Aux Aux Aux Aux
ABB
REB500 fibre optical cable
Up to 1200 Meter
<= 5dB
Rx TX
TX Rx
ABB
Process connection to / from REB500
Feeder
double busbar
Q1 Q2
Q0
ABB Switzerland Ltd. - 34
2007-05-01 / Ch. Pinzon
T1 T5 VT Trip Signalization
CT Image of Aux.
terminals terminals terminals terminals Isolators, terminals
for start breaker
REB500sys failure
ABB
and/or DR
New possibilities with numerical decentral busbar protection
Standard
Option
REB500 Main functionality
Busbar protection (87B) X Functionality as in
Isolator supervision X conventional
Differential current supervision X busbar protection
Comprehensive self-supervision X
Software Matrix for Inputs / Outputs / Trip matrix X
Time synchronization X
Event recording up to 1000 events X
Additional Functionality
Disturbance recorder (4 x I, 5x U ) 1.5 sec; (U if VT avail.) X
Dynamic Busbar replica with display of currents X
as Standard in REB500
Testgenerator X
Remote-HMI X
Trip command re-direction X
Measurement of neutral current / neutral current detection I0 (87B) X
Breaker failure protection (51BF) X
End-fault protection (51) X
Breaker pole discrepancy (51) X
ABB Switzerland Ltd. - 36
ABB
Overfluxing definite / inverse time (24)
Frequency (81)
Rate-of-change of frequency df/dt (81)
Test Sequenzer
REB500 Busbar protection - algorithms
Current data and pre-processing in the bay unit
DSP
A/I Max DIG
S/H MUX A/D
I2 Signal-
prolongation
at
Fourier filtering: CT saturation
Only 50, resp. 60Hz
component will be
ABB Switzerland Ltd. - 38
evaluated, no DC, no 0 t
2007-05-01 / Ch. Pinzon
0 k = stabilizing factor
N
0 Restrained current
IHalt = I Ln
n=1
ABB
REB500 Busbar protection - algorithms
2) Current direction comparison (phase comparison)
case 1: external fault =139
Im
12 =139
I1 I2 I2
2
1 I1 Re
Phase difference
Im
180 Re
External I1
fault
I2 12 =40
ABB Switzerland Ltd. - 40
74 min = 74
2007-05-01 / Ch. Pinzon
p
Tri
Current
different principles
IKmin
Restrained
(through fault) 1) Stabilized differential Current
0 (percentage differential current)
0 Restrained Current
IL1 &
& Phase segregated incl. I0
& Decision:
Phase difference
IL2 &
IL3 selective per protection
zone Trip Busbar
180
External
fault
ABB Switzerland Ltd. - 41
74
I1 2 I2 (phase comparison)
Internal
0
case 1 2 fault
1
ABB
ABB Switzerland Ltd. - 42
2007-05-01 / Ch. Pinzon
ABB
Checkzone was required in
High Impedance BBP, where CTs
No Check zone in REB500 required were switched via aux. contacts
I diff
T1 Q0 T1
Check zone
I diff
Q0
I direction
T1 T1
k - factor
1 CTs
2007-05-01 / Ch. Pinzon
Q0 Q0 Q0 Q0 Q0 Q0 Maximum security
T1 T1 T1 T1 T1 T1
ABB
but available in REB500
REB500 Neutral current measurement (protection)
independent settings
ABB Switzerland Ltd. - 49
2007-05-01 / Ch. Pinzon
ABB
REB500 Breaker failure protection - function
120 ms Trip Busbar 1
X Busbar 1 Timer t1 via inter - tripping
L1 I>
CB A >I
t 100 ms after line protection trip
& TRIP BFP L1
Circuit breaker CB A
L2
>I
t
& TRIP BFP L2
L3
>I
t
& TRIP BFP L3
+
L3 TRIP
BFP t1
t
Line protection trip Remote Trip
ABB Switzerland Ltd. - 50
2007-05-01 / Ch. Pinzon
ABB
REB500 Breaker failure protection - Benefits
Benefits of integrated breaker failure protection:
Feeder
double busbar 50% less external wiring
DC supply
CT connections
Isolator images
Tripping circuits
Q1 Q2 Internal start BFP
No external logics to be build up
Less space requirements
Q0 Common use image of isolators (topology via Central
Unit; selectivity warranted)
T1 T5 Integrated intertripping scheme, which is supervised
Common trip channels
Less Engineering
Simpler Commissioning & Maintenance (common for
ABB Switzerland Ltd. - 52
2007-05-01 / Ch. Pinzon
Q1 Q2 Q1 Q2
T1 36 ms
Q0 open t
t
Q0 &
Q0 T1 L1
>I
L2
>I 1
L3
ABB Switzerland Ltd. - 53
>I
2007-05-01 / Ch. Pinzon
Inter tripping
(here busbar 2) TRIP
Remote trip after
t + 36 ms
ABB
REB500 End fault protection - settings
function is activated by
CB open + Pick - up time
tripping time =
Pick - up time +36 ms
ABB Switzerland Ltd. - 54
2007-05-01 / Ch. Pinzon
ABB
REB500 Overcurrent protection - function & setting
Feeder
1
2
Q1 Q2
Q0 I>
L1
T1 >I
L2 t
>I 1 Trip CB
ABB Switzerland Ltd. - 55
2007-05-01 / Ch. Pinzon
L3
>I
Definite time
Undervoltage-
relay
Central unit
Q1 Q2 or external release Q1 Q2
<U
>I TRIP CB
2007-05-01 / Ch. Pinzon
Voltage release
BU &
from CU
ABB
<U
BU
REB500 Voltage - Check setting
Over or under -
Voltage Release
ABB Switzerland Ltd. - 58
2007-05-01 / Ch. Pinzon
ABB
REB500 overcurrent release & trip matrix - setting
Overcurrent - Release
Trip - Matrix
ABB Switzerland Ltd. - 59
2007-05-01 / Ch. Pinzon
ABB
REB500 Trip command re-direction (without BFP)
Underpressure situation in the CB (SF6 gas pressure is to low): CB OPEN coil is blocked
=> it sends a signal Low gas pressure
=> direct inter tripping of the allocated busbar and remote trip in fault situation
trip redirection
X
L1
>I
&
OC release
L2
>I >= 1
L3
>I
TRIP BB (BFP t2) &
&
Remote Trip
LP Tripping- contact
+ External Trip
>= 1
ABB Switzerland Ltd. - 60
any REB500
2007-05-01 / Ch. Pinzon
internal trip
ABB
REB500 Trip command re-direction ( in combination with BFP )
Underpressure situation in the CB (SF6 gas pressure is to low): CB OPEN coil is blocked
=> it sends a signal Low gas pressure
=> direct inter tripping of the allocated busbar and remote trip in fault situation
Timer 1 & 2
trip redirection =>
10 ms
X
L1
>I
t
& TRIP BFP L1
10 ms
L2
>I
t
& TRIP BFP L2
10 ms
L3
>I
t
& TRIP BFP L3
10 ms
Starting (tripping-) contacts
1 Timer t2
+
L1
ABB Switzerland Ltd. - 61
2007-05-01 / Ch. Pinzon
t
+ TRIP BB (BFP t2)
L2
10 ms
Remote Trip
+
ABB
L3
TRIP BFP t1
REB500 Blocking - Isolator Alarm
Isolator supervision
+
Optocoupler input
Q1 off
A1
OC01
Q1
Feeder
Q1 on
A2
- OC02
1 L1 L2 L3 A3
A4
ABB
REB500 Blocking - Differential Current Alarm
Differential current supervision
G
N CT Module
1
D I 1
5
2 IL1
Feeder 0
3
1
4
5
1 5 IL2
6 0
2 7 1
5
8 IL3
9 0
1
10
Q1 Q2 11 5 IL0
L1 L2 L3 12 0
Q0
Differential Current Alarm
T1
ABB Switzerland Ltd. - 64
Remain in operation
Selective block of tripping
System wide block of tripping ABB
ABB Switzerland Ltd. - 65
2007-05-01 / Ch. Pinzon
ABB
REB500 Fault on a busbar
Double busbar
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
ABB Switzerland Ltd. - 66
2007-05-01 / Ch. Pinzon
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
ABB
REB500 Current Plausibility Check
Double busbar
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
ABB Switzerland Ltd. - 67
This virtual current could result in a differential current and initiate a BBP trip
ABB
REB500 will block under this condition due to Current Plausibility Check
REB500 Inter tripping - Selective tripping
Double busbar
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
ABB Switzerland Ltd. - 68
2007-05-01 / Ch. Pinzon
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
ABB
REB500 Presentation content
Introduction
Central Unit Architecture & Hardware
Arrangements
Protection functions
Users interface
Event & disturbance recording
Communications interfaces
References
Bay Unit Bay Unit 1 1/2 breaker solutions
ABB Switzerland Ltd. - 70
2007-05-01 / Ch. Pinzon
ABB
HMI500 SW Configuration Tool & Users Interface
Operates under MS-Windows (98, NT4.0, 2000, XP)
32 bit technology
Program handling as in common windows
applications
Parameterization off-line (in the office)
Cyclic updates of events & disturbance record files
Cyclic up-load of display of measurement values
Online Test - Generator for commissioning /
maintenance
Functionality is visualized (Dynamic busbar replica,
trip characteristic, parameterization,In- / Output
configuration, ...)
Up-load and download of parameter on REB500
Simulation - Mode for training
Supporting different languages
ABB Switzerland Ltd. - 71
2007-05-01 / Ch. Pinzon
Start
selected
Offline Starting setfile
Check
status
Online
HMI500 Start
ABB Switzerland Ltd. - 72
2007-05-01 / Ch. Pinzon
Start Tool
ABB
with respective
Setfile
HMI500 Users HMI
ABB
REB500 Logic & Delay / integrator as Standard in BU03 V7.00
Delay
For delaying pick-up or reset or for
integrating 1 binary signal
Provision for inverting the input
ABB
ABB Switzerland Ltd. - 75
2007-05-01 / Ch. Pinzon
ABB
HMI500 Signal engineering & adjustments
Signal Filter per function
ABB
HMI500 extension
Active (existing)
Pre-engineered (future)
Feeder / Coupler
Feeder
ABB Switzerland Ltd. - 77
2007-05-01 / Ch. Pinzon
ABB
users interface
HMI500 Online Help function
F1
Online help function
provides required
information during
usage of HMI500
program
ABB Switzerland Ltd. - 78
2007-05-01 / Ch. Pinzon
ABB
HMI500 database / setfile compare function
ABB
REB500 Flexibility
Q0
T1
ABB Switzerland Ltd. - 80
2007-05-01 / Ch. Pinzon
ABB
REB500 HMI500 / Documentation
REB500 Documentation
of substation data /
settings & I/O
configuration
as Print
as print pre-view
generate PDF
generate HTML
ABB Switzerland Ltd. - 81
2007-05-01 / Ch. Pinzon
ABB
REB500 Presentation content
Introduction
Central Unit Architecture & Hardware
Arrangements
Protection functions
Users interface
Event & disturbance recording
Communications interfaces
References
Bay Unit Bay Unit 1 1/2 breaker solutions
ABB Switzerland Ltd. - 82
2007-05-01 / Ch. Pinzon
ABB
REB500 Event recording
Event memory
Central unit
Central unit: 1000
Event memory
Bay unit: 100
Resolution 1 ms
central unit or bay unit
ABB
REB500 Disturbance recorder DR
SA Systems like SAS5xx or SMS530
Local connection at
central unit or bay unit
frequency) available
802 Hz (16,7Hz) 401 Hz (16,7Hz)
2007-05-01 / Ch. Pinzon
ABB
10 sec 20 sec 40 sec Option 4I 5U
cyclic Up-Load
binary signal - recording
REB500 Disturbance recorder - settings
DR Settings
DR upload
ABB Switzerland Ltd. - 85
2007-05-01 / Ch. Pinzon
DR cyclic upload
ABB
ABB Switzerland Ltd. - 86
2007-05-01 / Ch. Pinzon
ABB
REB500 Disturbance recorder DR => PSM integration
Start Wineve out of HMI500 automatically after DR upload
The available disturbance recorders in REB500 allows a simple and
quick fault analysis
One mouse-click
away
ABB Switzerland Ltd. - 87
2007-05-01 / Ch. Pinzon
ABB
REB500 Dynamic busbar replica
Central unit
Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0
T1 T1
Small
Substation monitoring system
ABB Switzerland Ltd. - 88
with HMI500
2007-05-01 / Ch. Pinzon
dynamic
busbar replica Local connection at
central unit or bay unit
feeder currents
differential currents / zone
ABB
REB500 with embedded web server
Easy Monitoring on
station computer via
Internet Explorer over
LAN in the substation
Easy: no entering with
password, just IP-
Address
Analogue values
Dynamic busbar replica /
single line diagram
Eventlist: no deletion of
events in the target =>
Event can are still stored
and can be retrieved with
ABB Switzerland Ltd. - 89
HMI500
2007-05-01 / Ch. Pinzon
Cyclic update
Baden V7.30
ABB
REB500 Test generator
The test generator provides plenty of
useful functions
Analogue Input Measurements
Status & and forcing of (I/Os)
Switchgear object (refer also to
dynamic busbar replica)
Blocking / Reset
Analogue Input Measurements
Password protection
ABB Switzerland Ltd. - 90
I/Os forced
ABB
REB500 Revision & Maintenance
ABB
REB500 Presentation content
Introduction
Central Unit Architecture & Hardware
Arrangements
Protection functions
Users interface
Event & disturbance recording
Communications interfaces
References
Bay Unit Bay Unit 1 1/2 breaker solutions
ABB Switzerland Ltd. - 92
2007-05-01 / Ch. Pinzon
ABB
Central unit
REB500 Time synchronization
1- 2 / Accuracy of
time periodic Telegram The time synchronization of REB500 is
10 ms IEC-103 - Bus GPS
1ms IEC61850 & possible via:
LON - Bus
1 - Radio or satellite clock
2 - Interbay bus (IEC61850-8-1 / LON /
IEC60870-5-103)
Starcoupler 3 - Minute or Second pulse (periodic pulse
onto an optocoupler)
4 - PC via HMI500
RS 232
Min/Sec
pulse 3 - Accuracy
10 ms (min)
Central unit
ABB Switzerland Ltd. - 93
+
2007-05-01 / Ch. Pinzon
ABB
4 - Accuracy
approx. 1min / month
REB500 Communication interface
Ethernet - (TCP/IP)
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0
HMI500
Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1 via TCP/IP Substation
Automation or
Monitoring Systems
e.g.: SAS5xx or SMS530
1
2
Q1 Q2
Q0
Q1
Q0
Q2 Q1
Q0
Q2
T1
Q0
Q1
Q0
Q2 Q1
Q0
Q2 Q1
Q0
Q2 Q1
Q0
Q2
IEC61850-8-1 HMI500
via LON
T1 T1 T1 T1 T1 T1 T1
Remote - HMI
2007-05-01 / Ch. Pinzon
1
2
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
T1
Q0 Q0 Q0 Q0 Q0 Q0 Q0 Q0
T1 T1 T1 T1 T1 T1 T1
Modem Modem
Local front connection at
central unit or bay unit
ABB
REB500 IEC 61850-8-1
UCA Certificate
ABB Switzerland Ltd. - 95
2007-05-01 / Ch. Pinzon
ABB
REB500 IEC61850-8-1 Ethernet / TCP/IP connection
Substation
Automation or
Monitoring Systems
SCD File
export out of HMI500
for easy import into engineer tools
Disturbance records
Diff current
IEC 61850-8-1
electrical
ABB Switzerland Ltd. - 96
ABB
ABB Switzerland Ltd. - 97
2007-05-01 / Ch. Pinzon
ABB
REB500 Performance
ABB
REB500 Spare parts
Central unit
each of the used plug-in units
1 x 500CPU05 (processor module)
1 x 500PSM03 (power supply module)
1 x 500SCM01 (starcoupler module)
1 x 500BIO01 (input / output module)
1 x 500CIM06 (communication module)
1 x 500OCC02 (front connection cable for PC)
Bay units:
Node- and Device ID - configuration
(addressing) via Front HMI
ABB Switzerland Ltd. - 100
2007-05-01 / Ch. Pinzon
ABB
REB500 Presentation content
Introduction
Central Unit Architecture & Hardware
Arrangements
Protection functions
Users interface
Event & disturbance recording
Communications interfaces
References
Bay Unit Bay Unit 1 1/2 breaker solutions
ABB Switzerland Ltd. - 101
2007-05-01 / Ch. Pinzon
ABB
REB500 Reference of operation experience
Stability
Zell am Ziller 220kV / Austria in Nov. 1995
ext. Fault in Transformer approx. 6kA
Laufenburg / Switzerland in Dez. 95
ext. Fault of 7kA R/S/Ground for 450ms
ABB Switzerland Ltd. - 102
2007-05-01 / Ch. Pinzon
ABB
REB500 Reference of operation experience
Successful selective BBP - trip
Zell am Ziller 380 kV / Austria
Trip in 26ms at 1.8 x In, single pole - ground GIS
Feb. 1997
Zell am Ziller 380 kV / Austria /
Trip Nov 1999
Ayer Rajah 400kV / Singapore
Trip in 29ms at 2 x In / June1998
AL ERAAD 33KV MOBILE / UAE
Trip Dec 2000
RWE / BASF W210 220kV / Germany
Trip Sept. 2001
Bosques 220kV / Argentina
Trip Oct 2001: explosion of a CB breaker
Hamma 220kV / Algeria
Trip Dec. 2001: 8 kA single pole
Wadi Houf 220kV / Egypt
Trip June 2002: 3 kA single pole
ABB Switzerland Ltd. - 103
ABB
REB500 Reference of operation experience
ABB
Successful REB500 Trip in AIS Lskovec 220kV in CZ
1 Coupler
The total clearance time was 50ms
2007-05-01 / Ch. Pinzon
ABB
Successful REB500 Trip in AIS Lskovec 220kV in CZ
On 6 December 2003, 10:18h the REB500
successfully and selectively tripped a phase to
ground fault at Liskovec 220kV substation.
During storm a station grounding wire was
broken and its one end fell down and hit busbar
W21 disconnector. in the measuring VT field and
caused phase L1 to ground fault. The REB 500
detected the busbar fault on W21 and selectively
tripped the entire busbar.
After a while the second part of the broken
grounding wire swung and hit an interconnection
bar between VT and disconnector at busbar
W11. The REB 500 detected and tripped
consecutive L1 to ground fault on W11.
The total clearance time for the first fault was
approx 50 ms (REB500 tripping time + circuit
ABB Switzerland Ltd. - 106
fault.
Detail of the
ABB
disconnector after
fault clearance
Successful REB500 Trip in GIS S/S Hamma 220kV in Algeria
8.13 kA Fault
1 Coupler
The total clearance time was 55ms
2007-05-01 / Ch. Pinzon
ABB
Successful REB500 Trip in GIS S/S Hamma 220kV in Algeria
ABB Switzerland Ltd. - 108
2007-05-01 / Ch. Pinzon
ABB
Selective REB500 Trip in GIS Wadi Houf 220kV in Egypt
3.4 kA Fault
ABB
(REB500 Tripping time + Circuit breaker opening
time)
Successful REB500 Trip in GIS Wadi Houf 220kV in Egypt
Phase Ground Fault
Fault current: 3.4kA
Peak Current: 5.8kA
REB500 internal
disturbance record
ABB Switzerland Ltd. - 110
evaluated
with E_wineve
2007-05-01 / Ch. Pinzon
ABB
Display of phasors components Wadi Houf 220kV with PSM
ABB
Display of impedance Wadi Houf 220kV with PSM
ABB
Display of Symmetric components Wadi Houf 220kV with PSM
ABB
The POWER of REB500
Brwalde
Graustein
ABB
The POWER of REB500
66kV substation in
=>1
Singapore
=>3
4 Sectionalizer
=>2
resistive grounded
=>4
=>3 36 x bay units
BBP incl. I0
ABB Switzerland Ltd. - 115
2007-05-01 / Ch. Pinzon
=>4
BFR
31 x CB
ABB
REB500 numerical substation protection summary
Benefits of numerical technique and communication within substation protection
Improved functionality (optional functions On-line alarms and On-line event list
per bay) Ethernet connection (TCP/IP)
Less space required (NO auxiliary relays Connection to SCS/SMS (fault analysis)
for isolator image)
Disturbance record transfer
Easily extendible (activating pre-
engineered feeders) Data archiving (disturbance/events)
ABB
In 77 Countries > 1300 REB500 sold
Installed REB500 approx. 1150 installed and in service
(Mar 2007)
ABB Switzerland Ltd. - 117
2007-05-01 / Ch. Pinzon
ABB
REB500 is more than 26 Mio h in service = more than 3000 years proven experience
REB500 & IEC61850 References
REB500 is the first numerical
decentral busbar protection with
IEC61850-8-1 (since Aug 2005)
Proven interoperability (refer to left)
References:
NEK Bulgaria Dobrudja
BKW Switzerland
Atel Switzerland
Power Grid India
Italy Terna
Saudi Arabia
ABB Switzerland Ltd. - 118
2007-05-01 / Ch. Pinzon
ABB
REB500 IEC61850-8-1
Using for
Disturbance transfer
Monitoring
SCD / ICD Export
UCA Certificate
REB500
REB500sys
ABB Switzerland Ltd. - 119
2007-05-01 / Ch. Pinzon
ABB
REB500 / REB500sys on the internet
http://www.abb.com/substationautomation
REB500 / REB500sys
ABB Switzerland Ltd. - 120
2007-05-01 / Ch. Pinzon
ABB