Protection Application Protection in Breaker

Handbook and Half


Configuration
ABB Group - 1 -
Sep 16, 2017
Protection in breaker and half system
ABB Group - 2 -
Sep 16, 2017
Protection in breaker and half system
Some comments on CT locations
according to alternative 1
Fault at F1 will be cleared instantaneously
Fault at F2 will be cleared through LBB
For fault in overlapped zone both circuits get
disconected
In parallel connected CTs there could be
dissimilar performance resulting in out of
balance current
Autoreclosing takes place for faults in parallel
connected CTs
ABB Group - 3 -
Sep 16, 2017
Protection in breaker and half system

Problem of matching
parallel connected
CTs is not existant
Separate stub
protection can be
connected
Ratio of CT can be
selected to match
rating of circuit
ABB Group - 4 -
Sep 16, 2017
Protection in breaker and half system
ABB Group - 5 -
Sep 16, 2017
Protection in breaker and half system
Protection equipment associated with one and a half CB
system
ABB Group - 6 -
Sep 16, 2017
Protection in breaker and half system
Block diagram of trip and reclosing cooperation in breaker
and half system for a line transformer diameter
ABB Group - 7 -
Sep 16, 2017
Protection in breaker and half system

Autoreclosure

Protections that start Autoreclosure


Main1 Protection
Main 2 Protection
Protections that block Autoreclosure
Breaker fail relay
Line reactor protection
Over voltage protection
Direct transfer trip receive
Bus bar protection
Zone 2&3 of distance protection
Carrier fail condition
ABB Group - 8 -

CB problems
Sep 16, 2017

Directional earth fault protection (IDMT)


Protection in breaker and half system
ABB Group - 9 -
Sep 16, 2017
Protection in breaker and half system

Priority Unit

Priority unit allows closing of one breaker first


and upon successful reclosing of this breaker
the second breaker is allowed to close
This reduces wear and tear of breaker when
they are to reclose on persistent faults
ABB Group - 10 -
Sep 16, 2017
Protection in breaker and half system

Auto reclosure circuits

If DC supply to the group in which reclosing


relay is connected fails in the event of asingle
phase fault only the protection in the other
group operates and gives single phase trip
signal to breakers but there will be no
autoreclosing
To avoid this DC fail relay of auto reclose DC
circuit converts single phase trip impulse of
line protection in the other group to three
phase trip
ABB Group - 11 -
Sep 16, 2017
Protection in breaker and half system
ABB Group - 12 -
Sep 16, 2017
Protection in breaker and half system
ABB Group - 13 -
Sep 16, 2017
Protection in breaker and half system
Direct trip to remote end breaker is sent
under the following conditions
Manual trip or automatic trip of main breaker
when the tie breaker is open
Manual trip or automatic trip of tie breaker
when main breaker is open
Breaker fail relay of main breaker operated
Breaker fail relay of tie breaker operated
Three phase unit A or B operated
Bus bar protection operated (If tie CB Open)
ABB Group - 14 -
Sep 16, 2017
Protection in breaker and half system
Trip logic Line protection
ABB Group - 15 -
Sep 16, 2017
Protection in breaker and half system

Line and Reactor Protection Cubicles

Group A and Group B protections are


connected to separate DC source and are in
separate cubicles
CT and PT connections are from independent
cores
Over voltage protection is duplicated
Direct trip channels are separate for group A
and B
ABB Group - 16 -
Sep 16, 2017
Protection in breaker and half system

Line and Reactor Protection Cubicles

Reactor protections are grouped as under


Group -A Group -B
Reactor dif relay Buchholz trip
Back up relay Restricted E/F relay
Oil temp trip Winding temp trip
Pressure relief trip Oil level high/low trip
Fire Protection trip
ABB Group - 17 -
Sep 16, 2017
Protection in breaker and half system
Trip logic Transformer protection
ABB Group - 18 -
Sep 16, 2017
Protection in breaker and half system

Transformer Protection Cubicles


These are not duplicated but grouped as under

Group -A Group -B
Biased diff relay High imp diff relay
Back-Up relay (HV) Buchholz trip
Over fluxing relay Restricted E/F relay
Oil temp trip Back-Up relay (LV)
Pressure relief trip Overload relay
Delta wdg protection Wdg temp trip
OLTC trip
Oil level high/low
Neutral e/f relay
ABB Group - 19 -
Sep 16, 2017
Protection in breaker and half system
Trip logic Line CB
ABB Group - 20 -
Sep 16, 2017
Protection in breaker and half system
Trip logic Tie CB
ABB Group - 21 -
Sep 16, 2017
Protection in breaker and half system
Trip logic Transformer CB
ABB Group - 22 -
Sep 16, 2017
Protection in breaker and half system

Breaker Relay Panels

Trip Unit A trips TC-1 and Trip Unit B Trips


TC-2 and these are housed in different
cubicles
Auto reclose relay is in Group A
Breaker fail relay is in Group B
If tripping of both TC1 and TC2 is arranged
from these trip units , both group A and Group
B breaker relays can be housed in one
cubicle
ABB Group - 23 -
Sep 16, 2017
Protection in breaker and half system
Protection cubicles for line transformer diameter
ABB Group - 24 -
Sep 16, 2017
Protection in breaker and half system
Protection cubicles for line transformer diameter
ABB Group - 25 -
Sep 16, 2017
Protection in breaker and half system
Bus bar protection
ABB Group - 26 -
Sep 16, 2017
Protection in breaker and half system
ABB Group - 27 -
Sep 16, 2017