This system is available for,

All Gas Turbine Compartments


Gas Turbine Generator
Steam Turbine Generator

This system is very effective for


quenching the fire at shortest
possible time.
Atmospheric air contains,
21 % ----- Oxygen
78 % ----- Nitrogen
1% ----- Others
CO2 extinguishes the fire by reducing

oxygen content in the air in the

compartment from 21% to less than

15% (i.e.,) In sufficient concentration to

support combustion.
Initially a quantity of CO2 equal to or
greater than 34% of the compartment
volume is discharged in the compartment
in ONE MINUTE (Initial Discharge) and
then a prolonged slow discharge for 40
minutes (Extended Discharge) to
minimise the likelihood of Reflash
condition.
Gas Turbine Compartment (Zone-1)
Gas Turbine Bearing-2 Area (Tunnel)
(Zone-1A)
GT Generator Compartment (Zone -2)
GT Accessory module Compartment
(Zone -4)
Steam Turbine Generator.
No of Heat detectors used :
Turbine Compartment : 6 nos.
Exhaust Compartment : 4 nos.
Load Gear Compartment : 4 nos.

Heat Pickup Temperature : 315 oC


(At least 2 detectors should sense fire
for activation of CO2 System )
Initial Discharge: 14 Nos. X 45 Kg CO2
cylinders.
Extended Discharge: 25 Nos. X 45 Kg CO2
cylinders.
No of Heat detectors used : 4 nos.
Pickup Temperature : 510 oC
(Atleast 2 detectors should sense fire for
activation of CO2 System)
Initial Discharge: 01 No. X 45 Kg CO2
Cylinders.
Extended Discharge: 02 Nos. X 45 Kg CO2
Cylinders.
No of Heat detectors used :
6 Nos. for 80 oC (Alarm) and
6 Nos. for 100 oC (Trip)
Atleast 2 detectors should sense fire for
activation of CO2 System
Main Discharge: 04 Nos. X 45 Kg CO2
cylinders.
Standby Discharge: 04 Nos. X 45 Kg CO2
cylinders.
No of Heat detectors used :
Gas Compartment: 4 Nos.
Lube Oil Compartment: 4 Nos.

Pickup Temperature : 315 oC


(Atleast 2 detectors should sense fire for
activation of CO2 System)
Initial Discharge : 02 Nos. X 45 Kg CO2
cylinders.
Extended Discharge: 05 Nos. X 45 Kg CO2
cylinders.
No of Heat sensors used : 10 Nos.

CO2 Cylinders : 2 x 5 Nos.

Emergency push button: 3 Nos EPB

Hooter: 1 No.
Fire detected by 2 heat detectors in one
compartment at different locations....?

Fire Alarm sent to MARK-V in CCR and Gas


Turbine Will Trip...

Fire Audible Alarm initiated in CCR CO2


control panel and local also...
All the Ventilation fans and cooling fans in
GT (88BT,88TK,88BX,88VG,88BL and
88VL)stops immediately..

After 10 Secs, CO2 pilot cylinder solenoid


valve gets energised for the compartment
where FIRE sensed...

CO2 released from the Initial Discharge


cylinders rapidly(1 Minute)...
Fire dampers of the fans in that particular
compartment gets closed by CO2
released.

Extended Discharge cylinders will be


actuated by initial discharge manifold
pressure.

CO2 released from the extended discharge


cylinders gradually for 40 minutes to avoid
reflashing inside the compartment.
Come Out from the compartment and
close the doors. All doors should be in
closed condition.

Break the Local EPB glass and depress the


Pushbutton.

Inform to Control Room and Fire Station


Immediately.
Wait and see the CO2 discharge into the
compartment through glass from Outside.

Never let anybody to go inside the


compartment.

Confirm the CO2 cylinders discharge


locally by checking pilot and slave
cylinders by discharge noise and
coolingness.
Remove the PIN in the Manual/Pneumatic
actuator and pull down the lever in the
Pilot cylinder of the particular
Compartment..

Confirm the CO2 cylinders discharge


locally by checking pilot and slave
cylinders by discharge noise and
coolingness.
This system is very
sophisticated and reliable.

Very easy to Operate . Hence


in case of FIRE, Always take
full sincere efforts to
extinguish the Fire and save
lives and equipment.
Maintenance Schedule:
The CO2 cylinders has to be refilled when the
weight reduces to 10 % or 5 years of operation
which ever is less.

The Hydrostatic test of CO2 cylinders has to be


carried out after 10 years of service to check the
cylinders for any damage, crack etc.

Lubrication of Co2 dampers to be done periodically.

Healthiness of heat detectors and solenoid valves


to be checked periodically.
Thank you to All..!