You are on page 1of 30

Introduction to IEC 61439:

A new standard on
Switchgear & Controlgear
Assemblies
An effort
by
Virendra Sahdev
Introduction
IEC 60439, the standard for low-voltage switchgear and controlgear assemblies,
was under restructuring from the last decade. The new series of IEC 61439
standards were published in January 2009. This standard has brought
considerable clarity in technical interpretation.
The new standard follows the philosophy of IEC 60947 series i.e. IEC
61439-1 is General Rules standard to be referred to by subsidiary product parts
of IEC 61439 series. The IEC 60439 standards were ambiguous about how to assess
compliance of partially type tested assemblies. As a result manufacturers and
testing bodies often treated partially type-tested assemblies differently. One
of the main features of IEC 61439-1 is that the discrimination between Type
Tested Assemblies (TTA) and Partially Type Tested Assemblies (PTTA) has been
eliminated by the verification approach.
The three different but equivalent types of verification methods are introduced
and these are;
a) Verification by Testing.
b) Verification by Calculation/ Measurement.
c) Verification by Design rules.
The requirements regarding short circuit performance, temperature rise, dielectric
properties and rated diversity factor have been covered in more detail.
IEC 60439 vs IEC 61439
Introduction
The new series of IEC 61439 standards were published in January 2009.
The new standard follows the philosophy of IEC 60947 series i.e. IEC 61439-1 is
General Rules standard to be referred to by subsidiary product parts
of IEC 61439 series. (Refer Table 1 below)
Introduction
One of the main features of IEC 61439-1 is that the discrimination between
Type Tested Assemblies (TTA) and Partially Type Tested Assemblies (PTTA) has
been eliminated by the verification approach.
The three different but equivalent types of verification methods are introduced
and these are;
a) Verification by Testing.
b) Verification by Calculation/ Measurement.
c) Verification by Design rules.
The requirements regarding short circuit performance, temperature rise,
dielectric properties and rated diversity factor have been covered in more detail.
Verification Requirements

Verification Requirements
Verification Requirements
Examples of the limitations and margins applied to
verification without type test include:
All assemblies connected to a supply with a prospective short circuit
current in excess of 10kA rms or having a cut-off current of 17kA peak must
be of a type-tested design or the verification must be an interpolation from a
reference design. Under no circumstances can the assigned short circuit
current rating be higher than that of the reference design.
So as to take account of the air temperature within the enclosure, thermal
interactions and possible hot spots; components within a circuit that has not
been temperature rise tested, must be de-rated to 80% of their free air
current rating.
Comparison of the power loss of the components within an assembly with
the known heat dissipation capability of an enclosure, is restricted to
assemblies having a rating of 630A.
Confirmation of temperature rise performance by calculation is limited to
assemblies with a rating not exceeding 1600A. Test or interpolation from a
tested design must be used to verify higher ratings.
Salient features of IEC 61439
Verification of temperature rise
For multiple compartment assembly, verification by calculation can be done up to
rated current of 1600 A only.
Assemblies, verified by design rule from a similar tested assembly, should comply
with the following:
oFunctional units shall belong to the same group as functional unit selected
for test.
oSame type of construction.
oSame or increased overall dimensions.
oSame or reduced internal separation.
oSame or reduced power losses in the same section of assembly.
oSame or reduced number of outgoing circuit for every section.
Rated diversity factor (RDF) is elaborated in more details with incoming and
outgoing circuit diagrams.
The average ambient temperature for the duration of test shall not exceed 35 oC.
Salient features of IEC 61439
Rated divers1ty factor (RDF):
The rated diversity factor is the per unit value of the rated current, assigned by the
assembly manufacturer, to which outgoing circuits of an assembly can be
continuously and simultaneously loaded taking into account the mutual thermal
influences.
Rated diversity factor can be stated:
for groups of circuits;
for the whole assembly.
The rated diversity factor multiplied by the rated current of the circuits shall be
equal to or higher than the assumed loading of the outgoing circuits. The assumed
loading of outgoing circuits shall be addressed by the relevant assembly standard,
The rated diversity factor is applicable with the ASSEMBLY operating at rated
current (lnA)
Salient features of IEC 61439
Short circuit withstand test
Following requirements are greater than or equal to reference design:
oCross-sectional dimensions of the busbars and connections
o Spacing of the busbars and connections
o SCPDs are equivalent, i.e. of the same make with the same or better I2t based on
the device manufacturers data
Following requirements are less than or equal to reference design:
oShort circuit rating of each circuit
o Busbar supports spacing
o Length of unprotected live conductors of each nonprotected circuit
Following requirements are same as that of reference design
o Conductor material and its properties
o Enclosure design, type and dimensions
o Compartment mechanical design and dimensions
If all the above requirements are satisfied, then further verification by
calculation or actual testing is not required.
Salient features of IEC 61439
Power frequency withstand voltage
The values of dielectric test voltage are reduced corresponding to rated insulation
voltage (Refer Table 3)
Salient features of IEC 61439
Impulse voltage withstand test
oVerification is mandatory either by test or by design rules.
o Test is not required when clearances in the assembly are 1.5 times the specified
value in Table - 4.
Salient features of IEC 61439
Degree of protection
oThe IPX1 to IPX6 tests on an assembly are deemed to be failure if water
comes into contact with electrical equipment housed within the enclosure.
o Requirements for empty enclosures for assemblies (IEC 62208) have been
incorporated in the standard.
Mechanical operation
o Rated numbers of operating cycles have been increased from 50 to 200.
Protection provided by barriers
oThe protection provided by horizontal top surfaces of easily accessible barriers is
changed from IPXXB (the protection of person against access to hazardous parts
with finger) to IPXXD (the protection of person against access to hazardous parts
with wire).
Cross-section area of neutral
o 100% - for phase cross section area upto 16 mm2
o 50 % - for phase cross section area above 16 mm2, with a minimum of 16 mm2
o For conductor other than copper, the cross section should be greater than
equivalent copper conductor
Salient features of IEC 61439
Degree of protection
oThe protection provided by horizontal top surfaces of easily accessible barriers is
changed from IPXXB (the protection of person against access to hazardous parts
with finger) to IPXXD (the protection of person against access to hazardous parts
with wire).
Salient features of IEC 61439
Additional Tests in IEC 61439
Resistance to corrosion Test
Purpose:
oTo ensure that deterioration of metallic component caused by corrosion shall not
impair the mechanical strength of switchboard.
Procedure:
oThe test is carried out on a typical switchboard enclosure or on a representative
sample showing the same constructional details.
6 cycles of 24 hr each to Damp Heat Cycling Test according to IEC 60068-2-30 at
(403) o C & relative humidity of 95%.
Salient features of IEC 61439
Additional Tests in IEC 61439
Verification of Thermal stability
Purpose:
oTo check the thermal properties of the enclosure
Procedure:
o The specimen is kept in a heating chamber at 70 degrees C for 7 days.
After that the sample is kept at ambient temperature for 4 days.
Assessment criteria:
o The sample shall show no cracks nor shall the material become sticky or
greasy
Sample is pressed with the forefinger wrapped in a dry cloth with a force of
5 N; no traces of cloth shall remain on the sample.
Salient features of IEC 61439
Additional Tests in IEC 61439
Resistance to abnormal heat & fire (Glow Wire Test)
Purpose:
Glow wire test checks the capability of insulation material to handle thermal stresses
produced by sources of heat or ignition.
Procedure:
Sample: Thinnest wall thickness of the completed application.
Pre-treatment: 24 hours at 23 o C at 50% RH.
Temperatures of glow wire: 650, 850 or 960 degrees C (depending on the
relevant specification).
960 degrees C for parts necessary to retain cur rent carrying parts in position;
850 degrees C for enclosures intended for mounting in hollow walls:
650 degrees C for all other parts, including parts necessary to retain the protective
conductor.
Force: 1 N
Contact time: 30 s
Assessment criteria:
There is no flame and glowing on the sample or flames/glowing of the sample
extinguish within 30 s. The cotton or the paper underlay doesnt ignite or burn.
Salient features of IEC 61439
Additional Tests in IEC 61439
Resistance to UV radiation
Purpose:
The UV radiation causes deterioration of synthetic material used for enclosures.
Procedure:
UV Test according to ISO 4892 2 method A; 1000 cycles of 5 min of watering and 25 min.
of dry period with xenon lamp providing a total test period of 500 hrs. The value of
temperature and humidity for the test are (653) o C and (655) %.
Assessment criteria:
Adherence of synthetic material (according to ISO 2409) shall have minimum 50%
retention. Sample shall not show cracks or deterioration visible to normal or corrected
vision without any additional magnification. This test is not required if synthetic material
supplier demonstrates that materials of same thickness or thinner comply with this
requirement.
NOTE: This test is applicable only for enclosures and external parts of ASSEMBLIES
intended to be installed Outdoors.
Salient features of IEC 61439
Additional Tests in IEC 61439
Lifting:
Purpose:
To ensure that there should be no damage to the panel during transportation & installation.
Procedure:
o The test is carried out on a sample having weight 1.25 times its maximum shipping weight.
o From a standstill position, the ASSEMBLY shall be raised smoothly without jerking in a vertical
plane to a height of (10.1) m and lowered in the same manner to a standstill
position. This test is repeated a further two times.
o After this the ASSEMBLY is raised up and suspended for 30 min at a height of (10.1) m without
any movement.
o Following this test the ASSEMBLY shall be raised smoothly without jerking from a standstill
position to a height of (10.1) m and moved (100.5) m horizontally, then lowered to a standstill
position.
o This sequence shall be carried out three times at uniform speed, each sequence being carried
out within 1 min.
Assessment criteria:
During the test, with the test weights in place, the ASSEMBLY shall show no deflections and after
the test show no cracks or permanent distortions visible to normal or corrected vision without
additional magnification, which could impair any of its characteristics.
Salient features of IEC 61439
Additional Tests in IEC 61439
Mechanical Impact Test
Purpose:
This test measures resistance of an enclosure towards external Mechanical Impact. The degree of
protection provided by an enclosure against impacts is indicated by the letters IK followed by two
digits depending on its ability to withstand the impact (as per IEC 62262).
Procedure:
o Number of impacts on each exposed face shall be five unless otherwise specified in relevant
product standard.
o The impacts shall be evenly distributed on the faces of the enclosure under test.
o At the surrounding of any point of enclosure, not more than three impacts shall be applied.
Assessment Criteria:
o Structural integrity shall be maintained.
o Degree of protection (IP) shall be unaffected.
o Functionality of electrical products shall not be hampered.
NOTE: Mechanical Impact test is not applicable to low voltage power switchgear and controlgear
(PSC) assemblies.
Salient features of IEC 61439
Additional Tests in IEC 61439
Marking:
Purpose:
To ensure that the markings are legible.
Procedure:
Marking made by moulding, pressing, engraving or similar
shall not be submitted to the following test.
The test is made by rubbing the marking by hand for 15 s
with a piece of cloth soaked in water and then for 15 s with a
piece of cloth soaked with petroleum spirit.
Assessment criteria:
After the test the marking shall be legible to normal or
corrected vision without additional magnification.
Salient features of IEC 61439
Routine Verifications
1. Degree of Protection of enclosures Visual Inspection
2. Clearance and creepage distances
3. Protection against electric shocks & integrity of protective
circuits visual inspection
4. Incorporation of built in components
5. Internal electrical connections & circuits
6. Terminals of external connections
7. Mechanical operation
8. Di-electric properties
9. Wiring, operational performance & function
Ambiguities clarified
Previously a manufacturer had to assign a current rating to each circuit, but they
were never required by the standard to prove its rating. In accordance with the new
standard, the manufacturers have to verify the rating of each type of circuit.
Each type of circuit will have its rating verified within the assembly and the
capability of the assembly as a whole will be proven by loading adjacent outgoing
circuits to their rated current, multiplied by the diversity factor.
Historically it has been assumed that if nothing was said, the neutral could have a
current rating equal to 50% of that of its associated phase. However, because this
has not been stipulated in any low-voltage standards for many years, any query
could only be answered by its custom and practice. IEC 61439 includes a default
current rating in accordance with custom and practice for circuits with conductors
above 16mm, but a specifier can ask for a higher rating to suit the needs of his
application.
In addition the ongoing question in respect of forms of separation has been
answered.
A devices integral enclosure, for example the case of a moulded case circuit
breaker, is defined as a means of providing separation from an adjacent circuit.
Classification of assemblies
Open-type and enclosed assemblies
- Enclosed assembly
An assembly is enclosed when there are protected panels on all its sides so as to provide a degree of protection
against direct contact not lower than IPXXB . Assemblies intended to be installed in common environments
shall be of enclosed type
- Open-type assembly
An assembly, with or without front covering, in which the live parts of the electrical equipment are accessible.
Such assemblies can be used only in places where skilled persons have access for their use.

External design
- Cubicle-type (column)
Used for large distribution and control equipment; mechanically joined multi-cubicle-type assemblies
are obtained by combining side by side more cubicle-type
assemblies.
- Desk-type
Used to control complex machines or plants in mechanical, iron and steel and chemical industries.
- Box-type
Intended to be mounted on a vertical plane, both jutting out as well as built-in; such assemblies are used
mainly for the department or area distribution in industrial or service sector environments.
- Multi-box-type
A combination of boxes, generally of protected type and with fixing flanges, each housing a functional
unit which may be an automatic circuit-breaker, a starter, a
socket completed with a blocking or protective circuitbreaker.
Classification of assemblies
Conditions of installation
- Assembly for indoor installation
Assembly which is designed for use in locations where the normal service
Conditions for indoor use as specified in the Std. IEC 61439-1 are fulfilled.
- Assembly for indoor installation
Assembly which is designed for use in locations where the normal service
conditions for outdoor use as specified in the Std. IEC 61439-1 are fulfilled.
- Stationary assembly
Assembly which is designed to be fixed at its place of installation, for instance to
the floor or to a wall, and to be used at this place.
- Movable assembly
Assembly which is designed so that it can readily be moved from one place of use to
another.
Conclusion
With the ever-increasing pressures of demand for higher network
utilization, assembly design optimization and more stringent safety,
the changes included in the assembly standard IEC 61439-2 are
important and overdue.
All assemblies that do not have a specific product standard are
covered and there is no opportunity to avoid compliance.
In the new standard, the methods of confirming design performance
are practical and pragmatic, reflecting the different market needs
and ways in which assemblies are produced. Several alternative and
equivalent means of verifying a particular characteristic of an
assembly are included. These are defined and their use restricted.
Where alternatives to type tests are used, a compensatory approach is
taken and margins are added to ensure equivalence. Overall, the
standard is performance based.
Bibliography
IEC 61439-1 - Low-voltage switchgear and controlgear assemblies
Part 1: General Rules
IEC 61439-2 - Low-voltage switchgear and controlgear assemblies
Part 2: Power switchgear and controlgear assemblies
Introduction to IEC 61439: A new standard on Switchgear & Controlgear
Assemblies by Mr. A P Rao; Mr. D A Chavan; Mr. P Patel; Mr. T N Shah
Switchgear Design & Development Center
Improving safety and performance in electrical assemblies - A guide to IEC 61439-
2 by Schneider Electric
IEC 61439 The new Standard for Low-Voltage Switchgear Assemblies
Changes and Effects in respect of Tests by GE Ronald Borchert, IPH Berlin
The new IEC 61439 Series Technical Seminar, 10th November, 2010 Singapore,
KEMA Quality

You might also like