STEP UP
TRANSFORMER LV SWITCHGEAR
AC & DC
HV- BREAKER AUXILIARY
SYSTEMS CONTROL
SYSTEMS
2 1
AUX. PROTECTION
TRANSF.
GOVERNOR
GENERATOR
1 BREAKER 2
STATIC
STARTER
PTs
&
CTs
SYNCHRONIZING
SYNCHRONOUS EXCITATION
TURBINE GENERATOR SYSTEM
STAR
POINT EXCITATION
CUBICLE TRANSFORMER
Overview of Electrical Systems
ELECTRICAL SYSTEMS
Excitation
System
Controller
Thyristor Converter
Synchronous machine
Grounding transformer
used to reduce fault
currents.
The 100% stator earth
fault detection is also done
through this transformer
Starting system
Generator transformer
Unit auxiliary transformer
Excitation Transformer
MV/LV Transformers
Lighting Transformers
Generator transformer UAT
Three Phase, 153.5 MVA, Rating 25 MVA 10.5/6.9
BHEL make. kV
Delta Star, neutral solidly Cooling: ONAN/ONAF
grounded.
Quantity of oil-13095
10.5/230 kV.
liters
Cooling-
ONAN/ONAF/OFAF On load tap changer at 12
Off circuit Tap changer at positions
five positions
Oil quantity:-39715 liters
Busduct and UAT
Gen. Transformer
System
Features:
It is a planned changeover.
Thru Operator Intervention.
No Interruption in Voltages.
Thru Synchronizing Relay
Manual Changeover Scheme
Scope:
Example :
U1-B/C-U2 Changeover:
--Proven scheme
--Either of Breaker can be closed thru ECB.
--Choice of Breaker tripping is done thru Trip
selection switch.
Fast Changeover Scheme
Feature:
This is only for OCA Bus coupler.
This changeover occurs when Voltage sink is
likely to occur.
OCA Bus coupler will close in Auto without any
time delay. No manual Intervention possible.
This changeover will take place in less than
200millisecond, hence chances of supply
interruption is very less.
Slow Changeover Scheme
Features:
This is a backup of Fast changeover.
Bus coupler will close in auto after certain
Time delay and fulfillment of certain
condition
Chances of unit survival depends on
situation
Black Out Condition
Switchyard
EHV Control and Switchgear
Circuit Breaker
Isolator
Current Transformer
Capacitive Voltage Transformer
Lightning Arrestor
PLCC equipment
Bus Switching Schemes
Disturbance recorder
Event logger
Remote telemetering units
Line diagram
Bus Switching Schemes
Double main and Transfer bus scheme
Main Bus-2
Main Bus-1
Bus Coupler
Transfer
Bay
Transfer Bus
3 Generators 4 Transmission
lines
PLCC System
Substation A Substation B
Wave trap
CVT
Tx Tx
Rx Rx
Electrical Protections
Generator and transformer protections
6.6 kV Protections
Station transformer protections
Motor protections
Transformer protections
220 kV Protections
Line protections
Bus bar protection
Breaker failure protection
VT Panel Protection Panel Terminal Box
Protection
Panel
Numerical Relays
Backside of relays
Tripping Matrix
Tripping Relay
Generator Protection:
Protection Functions (1)
27 81O
59 81U
87G
87G Generator differential
50/51 Over current protection
50 51V 51V/21 Voltage dependent backup
51 21 50/51N Stator earth fault
67N 50N 59N Neutral displacement
51N
67N Sensitive directional E/F
59N 27T 27TN 100% Stator E/F
N 27 & 59 Under & over voltage
81U/O Under & over frequency
Generator Protection:
Protection Functions (2)
MiCOM-P340-42
Settings
A B
220 kV Transformer protections
Transformer Differential protection.(87)
Three phase over current protection. (51)
Earth fault relay (Phase current balance)
Breaker failure relay.
Bucholz relay
Winding temperature relay
Oil temperature relay
Pressure relief device
DC SYSTEM
DC Systems
220 Volts DC Gas Turbine batteries
220 and 24 Volts Station batteries
432 Volts UPS batteries
220 Volts Emergency Lighting batteries
48 V Switchyard Battery systems
415 Volts System
GT MCCs
All the LT auxiliaries of Gas turbine including:
Auxiliary lube oil pump
Generator cooling water pump motors
GT cooling water pump motors
Ventilation fans
Battery chargers
Jacking oil pump motor