Professional Documents
Culture Documents
OBJECTIVE OF
AUTOMATION
LIGHTING (emergency)
What is BMS ?
5. Plumbing Integration
Its purpose is to control, monitor
and optimize building services e.g.,
6. Electrical Integration
lighting; heating & cooling; security
; audio-visual and entertainment
7. Access control
systems; ventilation and climate
control; time & attendance control
and reporting
BMS – CATEGORIES
BMS – CATEGORIES
BMS – CATEGORIES
BMS – CATEGORIES
Direct Digital Control - Diagram
ETHERNET
MICROLAN
NETWORK
INTERFACE
BUILDING
EUIPMENT
WHY NETWORKING??.
BMS Protocols BMS system manufacturer divided predominantly into two different
protocols, mentioned below-
SUPPLY
• BACnet - A Data Communication Protocol for Building Automation and Control Networks
developed by ASHRAE. It gives freedom to client to connect all BACnet compliant devices and
ease in commissioning & configuring.configuring.
• Lonworks -Lon Works is actually a family of products originally developed by the Echelon
Corporation. At the core of this technology is a proprietary communications protocol called Lon
Talk. Here one needs to buy license for each individual controllers &
devices. Commissioning requires software key (dongle) all the
time for commissioning & configuration.
EFFICIENT
OPERATION OPERATION
IMPROVED COST
OCCUPANT REDUCTION IN
COMFORT ENERGY
CONSUMPTION
Generally, building automation begins with control of
mechanical, electrical, and plumbing (MEP) systems. For
What is Controlled? instance, the heating, ventilation, and air-conditioning
CCTV
Lighting control is, likewise, low-hanging fruit for optimizing building
performance.
FIRE Detect smoke/heat at an early stage
What is Controlled? Generate alarms to enable a quick
ALARM evacuation of people.
Other systems that are often
SYSTEM VESDA (very Early Smoke detection & Alarm
controlled and/or brought under a System) for the Server Room is to get an advance
&
warning of fire inside the server area
complete automation system VESDA
Quench it so that the down time of the server
include: SYSTEM is minimized.
The Fire Alarm System is designed to meet the local IS 2189 standards.
Power monitoring
Security Multi Loop Networkable Microprocessor based analog addressable fire
alarm panel to be located in the central security & BMS Room T
Close circuit video (CCTV)
Card and keypad access
Addressable Manual Call Pull Stations Y
Addressable Sounders cum strobes P
Fire alarm system
Addressable AHU / Fresh Air Fan tripping
Elevators/escalators
E
modules
Plumbing and water monitoring Addressable input modules
S
Short Circuit Isolators
Armoured FRLS cables
Graphics Software (Part of IBMS Package)
Fire Alarm Repeater Panels (if required)
ATMOSPHERE CONDENSED CHILLED
REFRIGERANT AIR(ROOM)
AIR WATER WATER
COOLING TOWER
CHILLER UNIT AHU UNIT
INPUTS TO DIGITAL INPUTS:
NETWORK
THE CONTROLLER 1. Supply fan on/off (DP switch)
COMPONENTS 2. Auto/Manual Staus(MCC)
•Primary buS 3. Supply fire damper status (Actuator)
SUPPLY
An alarm is generated
whenever the supply or return
air fans fail to respond to
start-stop commands.
• Duty cycling - This turns off different HVAC units during peak load times in order to reduce
the demand charge. The system regulates off time according to such things as indoor
temperature.
• Load shedding - This turns off various building electrical loads to reduce demand charges.
Usually a schedule called a shed table is developed that sets priorities on which loads will be
first to be turned off.
• Averaging control - This averages the input from several sensors. For example, building
temperatures will vary in a building. The temperature in a lobby will be much different than the
temperature of an inner office on one of the higher floors. The computer receives input from
sensors located in different parts of the building, averages them, and acts on the average.
• Soft starting - This brings large equipment on line slowly to minimize the large onrush of
current that occurs when starting large motors.
• Direct Digital Control (DDC) is the most common deployed
Control sequence integrated with the building
control system today.
• The sensors and output devices (e.g., actuators, relays) used There are two types of lighting control systems
for electronic control systems are usually the same ones used
which are:
on microprocessor-based systems.
Analogue lighting control
• The distinction between electronic control systems and
microprocessor-based systems is in the handling of the input Digital lighting control
signals.
Electronic control system - the analog sensor
signal is amplified
microprocessor-based system, the sensor input is
converted to a digital form
Electrical Systems DURING EMERGENCY:
The emergency system must be able to supply all
But don’t confuse emergency
emergency loads simultaneously . If an alternate
Emergency systems are the circuits
systems with standby systems
power supply has adequate capacity, it may supply
and equipment that supply
emergency loads, legally required standby loads , and
illumination, power, or both within
optional standby system loads . When the emergency
10 sec after interruption of the
supply also supplies power for nonemergency loads,
normal electrical supply
the emergency loads take priority. If it doesn’t have
adequate capacity to carry all loads, it must have
automatic selective load pickup and load shedding to
ensure adequate power in this order of priority
1) Emergency circuits
2) Legally required standby circuits
3) Optional standby circuits
A temporary alternate source of power must be
available whenever the emergency generator is out of
service for more than a few hours for maintenance or
repair.
Electrical Systems
Transfer equipment
Transfer equipment must be automatic, identified for emergency use, and
approved by the . It must supply only emergency loads . Automatic
transfer switches must be electrically operated, mechanically held, and
listed for emergency system use. You must use multiple transfer switches
where a single generator supplies emergency loads plus other loads.
Wiring
Controller production building and key areas like server room. The Access control system will assign
Proximity/ Smart Card visiting rights to occupants. A database of such access rights issued will be stored in a
computer earmarked for the system.
Readers
AREAS COVERED • INTRUDER ALARM SYSTEM
Tripod /Flap barriers for the
The access control will be provided in • An alarm box mounted high on the face and rear
main
the following areas of a building.
lobby Handicap Barriers
• Basements lift lobby entry by turnstile • These systems can be stand-alone, i.e. just used to
Electro Magnetic Locks raise a highly audible sound at the property, or
• Ground floor main entry by turnstile
Emergency release box • Ground floor lift lobby may be monitored systems.
Access Management • Each floor entry from the lift lobby • Monitored systems incorporate remote supervision
• Each work cluster entry (where ever, possibly the local police.
BMS can help in controlling the individual lighting circuits (Internal) based on lux levels
and/or on schedules and substantially save on energy.
Lighting can be turned on, off, or There are two types of lighting control systems
dimmed with a building
which are:
automation or lighting control
Analogue lighting control
system based on :
Digital lighting control
• Chronological time (time of
day)
• Astronomical time
(sunrise/sunset)
• Daylight availability
using photocells
• Alarm conditions