Evolution of Antipumping relay

SF, LF, Evolis 24kV, EvolisHP


Anti pumping Relay
Description:
The anti-pumping relay is built into the mechanism of circuit breakers to ensure that the opening order
has priority.
This function prohibits re-closing of CB in case of fault tripping. In other words it prevents the possibility of
maintaining a permanent closing order inorder to avoid « pumping » of the CB

Antipumping relay:

Schneider Electric - Division - Name – Date 2


What’s new?

● Replacement of Electromechanical antipumping relay by Electronic version


due to obsolete component.
● Capable of handling multi-voltages, from 24V to 380V
● Input: DC/AC, Output: DC only. Associated closing release coil YF to have DC
ratings only
● New Electrical diagram: Change in assembling closing coil with relay
Please see attached file for the updated diagrams.

Schneider Electric - Division - Name – Date 3


Ex. of updated Electrical Diagram

Schneider Electric - Division - Name – Date 4


Change in the offer structure
● Configured full product:
● No impact in Elonet configuration.
● Additional bridge options of internal electrical connection is not possible
anymore. Only standard bridge remains unchanged.
● Additional leaflet with new electrical diagram is attached with user manual
systematically

● Spare part:
● Ref MV261200 will be replacing old references for RI mechanism in SF, LF,
Evolis 24 and Evolis HP ranges
● Ref MV261202 will be replacing old references for GmH mechanism in SF
MCset4, SF F400 and SF2 fixed versions.
● It is recommended to replace the closing coil and relay at the same time.

● Level C adaptation:
Separate Mail

Schneider Electric - Division - Name – Date 5


Implementation Planning

Configured full product:

Week 23 Week 30

LF SF
Evolis 24
Evolis HP

Schneider Electric - Division - Name – Date 6