AC POWER ANALYSIS

Content
 Average Power
 Maximum Average Power Transfer
 Complex Power
 Power Factor Correction

2
Average Power
Average Power, in watts (W), is the average
of instantaneous power over one period

1
P  Vm I m cos( v   i )
2

3
Average Power
Resistive load (R) absorbs power all the time.
For a purely resistive circuit, the voltage and
the current are in phase (v = i).

1 1 2 1 2
P  Vm I m  I m R  | I | R
2 2 2

4
Average Power
Reactive load (L or C) absorbs zero average
power.
For a purely reactive circuit, the voltage and the
current are out of phase by 90o (v - i = ±90).
1
P  Vm I m cos 90  0
o
2

5
Exercise 11.3
Find the average power supplied by the source and the average
power absorb by the resistor

6
Solution
The current I is given by

530 o
I  1.11856.57 o A
4  j2

The average power supplied by the voltage source is

1
P  (5)(1.118)cos(30o  56.57 o )  2.5W
2

7
Solution
The current through the resistor is

I R  I  1.11856.57 o A
The voltage across resistor is
VR  4I R  4.47256.57 o V
The average power absorbed by the resistor is
1
P  (4.472)(1. 118)  2.5W
2
Notice that the average power supplied by the voltage source is same
as the power absorbed by the resistor.
This result shows the capacitor absorbed zero average power.

8
Practice Problem 11.3
Calculate the average power absorbed by the resistor and the
inductor. Then find the average power supplied by the voltage source

9
Solution
The current I is given by

845o
I  2.5326.57 o A
3 j

For the resistor

I R  I  2.5326.57 o A
VR  3I  7.5926.57 o V
1 1
PR  Vm I m  (7.59)(2.53)  9.6W
2 2

10
Solution
For the inductor

I L  I  2.5326.57 o A
VL  jI L  2.53116.57 o V
1
PL  (2.53)(2.53)cos(90o )  0W
2
The average power supplied by the voltage source is
1
P  (8)(2.53)cos(45o  26.57 o )  9.6W
2
Notice that the average absorbed by the resistor is same as the power
supplied by the voltage source.
This result shows the inductor also absorbed zero average power.
11
MAXIMUM AVERAGE POWER
TRANSFER

12
Maximum Power Transfer
For maximum power transfer, the load
impedance ZL must equal to the complex
conjugate of the Thevenin impedance Zth

Z L  Z th *
R L  jX L  R th  jX th

13
Maximum Average Power
The current through the load is
Vth Vth
I 
Zth  ZL (R th  jX th )  (R L  jX L )

The Maximum Average Power delivered to


the load is
1 2
P | I | RL
2
1 | VTh |2 R L

2 (R Th  R L ) 2  (X Th  X L ) 2
14
Maximum Average Power
By setting RL = Rth and XL = -Xth , the maximum average power is

1 | VTh |2 | VTh |2
Pavg,max  
2 4R Th 8R Th

In a situation in which the load is purely real, the load resistance


must equal to the magnitude of the Thevenin impedance.

R L | Z th |

15
Exercise 11.5
Determine the load impedance ZL that maximize the power drawn
and the maximum average power.

16
Solution
First we obtain the Thevenin equivalent

To find Zth, consider circuit (a)

ZTh  j5  4 || (8  j6)
 (2.933  j4.467) Ω
To find Vth, consider circuit (b)
(8 - j6)
VTh  (100o )
4  (8 - j6)
 7.454   10.3o V

17
Solution
From the result obtained, the load impedance draws the maximum
power from the circuit when

Z L  ZTh *  (2.933  j4.467) Ω

The maximum average power is

| VTh |2 (7.454) 2
Pmax    2.368W
8R Th 8(2.933)

18
Practice Problem 11.5
Determine the load impedance ZL that absorbs the maximum
average power. Calculate the maximum average power.

19
Solution
First we obtain the Thevenin equivalent

To find Zth, consider circuit (a)


Z Th  5 || (8  j4  j10)
 (3.415  j0.7317) Ω

To find Vth, consider circuit (b)


By using current divider
8  j4
I (2)
8  j4  5  j10
 1.249   51.34o A

 VTh  5I  6.25  51.34 o V 20


Solution
From the result obtained, the load impedance draws the maximum
power from the circuit when

Z L  Z Th *  (3.415  j0.7317) Ω

The maximum average power is

| VTh |2 (6.25) 2
Pmax    1.429 W
8R Th 8(3.415)

21
Example 11.6
Find the value of RL that will absorbs maximum average power.
Then calculate that power.

22
Solution
First we obtain the Thevenin equivalent

Find Zth
ZTh  j20 || (40  j30)
 (9.412  j22.35) Ω

Find Vth
By using voltage divider
j20
VTh  (15030 o )
j20  40  j30
 72.76134 o V
23
Solution
The value of RL that will absorb the maximum average power is

R L | ZTh | (9.412) 2  (22.35) 2


 24.25
The current through the load is
VTh 72.76 134 o
I 
Z Th  R L (9.412  j22.35)  24.25
 1.8100.42 o A
The maximum average power is
1 2 1
Pmax  | I | R L  (1.8) 2 24.25  39.29W
2 2
24
Practice Problem 11.6
Find the value of RL that will absorbs maximize average power,
Then calculate the power.

25
Solution
First we obtain the Thevenin equivalent

To find Zth let Z1  80  j60 and Z 2  90 || ( j30)  (9  j27)


Then
ZTh  Z1 || Z 2  (17.181  j24.57) Ω

To find Vth
By using voltage divider
Z2
VTh  (12060 o )
Z1  Z2
 35.98  31.91o V
26
Solution
The value of RL that will absorb the maximum average power is
R L | ZTh | 30

The current through the load is


VTh 35.98 - 31.91o
I 
Z Th  R L (17.181  j24.57)  30
 0.6764   4.4o A

The maximum average power is

1 2 1
Pmax  | I | R L  (0.6764) 2 (30)  6.863W
2 2
27
Complex Power
 Apparent Power, S (VA)
 Real Power, P (Watts)
 Reactive Power, Q (VAR)
 Power Factor, cos 

28
Complex Power
 Complex power is the product of the rms
voltage phasor and the complex conjugate
of the rms current phasor.
 Measured in volt-amperes or VA
 As a complex quantity
 Its real part is real power, P
 Its imaginary part is reactive power, Q

29
Complex Power (Derivation)
V
1 Vrms   Vrms θ v
S  VI * 2
2 I
I rms   I rms θ i
S  Vrms I rms * 2
S  Vrms I rms θ v  θi

 Vrms I rms cos(θ v  θi )  jVrms I rms sin( θ v  θi )

30
Complex Power (Derivation)

SI 2
rms Z
S  I 2 rms (R  jX)
 I 2 rms R  jI 2 rms X

31
Complex Power (Derivation)
From derivation, we notice that the real power is

P  Vrms I rms cos(θ v  θi ) or

P  I 2 rms R
and also the reactive power

Q  Vrms I rms sin( θ v  θi ) or

Q  I 2 rms X

32
Real or Average Power
 The real power is the average power
delivered to a load.
 Measured in watts (W)
 The only useful power
 The actual power dissipated by the load

33
Reactive Power
 The reactive power, Q is the imaginary parts
of complex power.
 The unit of Q is volt-ampere reactive (VAR).
 It represents a lossless interchange between
the load and the source
 Q = 0 for resistive load (unity pf)
 Q < 0 for capacitive load (leading pf)
 Q > 0 for inductive load (lagging pf)

34
Apparent Power
 The apparent power is the product of rms
values of voltage and current
 Measured in volt-amperes or VA
 Magnitude of the complex power

| S | Vrms I rms  P  Q
2 2

35
Power Factor
 Power factor is the cosine of the phase
difference between voltage and current.
 It is also cosine of the angle of the load
impedance.

P
pf   cos( v   i )
S

36
Power Factor
 The range of pf is between zero and
unity.
 For a purely resistive load, the voltage
and current are in phase so that v- i = 0
and pf = 1, the apparent power is equal
to average power.
 For a purely reactive load, v- i = 90 and
pf = 0, the average power is zero.

37
Power Triangular

Comparison between the power triangular (a) and the impedance triangular (b).
38
Problem 11.46
 For the following voltage and current phasors, calculate the
complex power, apparent power, real power and reactive
power. Specify whether the pf is leading or lagging.

a) V = 22030o Vrms, I = 0.560o Arms.

b) V = 250-10o Vrms, I = 6.2-25o Arms.

c) V = 1200o Vrms, I = 2.4-15o Arms.

d) V = 16045o Vrms, I = 8.590o Arms.

39
Solution
a) S = VI* = (22030o)( 0.5-60o) c) S = VI* = (1200o)( 2.415o)
= 110-30o VA = 95.26 – j55 VA = 28815o VA = 278.2 + j74.54 VA

Apparent power = 110 VA Apparent power = 288 VA


Real Power = 95.26 W Real Power = 278.2 W
Reactive Power = -55 VAR Reactive Power = 74.54 VAR
pf is leading because current leads voltage pf is lagging because current lags voltage

b) S = VI* = (250-10o)(6.225o) d) S = VI* = (16045o)(8.5-90o)


= 155015o VA = 1497.2 + j401.2 VA = 1360-45o VA = 961.7 – j961.7 VA

Apparent power = 1550 VA Apparent power = 1360 VA


Real Power = 1497.2 W Real Power = 961.7 W
Reactive Power = 401.2 VAR Reactive Power = -961.7 VAR
pf is lagging because current lags voltage pf is leading because current leads voltage

40
Problem 11.48
Determine the complex power for the following cases:

a) P = 269 W, Q = 150 VAR (capacitive)

b) Q = 2000 VAR, pf = 0.9 (leading)

c) S = 600 VA, Q = 450 VAR (inductive)

d) Vrms = 220 V, P = 1 kW, |Z| = 40  (inductive)

41
Solution
a) Given P = 269W, Q = 150VAR (capacitive)
Complex power, S  P  jQ  (269  j150)VA
 308   29.14 o VA
b) Given Q = 2000VAR, pf = 0.9 (leading)

pf  cos  0.9    25.84 o


Q 2000
Q  S sin   S    4588 .31
sin  sin( 25.84 )
o

P  S cos  4129 .48

Complex power, S  P  jQ  (4129  j2000)VA


 4588  - 25.84 o VA
42
Solution
c) Given S = 600VA, Q = 450VAR (inductive)

Q 450
Q  S sin   sin     0.75
S 600
  48.59 o
pf  cos  0.6614

P  S cos  396 .86

Complex power, S  P  jQ  (396.9  j450)VA


 600 48.59 o VA
43
Solution
d) Given Vrms = 220V, P = 1kW, |Z| = 40 (inductive)
| V |2 220 2
S   1210
| Z| 40
P 1000
P  S cos  cos    0.8264
S 1210
  34.26 o
Q  S sin   681.25

Complex power, S  P  jQ  (1000  j681.2)VA


 1210 34.26 o VA
44
Problem 11.42
 A 110Vrms, 60Hz source is applied to a load impedance Z. The
apparent power entering the load is 120VA at a power factor
of 0.707 lagging. Calculate

a) The complex power

b) The rms current supplied to the load.

c) Determine Z

d) Assuming that Z = R + j L, find the value of R and L.

45
Solution
Given S = 120VA, pf = 0.707 = cos   = 45o
a) the complex power

S  S cos  jS sin   84.84  j84.84VA


b) the rms current supplied to the load

S  Vrms I rms
S 120
 I rms    1.091A
Vrms 110

46
Solution
c) the impedance Z

S  I rms Z
2

S
Z  2
 (71.278  j 71.278)
I rms
d) value of R and L
If Z = R + jL then Z = 71.278 + j 71.278

 R  71.278Ω
71.278
ωL  71.278 L   0.1891H
2f
47
Problem 11.83
 Oscilloscope measurement indicate that the voltage across a
load and the current through is are 21060o V and 825o A
respectively. Determine

a) The real power

b) The apparent power

c) The reactive power

d) The power factor

48
Solution
a) the real power
1 1
S  VI*  (21060 o )(8  25o )
2 2
 (84035o )VA  (688.1  j481.8)VA
P  S cos(35o )  840 cos(35o )  688.1W
b) the apparent power
S  840 VA
c) the reactive power
Q  S sin (35o )  840 sin (35o )  481.8VAR
d) the power factor
P
pf   cos(35o )  0.8191(lag ging)
S 49
Power Factor Correction
 The process of increasing the power
factor without altering the voltage or
current to the original load.
 It may be viewed as the addition of a
reactive element (usually capacitor) in
parallel with the load in order to make
the power factor closer to unity.

50
Power Factor Correction
 Normally, most loads are inductive.
Thus power factor is improved or
corrected by installing a capacitor in
parallel with the load.
 In circuit analysis, an inductive load is
modeled as a series combination of an
inductor and a resistor.

51
Implementation of Power Factor Correction

52
Calculation
If the original inductive load has apparent power S1, then
P = S1 cos 1 and Q1 = S1 sin 1 = P tan 1

If we desired to increased the power factor from


cos1 to cos2 without altering the real power,
then the new reactive power is
Q2 = P tan 2

The reduction in the reactive power is caused by the shunt capacitor is given by
QC = Q1 – Q2 = P (tan 1 - tan 2)
53
Calculation
The value of the required shunt capacitance is determined by the
formula

QC P(tanθ1  tanθ 2 )
C 
ωV rms
2
ωV rms
2

Notice that the real power, P dissipated by the load is not affected
by the power factor correction because the average power due to
the capacitor is zero

54
Example 11.15

 When connected to a 120V (rms), 60Hz power line, a


load absorbs 4 kW at a lagging power factor of 0.8.
Find the value of capacitance necessary to raise the
pf to 0.95.

55
Solution
If the pf = 0.8 then,
cos1 = 0.8  1 = 36.87o
where 1 is the phase difference between the voltage and current.
We obtained the apparent power from the real power and the pf as shown below.

P 4000
S1    5000 VA
cos1 0.8
The reactive power is

Q1  S1 sin 1  5000 sin 36.87  3000 VAR

56
Solution
When the pf raised to 0.95,
cos2 = 0.95  2 = 18.19o

The real power P has not changed. But the apparent power has changed. The
new value is
P 4000
S2    4210 .5VA
cos 2 0.95

The new reactive power is

Q2  S 2 sin  2  1314 .4VAR

57
Solution
The difference between the new and the old reactive power is due to the parallel
addition of the capacitor to the load.
The reactive power due to the capacitor is

QC  Q1  Q2  3000  1314 .4  1685 .6VAR


The value of capacitance added is

QC 1685 .6
C   310.5μF
V rms 2 (60)(120)
2 2

58
Practice Problem 11.15

 Find the value of parallel capacitance needed to


correct a load of 140 kVAR at 0.85 lagging pf to
unity pf. Assume the load is supplied by a 110V
(rms) 60Hz power line.

59
Solution
If the pf = 0.85 then,
cos1 = 0.85  1 = 31.79o
where 1 is the phase difference between the voltage and current.
We obtained the apparent power from the reactive power and the pf as shown
below.

Q1 140kVAR
S1    265.8kVA
sin 1 sin( 31.79)

The real power is

P  S1 cos1  265 .8 cos(31.79)  225 .93kW

60
Solution
When the pf raised to 1 (unity),
cos2 = 1  2 = 0o

The real power P has not changed. But the apparent power has changed. The
new value is

P 225.93kW
S2    225.93kVA
cos 2 1

The new reactive power is

Q2  S 2 sin  2  0

61
Solution
The difference between the new and the old reactive power due to the parallel
addition of the capacitor to the load.
The reactive power due to the capacitor is

QC  Q1  Q2  140000  0  140 kVAR


The value of capacitance is

QC 140kVAR
C   30.69mF
V rms 2 (60)(110)
2 2

62
Problem 11.82

 A 240Vrms, 60Hz source supplies a parallel


combination of a 5 kW heater and a 30 kVA
induction motor whose power factor is 0.82.
Determine
a) The system apparent power
b) The system reactive power
c) The kVA rating of a capacitor required to adjust the
system power factor to 0.9 lagging
d) The value of capacitance required

63
Solution
For the heater
P1 = 5000 Q1 = 0

For the 30kVA induction motor, the pf = 0.82 then,


cos1 = 0.82  1 = 34.92o
The real and the reactive power for the induction motor

P2  S 2 cos(34.91)  30000 x 0.82  24600 W

Q2  S 2 sin( 34.91)  17171kVAR

64
Solution
The total system complex power
Stotal = S1 + S2 = (P1 + P2) + j (Q1 + Q2) = 29600 + j17171
The system apparent power
S = |Stotal| = 34.33kVA
The system reactive power
Q = 17171 kVAR

The system power factor

P 29600
pf    0.865
S 34220
65
Solution
The system pf = 0.865 then,
cos1 = 0.865  1 = 30.12o

The new system pf = 0.9 then,


cos2 = 0.9  2 = 25.84o

The rating for the capacitance required to adjust the power factor to 0.9

QC = P (tan 1 + tan 2) = 29600 (tan 30.12 + tan 25.84) = 2833kVAR

66
Solution
The value of capacitance is

QC 2833
C   130.46μF
V rms 2 (60)(240)
2 2

67