Professional Documents
Culture Documents
Emergency Standby
Engine Generators
10
TIME (SECONDS)
Regional Sales 1
Manager – Power
Electronics
Cummins Power 0.1
0.05
Generation
1 3 10
RTD’s
Resistance
temperature detectors
are used to sense
winding temperatures.
A long term
monitoring philosophy
that is not readily
detected by other
protective devices
IEEE Recommended Protection
Schemes
SMALL MACHINES Any recommendation
– Up to 1000kVA, 600V based entirely on
maximum machine size is not
MEDIUM MACHINES entirely adequate.
– 1000kW to 12,500 kVA The importance of the
regardless of voltage machine to the
LARGE MACHINES system or process it
– Up to 50,000 kVA serves & the reliability
regardless of voltage required are the
important factors
Small Generators – 1000kVA
Device 51V – Backup overcurrent
Device 51G - GFP
Device 32 – Reverse Power
Device 40 – Loss of Field
Device 87 - Differential
Medium Size Generators – 1 to
12.5 mVA
Device 51V – Backup overcurrent
Device 51G - GFP
Device 32 – Reverse Power
Device 40 – Loss of Field
Device 87 - Differential
Device 46 – Negative phase sequence
for paralleling or utility paralleling
My Opinion – 3mW and less GENSET
SURGE SUPPRESSORS
AM SW KW KWH PF 40 32 GOV AVR 51V
VM SW HZ 27 81 59
86
VM SW HZ 46 25C 25
SS
UL listed utility grade generator protection relay
SWITCHGEAR TRIP
CLOSE
NFPA70 - NEC
445.12(A) Overload Protection
– Generators, except AC generator exciters, shall be protected from
overloads by inherent design, circuit breakers, fuses, or other
acceptable overcurrent protective means suitable for the conditions of
use.
240.15(A)
– Overcurrent Device Required. A fuse or an overcurrent trip unit of a
circuit breaker shall be connected in series with each ungrounded
conductor. A combination of a current transformer and overcurrent relay
shall be considered equivalent to an overcurrent trip unit.
240.21(G) Conductors from Generator Terminals
– Conductors from generator terminals that meet the size requirements of
445.13 shall be permitted to be protected against overload by the
generator overload devices) required by 445.12
Is the Alternator Protected?
Generator is required to be
CABLETHERMAL
THERMAL
protected
– Generator conductors are
CABLE
DAMAGECURVE
DAMAGE CURVE
100
assumed protected by same
device protecting the genset.
10
GENERATOR
GENERATOR
THERMAL
DAMAGE
CURVE
THERMAL
DAMAGE
CURVE Most common protection is
10
10
molded case breaker with
PROTECTIVE RELAY
thermal/magnetic trip
CURVE
– 100% rated thermal magnetic
TIME (SECONDS)
(SECONDS)
1
breakers don’t fully protect
TIME(SECONDS)
1
1
alternator
GENERATOR
TIME
0.1
0.1
0.1
THERMAL DAMAGE
CURVE Generator Protective Relay
0.05
0.05
provides the best protection
& superior coordination for
11 333 10
10
10 100
100
100
downstream devices
AMPS
AMPS(TIMES
AMPS (TIMESRATED)
(TIMES RATED)
RATED)
100% Rated Electronic Trip
Breaker is an Improvement
800A
800A MOLDED
INSULATED CASE CB
CASE CB GEN FLA
Time
GENSET
DAMAGE
CURVE
Gen Relay
Current
Some Generator Mfrs offer self
contained alternator protection
Is it UL listed as a
generator protection
relay?
Does it provide O/L
protection for the
alternator and O/L and
short circuit protection for
the feeder?
Can it protect its transfer
switch on the emergency
side?
Differential Protection (87)
Rarely selected for LV
machines smaller
than 1.5 mW.
How do you mount
the CT’s?
Cost vs. benefit?
Differential Protection (87)
The value of differential protection is
that it is very fast in detecting faults in
a circuit.
High current levels that pass through
both sets of CT’s will not cause a trip
on common events like motor starting,
or even on downstream faults that are
intended to be cleared by other
means.
The high speed of operation for faults
sensed within the operating zone
makes it possible limit damage inside
an alternator stator when a fault inside
the machine occurs.
The device would also operate on a
feeder fault, but in general, once a
fault is sensed in a feeder, the feeder
will be replaced,
Differential Protection (87)
A key point to remember is that differential relays
don’t prevent damage, they LIMIT damage.
If a relay is properly operating it won’t trip until
there is actually a line to ground fault
somewhere in its zone of protection.
By limiting the duration of a fault, it is often
possible to limit damage, but there is STILL
damage.
Eventually, you will have to deal with it.
Some mfrs. have high speed internal single
phase protection
Differential Protection (87)
The protective devices GENSET
be selected based on an
understanding of the
SHUTDOWN
balance between
reliability and protection.
The more protection used 87
51
Always carefully consider the balance of protection versus reliability, especially when
the protection is for equipment that is operating for very few hours.
With some mfrs. the alternator current sensing function monitors faults inside the
machine. When the machine incorporates protection for the alternator from
overcurrent conditions based on an I2t function, and regulates single phase faults
differential protection is optional.
On 15kV class machines, the alternator stator is expensive enough that it would
probably be repaired rather than replaced, so it will make more sense to try to limit
damage in the machine and have it repaired, in the general case.
In cases where it is decided to use differential protection, it is desirable to minimize
the zone of protection and use properly sized and matched CT’s so that the
probability of nuisance tripping is reduced. Since the generator set provides
overcurrent protection from the alternator “out”, differential protection can be applied
with matched CT’s provided and mounted at the wye side and alternator output,
preferably in the terminal cabinet. The differential relay can be mounted in the vicinity
of the generator set or in the switchgear.
Recommendations
500
Peak Current: IR/X”d Alt %Standby Max Line
400 Current
300
Regulates at 3X Rated
%Current
100
0
0 5 10 15 20
time, sec
1Φ Fault – Current Regulation
600
300
200
100
0
0 1 2 3 4 5 6 7 8
tim e, sec
120
100
Percent of Nominal Voltage
80
60
40
20
0
0 1 2 3 4 5 6 7 8
tim e, sec