TRANSFORMER PROTECTION

G. Mohanan
Executive Engineer
Transmission Division.
Kazhakoottam
Phone 9446008139
TRANSFORMER PROTECTION

CLASSIFICATION

1. Protection against Electrical Faults


Unit Protection (against Internal Faults)
Differential Protection.

REF Protection.

Non-Unit Protection (against uncleared external faults)


IDMT O/C, E/F Relays.

Definite Time O/C, E/F Relays.

2.Protection against Abnormal Conditions


 Over Load protection

Over Fluxing Protection

3. Protective Devices (Non-electrical)


Buchholz (Main Tank / OLTC)

Oil / Winding Temperature Indicators / Relays

Pressure Release Valve

Oil Level Gauges / Indicators


TRANSFORMER PROTECTION

DIFFERENTIAL RELAY – OPERATING PRINCIPLE


Current Distribution (External Fault)

Battery Analogy (External Fault)


TRANSFORMER PROTECTION

DIFFERENTIAL RELAY – OPERATING PRINCIPLE.

Current Distribution ( Internal Fault)

Battery Analogy (Internal Fault)


TRANSFORMER PROTECTION

DIFFERENTIAL RELAY – NEED FOR


BIAS

 Transformer ratio = 100/50KV


 F.L. Current = 100A (on 100 KV side)
= 200A (on 50 KV side)
 Tap Range = (+/-) 10%
 % Impedance (Zt) = 10%
TRANSFORMER PROTECTION

DIFFERENTIAL RELAY – NEED FOR


BIAS.

Current Distribution on Load on Normal Tap


TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION – NEED FOR


BIAS

CURRENT DISTRIBUTION ON LOAD ON + 10% TAP


TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION – NEED FOR BIAS.

CURRENT DISTRIBUTION ON THROUGH FAULT ON + 10%TAP.


TRANSFORMER PROTECTION

DIFFERENTIAL RELAY – NEED FOR


BIAS.

 Diff. Pick-up = 15% (0.15A), Bias = 30% (Assumed)


 Modified Diff. Pick-up due to Restraining Effect of Bias
Id mod = 0.30 x (10+9)/2 + 0.15 = 2.85 + 0.15 = 3.0A.
 Actual Diff. Current = 1.0A
TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION – BIAS CHARACTERISTIC.


TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION – MAGNETISING


INRUSH.

STEADY STATE
 At zero volts, flux is “(-) ɸm” since flux in quadrature with voltage.
 Total flux change in half the voltage cycle is “2ɸm” (-ɸm to +ɸm).
SWITCHING AT VOLTAGE ZERO.
 Initial flux zero as against (-) ɸm corresponding to steady state.
 Total flux changes from zero to 2ɸm.
 Flux doubling causes extreme saturation of core.
TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION- MAGNETISING


INRUSH.

 Magnetising Impedance drastically reduces due to core


saturation causing heavy inrush current.
 Inrush appears on excited winding (primary) without any
balancing current on secondary and unstabilises differential
protection.
TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION – INRUSH


STABILITY

 Inrush current has predominant 2 nd harmonic content


(typical value, up to 60% max. of Fundamental depending
upon instant of switching).
 Dominant 2 nd harmonic component is used to restrain the
protection on inrush condition.
TRANSFORMER PROTECTION

BIASED DIFFERENTIAL PROTECTION- INTERNAL CIRCUIT.


TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION- CT CONNECTIONS.


STAR / STAR TRANSFORMER
TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION – CT CONNECTIONS.


DELTA / STAR TRANSFORMER (Dy11)
TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION – STAR / STAR


TRANSFORMER

Instability With STAR CONNECTED CTs On Up-stream Earth Fault.


TRANSFORMER PROTECTION

DIFFERENTIAL PROTECTION – STAR / STAR


TRANSFORMER.

Delta / Delta CTs filter Zero Seq. Current & ensure Stability.
TRANSFORMER PROTECTION

REF
PROTECTION

Current Distribution on External Earth Fault.


TRANSFORMER PROTECTION

REF
PROTECTION

Current Distribution on Single Phase load.


TRANSFORMER PROTECTION

REF
PROTECTION

Current distribution on Internal Fault.


TRANSFORMER PROTECTION

REF
PROTECTION

Current distribution on Internal Fault.


TRANSFORMER PROTECTION

STABILISING RESISTOR
SETTING CRIETERIA

 If B-ɸ CT fully active while


NCT fully saturates, maximum
Voltage across Relay Branch
(Vs) = If/n (Rct + 2Rl).
 If Relay current setting is “Is”
and Ohmic burden is “Zr”,
Stab. Resistor Setting (Rs)
= Vs/Is – Zr Ohms.
TRANSFORMER PROTECTION

BACKUP PROTECTION

INFLUENCING FACTORS

 Vector Group

 Infeed conditions (Single or both end infeeds)

 Type of Neutral Earthing


TRANSFORMER PROTECTION

BACKUP
PROTECTION

 50 – High Set Inst. O/C Relay ( Delta side S.C. protection)


 64 – REF Protection (Delta side REF protection)
 51 – IDMT O/C Relay (time graded backup for down-stream S.C.)
 51N – IDMT E/F Relay (time graded backup for down-stream E/F)
TRANSFORMER PROTECTION

BACKUP PROTECTION
E/F PROTECTION ON DELTA
SIDE.

 Delta side E/F relay inherently immune to Star side earth


faults but can respond to Delta winding earth faults. Hence
sensitive, high speed E/F relay (64) in High Impedance mode
can be used on Delta side.
TRANSFORMER PROTECTION

BACKUP
PROTECTION

 50 – High Set Inst. O/C Relay (Primary Star side S.C.)


 51- IDMT O/C Relay (time graded backup for down-stream S.C.)
 67N – Directional IDMT E/F Relay (backup to TFR/down-stream E/F.)
 51N–IDMT E/F relay (time graded backup against down-stream E/F)
TRANSFORMER PROTECTION

BACKUP E/F PROTECTION- STAR / STAR


TRANSFORMER

 Directional IDMT E/F relay (67N) looking towards


transformer do not respond to up-stream E/F due to
current out-flow from TFR terminal into Grid, thus
requiring co-ordination with down-stream E/F
protections only.
TRANSFORMER PROTECTION

OVER LOAD
PROTECTION
1. Definite Time Over Load Relay

 Definite Time O/C relay used for Alarm.

 Set above permissible over load with small time


delay(say 5 seconds)

 Relay should have adjustable current setting, time delay


(built-in or external) and high reset ratio.

 Some times, extended tripping is provided with


additional time delay.
TRANSFORMER PROTECTION

OVER LOAD
PROTECTION
2. Thermal Over Load Relay
 Set to match over load withstand of transformer.
 Pre-trip Alarm with lower pick-up threshold.
 Operating time for trip (t)
t = T. ln {(I/K.In)² – (I pre/K.In)²} / (I/K.In)²- 1}
Where
I = Over Load current.
K.In = Max. Permissible Load Current.
I pre = Load current prior to Over Load.
T = Thermal Time Constant (minutes)
TRANSFORMER PROTECTION

OVER FLUXING
PROTECTION
INDEX OF OVER FLUXING
V α Φ.f, Hence Φα V/f
 Tandem variations in voltage & frequency most
likely to occur in case of Generator Transformer
during startup or coasting down (due to AVR
malfunction or manual control) requiring Over
Fluxing Protection.

 It is necessary for Grid TFRs as well, under certain


conditions (e.g. TFR fed by long transmission line
subjected to high voltage due to Ferranti Effect
when off-loaded).
TRANSFORMER PROTECTION

OVER FLUXING
PROTECTION
1. Definite Time Over fluxing relay.
 Adjustable V/f setting (typically 1 – 1.5 of 110V / 50Hz).
 Adjustable trip time delay (typically 10 – 120S)
 Pre-trip Alarm (fixed or variable delay)
2. IDMT Over Fluxing Relay
 Adjustable V/f setting.
 Inverse time characteristic to match with TFR with-stand
characteristic.
 Pre-trip Alarm and accelerated trip for severe over
fluxing condition.
TRANSFORMER PROTECTION

BACKUP EARTH
FAULT
PROTECTION
 NCT operated
Standby E/F
Relay responds to
internal earth
faults as well,
besides providing
backup against
external faults.
 Stand by E/F relay
offers better
sensitivity since
NCT ratio not tied
up with load and
lower ratio, based
on E/F infeeds, is
possible.