[Meaning] This is the method that detects any possible lost phase of E/L three-phase [Countermeasures]
input power. The decision is carried out by checking the DC rectifying
voltage(DC 48V) in the controlling power three-phase AC37V. 1. Verify that D48 FUSE LED(LED3.LED4) in DOP-116
PCB lights on.
[Explanation] 2. Check the fuse(FS3, FS4) when the above LED lights off. If it
If IALM(red) LED and P.F(red) LED lights up on DOC-131,
operation will be unable. is disconnected, replace it with a rated fuse(250V/3A).
3. If any error are not found at the above items, verify that the
V48_Down_Count >5 voltage AC 37V± 10% among pin 1, 9 and 12 of PB
TCD 70
connector in DOP-116 PCB BOARD.
4) Verify that the voltage between AB-10 pin in DOC-131 PCB
and F.G is DC48V± 10% .
Left picture below show DC 48V at a normal power and the right picture shows
wave form when a phase was lost.
Lost phase detecting circuit in DOC-131 lights ARM LED when it detects a wave
form which falls down 35V or less. If it detects such wave for 300msec, it makes
Error 70.
[ Wave form & voltage on normal ] [ Wave form & voltage on abnormal ]
[Meaning] When input power(3 phases) drops to its 85% or below, [Countermeasures]
the trouble occurs.
1. There is no special countermeasure.
Check the power source from the building.
2. Refer to countermeasures of TCD70.
[Explanation] In case 85% of voltage drop continues for 90 msec, the trouble is
detected.
It is detected by the voltage(DC48V) rectified from AC37V that is
3 phases power for control.
+1 under_85p_count
Part: : TCD Code
Di1(Si210) Elevator / Trouble Shooting Ctrl No. : SI-TS-02-2
Page: 42/117
○ Operation CPU
TCD 72 ER_C1SW_ON Detection Application Si210
○ Speed CPU
[Meaning] C1SW ON condition lasts for over 540ms after C1SW OFF [Countermeasures]
commanded.
1. Check the C1SW wiring according to drawing.
2. Refer to countermeasures of TCD88.
3. Replace C1SW contactor.
[Explanation]
Coil[SW_SS_48V_
SWD_I[VI_C1SW] SWD_O[VO_C1ST] DOWN_HOLD] Check_out
Coil[SV_INV_
SWD_I[VI_C1SW] SWD_O[VO_C1ST] 0x923D
SW_FAIL]
Coil[SW_SS_
0x8066 0x8081 0x9210 DSP_WD]
Check_out
TMC_Start(C1SW__
ERROR_DETECT_T)
TMC_Check(C1SW_ERROR SWD_I[V1_C1SW]
_DETECT_T,FINISH_STATE) TCD 72
0x802A
Part: : TCD Code
Di1(Si210) Elevator / Trouble Shooting Ctrl No. : SI-TS-02-2
Page: 43/117
○ Operation CPU
TCD 73 ER_C1SW_OFF Detection Application Si210
○ Speed CPU
[Meaning] C1SW OFF condition lasts for over 540ms after C1SW ON [Countermeasures]
commanded.
1. Check the C1SW wiring according to drawing.
2. Refer to countermeasures of TCD89.
3. Replace C1SW contactor.
[Explanation]
Coil[SW_SS_48V_
SWD_I[VI_C1SW] SWD_O[VO_C1ST] DOWN_HOLD] Check_out
Coil[SV_INV_
SWD_I[VI_C1SW] SWD_O[VO_C1ST] 0x923D
SW_FAIL]
Coil[SW_SS_
0x8066 0x8081 0x9210 DSP_WD]
Check_out
TMC_Start(C1SW__
ERROR_DETECT_T)
TMC_Check(C1SW_ERROR SWD_I[V1_C1SW]
_DETECT_T,FINISH_STATE) TCD 89
0x802A
If data of each BIT is 1, the SPEC DATA of set BIT is the reason of the trouble.
15 14 13 12 11 10 9 8
Service Shelter
- - - - - -
floor plate
7 6 5 4 3 2 1 0
H.CT Rotary
IGBT Motor - Speed TM Gear
TURN Encoder
Part: : TCD Code
Di1(Si210) Elevator / Trouble Shooting Ctrl No. : SI-TS-02-2
Page: 45/117
○ Operation CPU
TCD 76 EEPROM Write Trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
When different values are found over 100 times while writing data on
EEPROM and reading data from the same address.
1. Verify if SW2 switch in DOC-131 is switched to “WE” side.
2. Verify if EEPROM is properly inserted into DOC-131.
[Explanation] This error means that the SPEC DATA is not written properly due to 3. Check EEPROM.
fault
4. Replace SPEC ROM.
Part: : TCD Code
Di1(Si210) Elevator / Trouble Shooting Ctrl No. : SI-TS-02-2
Page: 46/117
○ Operation CPU
TCD 77 EEPROM Read Trouble Detection Application Si210
○ Speed CPU
[Meaning] Different data are found over 4 consecutive times while reading data [Countermeasures]
from the same address on EEPROM. 1. Check EEPROM.
2. Verify that EEPROM is properly inserted into DOC-131
BOARD.
[Explanation] If there is any different data over 4 times consecutively as same
address data is read. The error is detected 3. Replace SPEC ROM.
Part: : TCD Code
Di1(Si210) Elevator / Trouble Shooting Ctrl No. : SI-TS-02-2
Page: 47/117
○ Operation CPU
TCD 78 Floor Height measuring Table SUM trouble Detection Application Si210
○ Speed CPU
[Symptom]
* How to measure floor height
1. Low speed return operation to the lowest level with buzzer ringing and display 1) Press ‘A12E’ on ANN, and press 3.
ACD = 09.
2) If the floor height is measured successfully, press ‘FFFF’.
2. In case there is no Non-Stop floor, operate the nearest floor.
3. Stop and standby with ACD = 09. 3) If the measuring fails, measure the floor height again.
4) If the measuring fails repeatedly, verify if the total floor number
and the highest floor in EEPROM(28C64) are identical with
those in the field.
Part: : TCD Code
Di1(Si210) Elevator / Trouble Shooting Ctrl No. : SI-TS-02-2
Page: 48/117
○ Operation CPU
TCD 79 NVRAM Floor Height measuring Table SUM trouble Detection Application Si210
○ Speed CPU
[Meaning] [Countermeasures]
NVRAM floor height table error
If even one of three cases below occurs, this error will occur.
1. When the sum obtained by adding each floor height table value saved in
NVRAM(Backup RAM) and the floor height sum data saved in
RAM(Backup RAM) does not match.
2. When the floor height sum data in NVRAM is 0(Zero).
3. When the floor height of the lowest floor of floor height table in NVRAM is
not the lowest floor height(150000).
[Symptom]
1. Low speed return operation to the lowest level with buzzer ringing and display
ACD = 0B.