Mandatory Test
In addition
No-load test
Before commencing making and breaking tests, no-load operations and no-
load operating sequences (O, CO and O – t – CO) shall be made and details
of the operating characteristics of the circuit-breaker recorded. Details such as
closing time and opening time shall be recorded.
Frequency
Arcing time and arcing window: Depending on the point of mechanical contact
separation, interruption with minimum, medium and maximum arcing time
The main requirements for the test duty are related to:
Outer pole under test to simulate the maximum stress in the coupling
mechanism
The main requirements for the test duty are related to:
Breaking of the 87% of the rated symmetrical short-circuit current with the
maximum arcing time and with the recovery voltage based on phase-to-phase
voltage
Compact & Lightweight and High Reliability with extremely low failure rate
Contact materials with low welding tendency and low chopping current
Contact design with arc control for high interrupting capacity and for
withstanding fast recovery voltages
Who?
What?
Responsibility
only manufacturer
Type tests qualify the type of product series while the routine tests ensure that
the manufactured series are always in accordance with the type tested sample
Circuit-breakers qualified according to the IEC 62271-100 are best suited for
switching of short-circuit currents. They are able to switch currents with high
asymmetry and fast rising TRVs without any maintenance throughout the lifetime
Most of the failures are due to inappropriate human behaviors either during the
project management phase (wrong product definition) or during operations
(installation, operation, maintenance, etc.)