Product Manager
ACS 1000 Product Overview
© ABB Switzerland Ltd. MV Drives
ACS 1000 Product Overview
Objectives of Presentation
Overview
Main Features
Options
© ABB Switzerland Ltd. MV Drives
ACS 1000 Product Overview
Sinusoidal output Drive Product with a wide
variety of Standard Options
Efficiency >98%
Less than 2 days com-
IGCT technology
missioning for the drive
Direct Torque
Control
© ABB Switzerland Ltd. MV Drives
(6’000 kVA)
5,000
Motor Power in kW
W3 Water-
W2 cooled
re-connection with
W1
2’000 A3 Air- cooled
of Motor
winding from
step- up
transformer
Star to Delta
A2
315 A1
© ABB Switzerland Ltd. MV Drives
I>> Prot
MV AC
Induction
Motor
2000 mm
excl.
air outlet
cover
© ABB Switzerland Ltd. MV Drives
3000 mm
900 mm
ACS 1000 Air Cooled Looking Inside ...
2000 mm
© ABB Switzerland Ltd. MV Drives
Sine filter
Capacitor
Cooling
© ABB Switzerland Ltd. MV Drives
Unit
DC Capacitors
Sine Filter
Choke Common
Control
mode
Choke
ACS 1000 Water Cooled Swing Frame for easy Maintenance
© ABB Switzerland Ltd. MV Drives
ACS 1000 Water Cooled Cooling Circuit Overview
© ABB Switzerland Ltd. MV Drives
Air cooled drive with
integrated Transformer
ACS 1000i
2150 mm excl.
air outlet cover
2660 mm incl.
air outlet cover
Note: provide
min. 800mm
clearance for
free air flow !
© ABB Switzerland Ltd. MV Drives
3300 mm
1120 mm
ACS 1000i - Overview
Contactor Control
Line
connection Inverter
© ABB Switzerland Ltd. MV Drives
Motor
connection
Rectifier Transformer Sine filter
capacitor
ACS 1000i - Overview
Maximum re-use of ACS 1000 components
Extension of the existing ACS 1000 product family
MV AC
Induction
Motor
© ABB Switzerland Ltd. MV Drives
ACS 1000i – Topology and Main Data
Medium Voltage Input Input 24-Pulse DC-Link Inverter Output Sine
Supply Bus Isolator and Transformer Rectifier Filter
Contactor
MV AC
Induction
Motor
MV AC
Induction
Motor
Main Feeder
Breaker
MV AC
Induction
Motor
Main Feeder
Breaker
MV AC
Induction
Motor
Main Feeder
Breaker
solution
different from
ACS1000
ACS 1000i – Cooling
transformer
Two independent cooling circuits cooling fan
inverter
Transformer cooling fan
Inverter
Two top mounted cooling fans
Ductable air outlet
12-pulse 24-pulse
Converter Input Converter Input
Transformer Transformer
Rectifier
Rectifier
+/- 10%
Ride through capabilities
I>> Prot
MV AC
Induction
Motor
© ABB Switzerland Ltd. MV Drives
In case aux. power does not return and drive has internal batteries, control will be switched off
after about 15 min.
Within the 5 sec limit and in case of a simultaneously fail of aux. and main power the drive will
be automatically accelerate again to reference speed 2 seconds after the (both) voltages have
returned.
Aux. power loss ride through
Note:
Increased risk for self excitation in case of aux. power loss without
simultaneous main power loss.
After the aux. ride through time is elapsed the inverter stops modulation
If the motor runs above the self excitation frequency, then during
coasting down the unavoidable consequence would be a major trip
(including MCB open).
8kW power for air cooled converters, 5kW for water cooled converters
Fuseless design
I>> Prot
MV AC
Induction
Motor
Inverter Motor
Side Side
© ABB Switzerland Ltd. MV Drives
Sine Wave
Filter
Standard
DC
AC Induction
Link
Motor
© ABB Switzerland Ltd. MV Drives
Legend
_ _ _
Negative Current:
+ + +
© ABB Switzerland Ltd. MV Drives
_ _ _
3-Level Inverter Output Voltage
Features Benefits
Fast switching (up to 20kHz) High Performance
Low switching and on-state High Efficiency
losses
Snubberless Low Parts Count
Integrated gate driver & free Low Parts Count and High
wheeling diode (ACS 1000) Reliability
© ABB Switzerland Ltd. MV Drives
Routine Testing
Rigorous 7 hour, 4 step
testing program
Including 3 hour load test
Reduces on-site
commissioning time
Test Sequence
1.
High Voltage
Insulation Test
0.5 h
2.
Testing of
Controls
1.0 h
3.
© ABB Switzerland Ltd. MV Drives
Testing of
Power Part
2.5 h
4.
a) Motor Load Test
b) Full Current Test
3.0 h
Local Control Panel
Intelligent Control Panel
CDP 312 R
Language: English
Control
Customer I/Os
IOEC-Board 2 for remote control & main feeder breaker
control
© ABB Switzerland Ltd. MV Drives
Yes
State machine controls the start-
No
up procedure MCB On
?
Udc < 50V
?
Direct start
Similar to encoderless flying start, but
No frequency search (part of state machine skipped)
Magnetization of motor is done at settable frequency
Flying start with encoder
similar to direct start, but
Magnetization of motor is done at measured frequency
© ABB Switzerland Ltd. MV Drives
Motor Protection
Motor Over- and Under-Load Protection
Supervision of motor current within a free programable range
IIdealMot
A
Par.: 42.26
Current Level P9 P9
P8
9 current points (P1 ... P9)
Par.: 42.18 ... 42.26
P7
P5
Par.: 42.18 P2
Current Level P1 P1
Underload Trip Current
Par.: 42.17
LoadProtStartCurr
Par.: 5.08 Ideal Motor Current (calcutated)
Par.: 42.07
LoadProtStartFreq
Motor Protection
Phase Unbalance Protection
Supervision of all three motor phase currents
IMotPhase Par.: 1.18 MotCurrent Phase U
A
(RMS)
Standards
Applicable standards
Declaration of EU conformity
UL and cUL Certifications
For public information, go to:
http://database.ul.com/cgi-
bin/XYV/template/LISEXT/1FRAME/index.htm
Enter „ACS 1000“ as key words
ISO 9001:2000, ISO 14001:20004, OHSAS 18001:1999
© ABB Switzerland Ltd. MV Drives
Additional features
Programable Customized Supervision Functions
Possibility to process customer I/Os arithmetically and logically
“Programed“ by parameter settings
Backspin Lockout
Protect the motor from restart within a selectable time
n Pump
rpm Stop
Command Stopped
Par.: 21.12
Backspin Lockout Time
Start inhibited
© ABB Switzerland Ltd. MV Drives
0 t s
Motor Side
Increased output frequency 82.5Hz*
Ex-Zone signal interface
Motor cooling pump/fan control
Speed feedback
Motor space heater control
Converter Cooling
Redundant cooling fan*
Redundant cooling pump*
Glycol cooling
© ABB Switzerland Ltd. MV Drives
Drive Windows*
Displaying system
configuration
Monitoring actual signal
values
Viewing and changing
parameters
Fault logger
Event logger
Data logger for fast and
accurate measurements
Drives control
© ABB Switzerland Ltd. MV Drives
FWP Fmax
F [Hz]
=100%
© ABB Switzerland Ltd. MV Drives
Operation HMI
level HMI
System Bus
Control
level
PROFIBUS-DP PROFIBUS-PA
© ABB Switzerland Ltd. MV Drives
Device
level
Fieldbus Interfaces
Fieldbus Interfaces with ABB Drives
Supported fieldbusses
Profibus
Modbus
ModbusPlus
DeviceNet
Ethernet
AF100
- AC70, AC80, AC800 PLC functions
© ABB Switzerland Ltd. MV Drives
I>> Prot
Common MV AC
Mode Choke
Induction
Motor
If cables are longer than following limits, then please contact PRU:
200 m for ACS 1000, 12-pulse and
150 m for ACS 1000, 24-pulse.
Common Mode Choke
Common Modes inside the Drive System
I_Cf uvw _G
A
35
30
25
20
15
10
-15
-5
-25
0 5 10 15 20 25 30
ms
In ACS 1000 they are directed back to the transformer, but kept away
completely from the motor.
Redundant Cooling Fan
M
Output 3-Ph
Isolator
Squirrel Cage
Induction Motor
Application Control and
Converter Direct Torque Control (DTC)
Transformer
12-pulse Output
© ABB Switzerland Ltd. MV Drives
Rectifier Filter
Note: the output isolator has to be a load disconnector for breaking the
current flow between motor / network and sine filter
Synchronized Bypass Control
Single Line Diagram of a Starting
System for 2 .. 4 Motors
Not included
To be part of the drive system:
All bypass breakers and output disconnectors
© ABB Switzerland Ltd. MV Drives
Motor protection (only the motor in VSD operation is protected by drive controls)
Overriding controls for coordination of the different motors
Braking Chopper
Electrical
Diagram:
© ABB Switzerland Ltd. MV Drives
Braking Chopper
Mechanical
Layout:
644 mm wide
cabinet, installed
© ABB Switzerland Ltd. MV Drives
Features:
For use with an external braking resistor (max. cable length 50 m
between chopper and resistor)
“One size fits all”
Always air cooled with natural convection
Main Data:
Max. braking power is 2.5 MW or 60% of rated drive power,
whatever is more stringent
© ABB Switzerland Ltd. MV Drives
Considerations:
Usually mounted outdoors, using natural convection
Relevant for basic dimensioning (and pricing):
- max. braking power
- max. braking energy per time interval
- max. voltage
For specification of the resistance value please contact the PRU in
Turgi
© ABB Switzerland Ltd. MV Drives
Floating Ground
Option Floating Ground is designed to run the motor under ground
fault (single fault)
Always an ”engineered option” (case specific dimensioning
required)
© ABB Switzerland Ltd. MV Drives
Rst Cst
ACS 1000 Water Cooling Engineered Options
Special Water Cooling Options
Flange connections
(instead of standard hose connectors)
ANSI flange 2’’ / B16.5 / 150 lbs or
DN 50 / PN16
Flange orientation to top, bottom or side
Manual shut-off valves on request
2’’ ANSI flange also for drain connection
available
© ABB Switzerland Ltd. MV Drives
ACS 1000 Water Cooling Engineered Options
Special Water Cooling Systems
higher cooling water temperatures up to 45°C
one loop cooling system
chiller cooled drive cabinet
IP42 ventilated drive cabinet
closed cooling system design
recommended if glycol shall be added
preferred for one loop systems
Packages
fin / fan cooler packages
for demineralised water cooling circuit (one loop system)
© ABB Switzerland Ltd. MV Drives
by
fin/fan cooler,
analog
chillers or
others
Advantages:
M
Separation between internal demineralised
water and external raw water circuit
Lowest WCU costs on ACS1000 side
Power losses Air A/W HEX
© ABB Switzerland Ltd. MV Drives
ACS 1000 Water Cooling Engineered Options
ACS1000-W One-loop system < 38°C water temp.
Heater*
Filter
Q P T *Heater needed if
closed analog analog analog
Watercan be below
5°C during Standby
system Customer
side
Power losses water W/W HEX,
fin/fan cooler
Advantages: or chiller
<38°C
No raw water pumps needed
No temperature
P control valve on raw water
M
side needed, i.e. minus temperatures possible
analog
No temperature
P
control valve on raw water
M
side needed, i.e. minus temperatures possible
analog
A/W HEX
Increased water temperatures up to 45°C Autonomous
possible no need for chiller,
Power losses Air P if max. ambient Digital
compact
chiller (7kW)
© ABB Switzerland Ltd. MV Drives
possible on request
Increased
P
water temperatures up to 45°C
M
analog
feasible up to 40°C max. ambient room Cooling Air from
control room
temperature (power derating above 35°C room
temperature)
Power losses Air
© ABB Switzerland Ltd. MV Drives
up to 7kW heat
losses into the
control room
ACS 1000 Options 3-Way Raw Water Control Valve
Note:
Retrofitting of this option
is not possible !
ACS 1000 Options 3-Way Raw Water Control Valve
ACS 1000(i)
Service and Support
24x365 Service Support
Service Level
3
© ABB Switzerland Ltd. MV Drives
Level 3
24x365 SupportLine
If also local efforts fail, a Support Center Experts of ACS1000 available in
operator can be called. A system specialist Turgi, Switzerland
will return the call in 30 minutes. - Emergency Spare Parts Deliveries out of
Logistic Center Helsinki / Finland