Headed Reinforcement
Corporation
ERICO Incorporation
HEADED
REINFORCEMENT ?
Plate Anchor
Rectangular/Round
Threaded/Friction Weld
Area = 5 to 10 Bar Area
Beam-Column Joints
Standard Hooks
Ease of Fabrication &
Placement
WHY HEADED REINFORCEMENT ?
Congestion/Fabrication/Placement
AVAILABLE INFORMATION
Anchorage/Beam-Column Joints
UCLA & Clarkson University
Wallace, McConnell, Gupta
Reports/ACI Papers (1994, 1997, 1998)
Also Yu (2001)
University of Texas, Austin
Jirsa, Devries, Bashandy
Ph.D. Dissertations (1996), ACI Paper (1999)
University of Kansas
McCabe, Wright, Wu (Reports, 1997)
PROJECT OVERVIEW
EXTERIOR ROOF
& CORNER JOINTS
EXTERIOR INTER-
STORY JOINTS
TEST SETUP
Exterior Roof Connections
36" CLEVIS
HEAVY LINK
RIGID REFERENCE
FRAME TIE DOWN REACTION WALL
STRONG FLOOR
SPECIMEN DETAILS
Exterior Roof Connections
BEAM CROSS SECTION COLUMN CROSS SECTION
#3 STIRRUP
(9.5 mm)
14.5" 14.5"
4
Drift Level (%)
-2
-4
BCEJ-1
-6
0 200 400 600 800
Counter Number
Specimen Damage
Exterior Roof Connections
KJ16 - Top Bar Pull-out
REINFORCING DETAILS
Exterior Roof Connections
Moment (kN-m)
500 50
0 0
-500 -50
6.0% -100
-1000
2.0%
Mn=1508 in-kips -150
-1500
(P=49.5 kips)
4.0% 3.0% -200
-2000
-250
Closing Knee Joint #17
-2500
-0.06 -0.04 -0.02 0.00 0.02 0.04 0.06
Specimen Rotation
MEASURED REBAR STRAINS
Beam Top Bars Within the Joint
6000
TB1-FACE
MICROSTRAIN
4000 TB1-MID
2000
0
1.0% 2.0% 4.0%
-2000
6000
TB2-FACE
MICROSTRAIN
4000 TB2-END
2000
0
1.0% 2.0% 4.0%
-2000
0 100 200 300 400 500
DATA POINT
TEST SETUP
Exterior Inter-Story Connections
12.75 ft (3.89 m)
10 ft
(3.05m)
SPECIMEN GEOMETRY
Exterior Inter-Story Connections
BEAM CROSS SECTION COLUMN CROSS SECTION
18" x 24" 18" x 18"
457 mm x 610 mm 457 mm x 457 mm
DESIGN REQUIREMENTS
Exterior Inter-Story Connections
Strong Column - Weak Beam (352-01)
M column / M beam 1.2 (1.7 Test)
Joint Confinement Reinforcement (352-01)
Ash = 0.3 shc ( Ag / Ach - 1) f c' / f y
Ash , provided / Ash ,req 'd = 1.17 (test)
Joint Shear Stress Limits (352-91)
fVn = ( 0.85 )(15 ) 4000 (psi) (18" )(18" ) = 260 kips
Vu = ( 4 x 0.79 in 2 )(1.25 )( 60 ksi ) - Vcolumn = 207 kips
Vu / f Vn = 0.80
DESIGN REQUIREMENTS
Exterior Inter-Story Connections
Anchorage Requirements
– Tension (318 Eq. 21-5, 352-91)
l dh = f y d b / 65 f c' (psi) = 925 d b / f c' (psi) = 14.6 d b
l provided / l dh = 13 d b / 14 .6d b = 0.9 (0.82 per 352)
– Compression (318 S12.3)
l db = 0.02 d b f y / f c' (psi) = 1200 d d / f c' (psi)
l d = (0.75) l db = 900 d d / f c' (psi) = 14 .23 d b
l provided / l d = 13/14.23 = 0.91
Beam End Rotation
Exterior Interstory Connections
BCEJ1 - Drift Level 6%
Potentiometer
Potentiometer
MOMENT-ROTATION
Exterior Inter-Story Connections
6000
3 beam bars in tension
4000
MOMENT (kip-in)
Mn= 2860
2000
4%
0
6%
-2000
Mn= 3760
-4000
4 beam bars in tension 2%
-6000
-0.06 -0.04 -0.02 0.00 0.02 0.04 0.06
JOINT ROTATION 24" FROM THE COLUMN FACE
Specimen Damage
Exterior Interstory Connections