Professional Documents
Culture Documents
150 Amp
C71
S2
R Ph O/C (51R)
0.75 Amp S1 C11
E/F (51N)
0.75 Amp S1 C31
0.0 Amp
B Ph O/C (51B)
0.75 Amp S1 C51
3
O/C E/F Relay & Time Coordination 1S1R
A11
1S2R
R Ph CT
Core-3 Core-2 Core-1
Yard MB Wiring 1S3R
1S1Y
A31
1S2Y
1S3Y
A51
1S1B
1S2B
A71
1S3B
2S1R
C11
2S2R
Y Ph CT 2S3R
Core-3 Core-2 Core-1
2S1Y
C31
2S2Y
2S3Y
C51
2S1B
2S2B
C71
2S3B
D71
3S1R
B Ph CT 3S2R
Core-3 Core-2 Core-1
3S3R
D11
3S1Y
3S2Y
3S3Y
D31
3S1B
3S2B
3S3B
D51
4
O/C E/F Relay & Time Coordination 1S1R
A11
1S2R
R Ph CT
Core-3 Core-2 Core-1
Yard MB Wiring 1S3R
1S1Y
A31
1S2Y
1S3Y
A51
1S1B
1S2B
A71
1S3B
2S1R
C11
2S2R
Y Ph CT 2S3R
Core-3 Core-2 Core-1
2S1Y
C31
2S2Y
2S3Y
C51
2S1B
2S2B
C71
2S3B
D71
3S1R
B Ph CT 3S2R
Core-3 Core-2 Core-1
3S3R
D11
3S1Y
3S2Y
3S3Y
D31
3S1B
3S2B
3S3B
D51
5
O/C E/F Relay & Time Coordination
Terminal Diagram of MiComP141
6
O/C E/F Relay & Time Coordination
Single Line to Ground Fault
200/1 Amp
1500 Amp
P1 P2
C71
S2
R Ph O/C (51R)
7.5 Amp S1 C11
E/F (51N)
S1 C31
7.5 Amp
B Ph O/C (51B)
S1 C51
7
O/C E/F Relay & Time Coordination
Electromagnetic Induction relays
50%
75%
100%
125%
150%
200%
Φ1 Φ2
8
O/C E/F Relay & Time Coordination
Relay Operation Time - 1
E/F PSM 30% i.e. 0.3 Amp
E/F Relay Current 7.5 Amp
E/F Relay Current is 7.5/0.3 = 25 Times
its operating current
From Graph for 25 Times relay operating
current for TMS = 0.15 relay time of
operation would be @ 0.35 Sec
General Steps
1) Decide PSM
2) Find out fault current
3) Find out multiple of relay set current as per decided PSM in step-1
4) Find out time of operation for above multiple of current and TMS=1 using
relay characteristic curve
5) Decide relay time of operation as per protection needs
6) Find out TMS = Required Time of operation /Time of operation with TMS =1
10
O/C E/F Relay & Time Coordination
Basic Information – Selection of PSM
E/F PSM generally selected as 30% ( Other than 30% settings may also be selected but about this
discussed somewhere else in the presentation)
For O/C PSM is selection depends upon place and purpose of use for example –
1.Transformer O/C protection
a) Transformer HV or LV side O/C relay PSM settings should be in commensuration with transformer
full load current and respective CT ratio such that PSM = T/F Full load current / CT ratio ( Generally
expressed in %)
b) For example for a 25 MVA transformer HV side full load current is 109 A if HV CT ratio is 200/1 Amp
then PSM =109/200 ≈ 55% ( exact value 54.5%)
c) For old type numerical relay it was not possible to go as near as possible to value calculated from
above formula due to large steps available
d) Under such condition it is decision as per local condition to select higher or lower nearest PSM
e) In above example it is customary to select 50%, however due to this selection there is apparent
loss of about 10% capacity of the T/F
f) It is also possible to select 75% but load on transformer is to be monitored carefully ( and manually
)
2.For 220-132 kV feeder
Here generally it is customary to select relay PSM as per-
a) Line conductor allowable loading limit
b) CT primary normal current
c) Substations capacity/normal load feed by the line
d) Considering above facts it is very common to select 100% PSM for 132kV lines with CT ratio 400/1
Amp
e) For 220kV lines with CT ratio 800/1 amp and conductor 0.4 ACSR or 0.525 AAAC it is 100%
a)For 33-11kV feeder
a) As per local feeder condition, load pattern and needs ranging between 50% to 100%
11
O/C E/F Relay & Time Coordination
Relay Operation Time - 3
100
10 Fuse
Trafo
1
0.1
0.01
0 500 1000 1500 2000 2500 3000
17
O/C E/F Relay & Time Coordination
Simplest Protection – Fuse
• These
characteristic
graphs are
generally double
log graph
• This is due to
including from very
small to very large
values on both axis
18
O/C E/F Relay & Time Coordination
Simplest Protection - Fuse
Long Time
Inverse
Trafo Damage
Curve
Extremely Inverse
Normal Inverse
28
O/C E/F Relay & Time Coordination
End of More Information
R3 R2 R1
A B C
S
R3 R2 R1
S
R3 R2 R1
X Y M
E
Z
A C