Type Code Labels and

FlashScan® Type
For All Onyx Panels including the NFS-320,
NFS2-640 and NFS2-3030
What is the Difference Between Type Code
Label, and FlashScan® Type?
What is the Difference Between Type Code
Label, and FlashScan® Type?

•Type Code Label defines what you wish to do with a device

•FlashScan® Type is determined by what type of device is being


used.
What is the Difference Between Type Code
Label, and FlashScan® Type?

•Example: FSP-851 photo-electric smoke detector

•It can be an alarm input, or a supervisory.

•If supervisory, it can be tracking or latching.

•This is all determined by the Type Code Label.

•Regardless of selection, the FlashScan® Type will be PHOTO.


Type Code Labels

Type Code Labels are software selections for:

 Initiating devices
 Detectors
 Monitor Modules

 Output devices
 Control Modules
 Relay Modules
 NACs
Type Code Labels for Detectors

• There are many types of Detectors


– Photo
– Ion
– Laser
– Heat (Fixed and Rate of Rise)
– Acclimate ® Plus™
– HARSH™ (Hostile ARea Smoke Head)
– IntelliQuad™ (Smoke, Heat, IR and CO)
Type Code Labels for Detectors

Possible uses for a PHOTO (FSP-851) detector


Type Code Point Type Latching Activate Device Function
(Y/N) s CBE
SMOKE (PHOTO) Fire Y Y Photoelectric smoke detector

SUP L(PHOTO) Supervisory Y Y Photoelectric smoke detector

SUP T(PHOTO) Supervisory N Y Photoelectric smoke detector

SMOKE (DUCTP) Fire Y Y Photoelectric smoke detector

SUP L(DUCTP) Supervisory Y Y Photoelectric smoke detector

SUP T(DUCTP) Supervisory N Y Photoelectric smoke detector

Other types of detectors would have similar options


Type Code Labels for Input Modules

After auto-programming….

…. Default Type Code Label is MONITOR


…. FlashScan ® Type is MONITOR or MINI/DUAL

The panel doesn’t know what is connected to it

It is up to YOU to tell it!


Type Code Labels for Input Modules

Here are some examples of Monitor Module Type Code Labels.

Type Code Point Type Latching Activates Device Function


(Y/N) CBE
MONITOR Fire alarm Y Y Alarm-monitoring device

PULL STATION Fire alarm Y Y Manual fire-alarm-activating device

WATERFLOW S Supervisory Y Y Indicates supervisory condition for activated


waterflow switch.
*Note that this type code label is only available for the NFS2-3030
FMM 4-20* User- Y Y Monitors 4-20 mA industrial sensors
** Some type code labels allow for system functions, such as Acknowledge, Silence, Reset and Drill.
programmable
RESET SWITCH** Non-alarm N N Performs reset function

*Note that this Type Code Label only applies to the NFS2-3030.

**Type Code Labels also allow for some system functions, such
as Acknowledge, Silence, Reset, and Drill
Type Code Labels for Output Modules

After auto-programming….

…. the panel will often set default values to CONTROL or RELAY


with the appropriate FlashScan ® Type.

Again, the panel doesn’t know what is connected to it.


It is up to YOU to tell it!
Type Code Labels for Output Modules

Examples of Output Types taken from the NFS2-3030 Programming Manual

Type Silenceable Switc Walk SLC Local Mode Device Function


Code h Test Output Group
Inhibit Point Point Types

CONTROL Y N Y NAC n/a Supervised NAC

RELAY Y N Y Relay n/a Relay output

STROBE Y N Y NAC Fire Supervised NAC


CKT

SPEAKER Y N Y NAC Fire Supervised NAC for speaker circuits


*Note that this type code label is only available for the NFS2-3030
** Some type code labels allow for system functions, such as Acknowledge, Silence, Reset and Drill.
REL Y Y N NAC n/a Activates audio or visual devices steady
AUDIBLE when releasing starts.
Programming Examples
NFS2-3030 Point Programming

This is the Type This is the FlashScan®


Code Label Type
NFS2-640/NFS-320 Point Programming

This is the Type


Code Label

Note that the FlashScan ® Type cannot be


changed at the panel with the NFS2-640 or NFS-
320.
VeriFire™ Tools Selection
This is the Type This is the FlashScan®
Code Label Type

Note that this is the Point Programming screen for


the NFS2-3030. The NFS2-640 and NFS-320 screens
look different, but the selection process is the same.
FlashScan® Type

• When the panel is auto-programmed, the appropriate


selection will be made.

• Most of the time, this is sufficient.

• However, there are a few instances to watch out for.


FlashScan® Type Issue #1

• FlashScan® Type for the FDM-1, FMM-101, and XP-10M


monitor modules is MINI/DUAL.

• If Type Code Label is changed using VeriFire Tools (i.e.


WATERFLOW), it reverts to the generic FlashScan® Type of
MONITOR.

• This will result in an Invalid Reply trouble for the device.

• It must be set to Mini/Dual prior to downloading.


FlashScan® Type Issue #1

Screen as it would appear after initial auto-program.


Note that default values are set.
FlashScan® Type Issue #1

Change type Code


Label to something
else, like H20 flow.
FlashScan® Type Issue #1

Note what happens


to the FlashScan®
Type selection.

This would have to set back to the MINI/DUAL selection to function properly.
FlashScan® Type Issue #2

• For certain releasing Type Code Labels, the


FlashScan® Type is automatically set to RELEASE.

• Recall that the FlashScan® Type is set by the


hardware, not the application.

• Results in an Invalid Reply trouble

• RELEASE FlashScan® Type is only for the FCM-1 REL


module

• Only applies to VeriFire™ Tools programming


FlashScan® Type Issue #2

This Type Code Label is


used for a relay used to
perform a releasing
function

Since it is an FRM-1 Relay


Module, this is the incorrect
FlashScan® Type.
FlashScan® Type Issue #2

This Type Code Label is


used for a relay used to
perform a releasing
function

The correct FlashScan®


Type is RELAY
Blah,Blah,Blah,
Blah,Blah,Blah. What was
he talking
about ?
Zzzz
zzzz
zz
Questions,
Comments, ?
Ideas