You are on page 1of 89

2

ProInert®
Equipment Section
System Equipment
Section
Argon Nitrogen

ProInert is made up of
blends of Inert Gases
that occur naturally in
the atmosphere

Carbon
Dioxide
Fike’s ProInert Inert Agents
IG-55 IG-541
52% Nitrogen (N2)
50% Nitrogen (N2)
40 % Argon (Ar)
50% Argon (Ar)
8% Carbon Dioxide (CO2)
Globally Accepted
NFPA 2001 & ISO 140520
Safe for People
ProInert is safe for 80
use in occupied 70
spaces at 60 Argon
concentrations up to 50 Nitrogen
52%. 40 Oxygen
30 CO2
20
A ProInert discharge 10
simply alters the ratio 0
of Nitrogen, Argon & 0 .1 % 78 % 21 % 0.3 %
CO2 vs. Oxygen.
The Air we Breathe
Safe for People
Typical 42% Design 70
Concentration results 60
in an Oxygen level 50 Argon
suitable for Occupied 40 Nitrogen
Spaces 30 Oxygen
(Ref. NFPA 2001) CO2
20
10
0
17 % 70 % 12.5 % 0.3 %

The Air After a Typical IG-55 Discharge


Safe for People
Typical Design 70
Concentrations result 60
in an Oxygen level 50 Argon
suitable for Occupied 40 Nitrogen
Spaces 30 Oxygen
(Ref. NFPA 2001) CO2
20
10
0
16 % 70 % 12.5 % 1.5 %

The Air After a Typical IG-541 Discharge


Inert Gas Features and benefits:
• Natural gas present in the atmosphere
• Suitable for occupied areas
• No toxic or corrosive decomposition products from agent
• Colorless, odorless, compressed gas
• Fogging does not occur when agent is discharged
• Electrically non‐conductive
• No residue to clean up after discharge
• Zero ozone depleting potential
• Zero global warming potential
• Listing and Approvals: UL / ULC Listed & FM Approved
Inert Gas Applications and uses:
• Class A: Non-Energized surface
fires (wood, paper, plastic)
• Class C: Energized Electrical
Hazards (Telecommunications
Facilities, computer rooms and
other high value assets, where
down‐time associated with
sprinkler systems would be too
costly)
Inert Gas Applications and uses:

• Class B: Chemical
Storage/Processes, Labs, etc.
(Consult Fike for specific
Design Concentration
requirements)
Inert Gas Application limitations:
Per NFPA 2001, Clean Agent systems shall “NOT” be used on fires
involving the following materials:
• Chemicals or mixtures of chemicals that are capable of rapid
oxidation in the absence of air.
(Examples include: Cellulose Nitrate and Gunpowder)
• Reactive metals such as Lithium, Sodium, Potassium, Magnesium,
Titanium, Zirconium, Uranium, and Plutonium
• Metal hydrides such as Sodium Hydride and Lithium Aluminum
Hydride
• Chemicals capable of undergoing auto‐thermal decomposition.
(Examples: Organic Peroxides and Hydrazine)
Inert Gas Typical Design Concentration / Oxygen Levels

Design Concentration / Oxygen Maximum Human Exposure


Hazard Type
Levels Time
Up to 43% / 12% Min. 5 minutes
Normally Occupied Spaces
43% to 52% / 12% to 10% 3 minutes
52% to 62% / minimum 8% 30 seconds
Normally Un-Occupied Spaces
Above 62% / 8% or lower No permitted exposure

Ref. NFPA 2001, Table A.1.5.1.3(a)

Inert Gases should not be used in Occupied spaces at


concentrations greater than 52%
IG-55 / IG-541 is stored as a compressed gas
blend in high pressure cylinders
How is IG-55/IG-541 made?
Watch this short video!
https://www.youtube.com/watch?v=ImDhFK2A1cQ
Cylinders available in 200 or 300 bar charging capacity.

Cylinder Dimensions Mounting


Cylinder Size
Height in. (mm) Width in. (mm) Position

80 Liter (water
69” (1753) 11-1/4” (286) Upright
capacity)

200 bar and 300 bar utilize the same cylinder


body and valve.
Cylinders available in 200 or 300 bar charging capacity.

Cylinder Specifications
IG-55 IG-541
IG71-103-200-55 (200 bar) IG71-103-200-541 (200 bar)
Cylinder Part Number
IG71-103-300-55 (300 bar) IG71-103-300-541 (300 bar)

Cylinder Pressurization 2,900 psi @ 60°F (200 bar @ 15°C)


Level 4,351 psi @ 60°F (300 bar @ 15°C)
572.3 ft3 (16.2 m3) @ 200 bar 598.5 ft3 (16.9 m3) @ 200 bar
Cylinder Agent Capacity
823 ft3 (23.3 m3) @ 300 bar 856.4 ft3 (24.3 m3) @ 300 bar
Cylinder Storage
Temperature -4°F to 120°F (-20°C to 49°C)
Limitations
Cylinders available in 200 or 300 bar charging capacity.

Cylinder Specifications

Cylinder Color Signal Red

Cylinder Tare Weight 250 lbs. (113.4 Kg) Approx.

300 lbs. (136 Kg) Approx. @ 200 bar


Cylinder Gross Weight
IG-55
321 lbs. (145.6 Kg) Approx. @ 300 bar

Cylinder Gross Weight 301 lbs. (136.5 Kg) Approx. @ 200 bar
IG-541 324 lbs. (146.9 Kg) Approx. @ 300 bar
Cylinders available in 200 or 300 bar charging capacity.

Cylinder Specifications

Int’l Recognized (Based on TPED)

Cylinder Rating TC-3AAM (Transport Canada)

EN ISO 9809-2 & TPED 1999/36/EC

Listings & Approvals UL / ULC / Factory Mutual


Items furnished with 200 bar and 300 bar Cylinders.
Shipping Cap
Self-Regulating Valve

Cylinder I.D. Label

Each ProInert Cylinder is equipped with:


• 200 bar or 300 bar valve with appropriate
gauge or gauge/switch combination
• Shipping Cap
• Cylinder I.D. Label
Items furnished with 200 bar and 300 bar Cylinders.

Shipping Cap

• Each ProInert Cylinder is fitted with a


safety/shipping cap
• Cap to be retained for future use.
• Shipping Cap required on cylinder at
all times during shipping, handling &
installation!
• Replacement Cap: P/N: 02-4829
Items furnished with 200 bar and 300 bar Cylinders.

Each ProInert Cylinder label indicates:


• Assembly No.
• Charge Pressure (200 or 300 bar)
• Tare, Gross & Agent Weight
• Year Manufactured
Cylinders Fitted with Brass Valve

• The Fike ProInert Cylinder is


equipped with a pressure-
regulating outlet valve
designed to provide a
constant outlet pressure of
645 psi (44.5 bar) with a free
flow area of 12mm diameter.
Cylinders Fitted with Brass Valve

• Each valve is equipped with a


combination pressure gauge and
low pressure switch on the
Primary cylinder(s) and pressure
gauge only on the Secondary
cylinders, providing visual
pressure monitoring, as well as
continuous cylinder pressure
monitoring at the control panel.
Cylinder Completer Kits
Must be purchased separately.
Each System Cylinder MUST have one of
the following Completer Kits:

• Primary-Electric (PE)

• Primary Pneumatic (PP)

• Secondary Pneumatic (SP)


Primary-Electric Cylinders (PE)
UVO Primary-Electric refers to cylinder
operated by Universal Valve Operator
(UVO):
• “Primary” or “First” cylinder in
cylinder bank
• Requires a Universal Valve Operator
• Can be electrically (automatically)
operated via UVO connection to
control panel
• Can be manually operated by
manual button on UVO
Secondary-Pneumatic Cylinders (SP)

Pneumatic Secondary-Pneumatic refers


Actuator
to cylinder(s) operated by
Pneumatic Actuator:
• Utilizes Pneumatic Actuator
for pneumatic operation
• All Non-Primary cylinders
are Secondary-Pneumatic
cylinders
Primary-Pneumatic Cylinders (PP)
Relay Actuator
Primary-Pneumatic refers to
cylinder(s) operated by Relay
Actuator:
• Utilizes Relay Actuator for
pneumatic operation
• Used on large systems with
cylinder banks exceeding 60
cylinders
Cylinder Completer Kits
Completer Kits include the following
items:
• Appropriate Gauge or Gauge with
Low Pressure Switch
• Discharge Hose Kit
• Universal Valve Operator (UVO) or
• Relay Actuator Assembly or
• Pneumatic Actuator Assembly
• Appropriate Actuation Hose
Completer Kits for IG-55 Primary Cylinders with
Electric/Manual Operation (PE) on NPT Pipe Network
Completer Kits: IG71-236-200-55-PE (200 bar)
IG71-236-300-55-PE (300 bar)
Part Number Description
02-13131 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14066 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-123 Discharge Hose Assembly with NPT Check Valve
02-13571 Universal Valve Operator (UVO)
02-13713 Actuator Hose
02-14627 UVO Supervisor
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-55 Secondary Cylinders with
Pneumatic Operation (SP) on NPT Pipe Network
Completer Kits: IG71-236-200-55-SP (200 bar)
IG71-236-300-55-SP (300 bar)
Part Number Description
02-13441 Pressure Gauge for 200 bar
or
02-13541 Pressure Gauge for 300 bar
IG71-123 Discharge Hose Assembly with NPT Check Valve
IG71-104 Pneumatic Actuator Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-55 Primary Cylinders with
Pneumatic Operation (PP) on NPT Pipe Network
Completer Kits: IG71-236-200-55-PP (200 bar)
IG71-236-300-55-PP (300 bar)
Part Number Description
02-13131 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14066 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-123 Discharge Hose Assembly with NPT Check Valve
IG71-220 Pneumatic Relay Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-55 Secondary Cylinders with
Pneumatic Operation & LPS (SPL) on NPT Pipe Network
Completer Kits: IG71-236-200-55-SPL (200 bar)
IG71-236-300-55-SPL (300 bar)
Part Number Description
02-13131 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14066 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-123 Discharge Hose Assembly with NPT Check Valve
IG71-104 Pneumatic Actuator Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-541 Primary Cylinders with
Electric/Manual Operation (PE) on NPT Pipe Network
Completer Kits: IG71-236-200-541-PE (200 bar)
IG71-236-300-541-PE (300 bar)
Part Number Description
02-14013 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14014 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-123 Discharge Hose Assembly with NPT Check Valve
02-13571 Universal Valve Operator (UVO)
02-13713 Actuator Hose
02-14627 UVO Supervisor
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-541 Secondary Cylinders with
Pneumatic Operation (SP) on NPT Pipe Network
Completer Kits: IG71-236-200-541-SP (200 bar)
IG71-236-300-541-SP (300 bar)
Part Number Description
02-13662 Pressure Gauge for 200 bar
or
02-13663 Pressure Gauge for 300 bar
IG71-123 Discharge Hose Assembly with NPT Check Valve
IG71-104 Pneumatic Actuator Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-541 Primary Cylinders with
Pneumatic Operation (PP) on NPT Pipe Network
Completer Kits: IG71-236-200-541-PP (200 bar)
IG71-236-300-541-PP (300 bar)
Part Number Description
02-14013 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14014 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-123 Discharge Hose Assembly with NPT Check Valve
IG71-220 Pneumatic Relay Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-541 Secondary Cylinders with
Pneumatic Operation & LPS (SPL) on NPT Pipe Network
Completer Kits: IG71-236-200-541-SPL (200 bar)
IG71-236-300-541-SPL (300 bar)
Part Number Description
02-14013 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14014 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-123 Discharge Hose Assembly with NPT Check Valve
IG71-104 Pneumatic Actuator Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-55 Primary Cylinders with
Electric/Manual Operation (PE) on BSP Pipe Network
Completer Kits: IG71-112-200-55-PE (200 bar)
IG71-112-300-55-PE (300 bar)
Part Number Description
02-13131 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14066 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-003 Discharge Hose Assembly with BSP Check Valve
02-13571 Universal Valve Operator (UVO)
02-13713 Actuator Hose
02-14627 UVO Supervisor
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-55 Secondary Cylinders with
Pneumatic Operation (SP) on BSP Pipe Network
Completer Kits: IG71-112-200-55-SP (200 bar)
IG71-112-300-55-SP (300 bar)
Part Number Description
02-13441 Pressure Gauge for 200 bar
or
02-13541 Pressure Gauge for 300 bar
IG71-003 Discharge Hose Assembly with BSP Check Valve
IG71-104 Pneumatic Actuator Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-55 Primary Cylinders with
Pneumatic Operation (PP) on BSP Pipe Network
Completer Kits: IG71-112-200-55-PP (200 bar)
IG71-112-300-55-PP (300 bar)
Part Number Description
02-13131 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14066 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-003 Discharge Hose Assembly with BSP Check Valve
IG71-220 Pneumatic Relay Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-55 Secondary Cylinders with
Pneumatic Operation & LPS (SPL) on BSP Pipe Network
Completer Kits: IG71-112-200-55-SPL (200 bar)
IG71-112-300-55-SPL (300 bar)
Part Number Description
02-13131 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14066 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-003 Discharge Hose Assembly with BSP Check Valve
IG71-104 Pneumatic Actuator Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-541 Primary Cylinders with
Electric/Manual Operation (PE) on BSP Pipe Network
Completer Kits: IG71-112-200-541-PE (200 bar)
IG71-112-300-541-PE (300 bar)
Part Number Description
02-14013 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14014 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-003 Discharge Hose Assembly with BSP Check Valve
02-13571 Universal Valve Operator (UVO)
02-13713 Actuator Hose
02-14627 UVO Supervisor
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-541 Secondary Cylinders with
Pneumatic Operation (SP) on BSP Pipe Network
Completer Kits: IG71-112-200-541-SP (200 bar)
IG71-112-300-541-SP (300 bar)
Part Number Description
02-13662 Pressure Gauge for 200 bar
or
02-13663 Pressure Gauge for 300 bar
IG71-003 Discharge Hose Assembly with BSP Check Valve
IG71-104 Pneumatic Actuator Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-541 Primary Cylinders with
Pneumatic Operation (PP) on BSP Pipe Network
Completer Kits: IG71-112-200-541-PP (200 bar)
IG71-112-300-541-PP (300 bar)
Part Number Description
02-14013 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14014 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-003 Discharge Hose Assembly with BSP Check Valve
IG71-220 Pneumatic Relay Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Completer Kits for IG-541 Secondary Cylinders with
Pneumatic Operation & LPS (SPL) on BSP Pipe Network
Completer Kits: IG71-112-200-541-SPL (200 bar)
IG71-112-300-541-SPL (300 bar)
Part Number Description
02-14013 Pressure Gauge w/ Low Pressure Switch for 200 bar
or
02-14014 Pressure Gauge w/ Low Pressure Switch for 300 bar
IG71-003 Discharge Hose Assembly with BSP Check Valve
IG71-104 Pneumatic Actuator Assembly w/ Actuation Hose
02-14802 Molykote 111 O-Ring Lubricant
Pressure Gauge with Low Pressure Switch
(Primary Cylinders)
• All “Primary” Cylinders are fitted
with a Pressure Gauge and Low
Pressure Switch Assy.
• Gauges are field removable and
can be replaced if necessary.
• Low Pressure Switch to be
monitored by control panel as a
“Supervisory” input.
Pressure Gauge with Low Pressure
Switch (Primary Cylinders)
Pressure Gauge Specifications
IG-55 IG-541
02-13131 (200 bar) 02-14013 (200 bar)
Assy. Part No.
02-14066 (300 bar) 02-14014 (300 bar)
2,434 psi / 168 bar 2,335 psi / 169 bar
decreasing (200 bar) decreasing (200 bar)
Pressure Setting
3,395 psi / 234 bar 3,480 psi / 240 bar
decreasing (300 bar) decreasing (300 bar)
Body Material Stainless Steel Body w/ Brass Pressure Connection
Pressure Connection M10 x 1
Pressure Gauge with Low Pressure
Switch (Primary Cylinders)
Pressure Gauge Specifications (Continued)
IG-55 IG-541
02-13131 (200 bar) 02-14013 (200 bar)
Assy. Part No.
02-14066 (300 bar) 02-14014 (300 bar)
Temperature Limits -4°F to +120°F (-20°C to +49°C)
Contact Ratings Single Pole. 4.5 to 24VDC/VAC, 5 to 100 mA; 3W
Wire Leads (2) 18 gauge x 8.5” (0.21 M) long
Listings & Approvals UL / ULC/ Factory Mutual
Pressure Gauge only
(Secondary Cylinders)

• All “Secondary” Cylinders are


fitted with a Pressure Gauge
Assembly.
• Gauges are field removable and
can be replaced if necessary.
Pressure Gauge (Secondary Cylinders)

Pressure Gauge Specifications


IG-55 IG-541
02-13441 (200 bar) 02-13662 (200 bar)
Assy. Part No.
02-13541 (300 bar) 02-13663 (300 bar)
Temperature Limits -4°F to +120°F (-20°C to +49°C)
Pressure Connection M10 x 1
Body Material Stainless Steel Body w/ Brass Pressure Connection
Listings & Approvals UL / ULC / Factory Mutual
IG71-123, NPT Discharge Hose Kit
• Includes Discharge Hose & Check Valve
• Same Kit used on 200 bar and 300 bar

Discharge Hose Specifications


Part No. 02-10721
Pressure Rating 5,076 psi (350 bar)

G⅝ - ISO 228-1 (Female Connector w/


Thread Type Swivel Fitting)
R⅝ - ISO7-1 (Male Connector)

Overall Length 20-1/2” (520mm)

Min. Bend Radius 9.8” (250mm)


IG71-123, NPT Discharge Hose Kit
• Check Valve required to make connection to
NPT pipe network

Check Valve Specifications


Part No. IG71-124
Pressure Rating 5,308 psi (366 bar)
RC⅝” - ISO7-1 (Female)
Thread Type
1” NPT Male
Overall Length 2.35” (66mm)
IG71-003, BSP Discharge Hose Kit
• Includes Discharge Hose & Check Valve
• Same Kit used on 200 bar and 300 bar

Discharge Hose Specifications


Part No. 02-10721
Pressure Rating 5,076 psi (350 bar)

G⅝ - ISO 228-1 (Female Connector w/


Thread Type Swivel Fitting)
R⅝ - ISO7-1 (Male Connector)

Overall Length 20-1/2” (520mm)

Min. Bend Radius 9.8” (250mm)


IG71-003, BSP Discharge Hose Kit
• Check Valve required to make connection to
BSP pipe network

Check Valve Specifications


Part No. IG71-008
Pressure Rating 5,308 psi (366 bar)
RC⅝” - ISO7-1 (Female)
Thread Type
1” BSP Male
Overall Length 2.35” (66mm)
70-315, Universal Valve Operator Kit (UVO)
• At least 1 Cylinder must be designated as
“Primary” Electric and will require a UVO
Universal Valve Operator (UVO)
Universal Valve Operator Kit: 70-315
Item No. Part Number Description
1 02-13571 Universal Valve Operator (UVO)
2 02-13713 Actuation Hose
3 02-14627 Universal Valve Operator Supervisor
Universal Valve Operator (UVO)
Universal Valve Operator Kit Specs
Supply Voltage 24VDC
Alarm max: 912 mA
SHP Pro
Supervision max: 33.4 mA
Current Consumption
Alarm max: 930 mA
Cheetah Xi / Xi 50
Supervision max: 25.4 mA
Material Stainless Steel body / Brass end-cap
Temperature Range -4°F to 120°F (-20°C to 49°C)
Listings and Approvals UL / ULC / Factory Mutual
UVO Supervisor
• Meets current NFPA 2001 requirements (4.3.4.1)
• Provided with each UVO Kit (Replaces the “U” clip
used to secure the UVO to the discharge valve)
• Provides supervision of the physical connection of
the UVO
UVO Supervisor
Universal Valve Supervisor Specs
Part No. 02-14627
.25” I.D. SST Flexible Conduit 34.75” long with 3/8”
Conduit
Electrical Connection
Wire Leads 44” long, 22 gauge
Temperature Range 32°F to 130°F (0°C to 55°C)
Listings and Approvals UL / ULC / Factory Mutual
IG71-220, Relay Actuator Assembly
• Used in conjunction with UVO on cylinder banks
in excess of 60 cylinders to activate the Primary
Pneumatic cylinder(s)

Relay Actuator Assembly


IG71-220, Relay Actuator Assembly
Relay Actuator Assembly includes:
Part Number Description
IG71-120 Relay Actuator
02-13713 Actuation Hose (not shown)
Relay Actuator
Relay Actuator Specs
Body Material Brass
Temperature Range -4°F to 120°F (-20°C to 49°C)
Listings and Approvals UL / ULC / Factory Mutual

IG71-0166, Reset Tool IG71-220, Relay Actuator

• Utilize IG71-0166, Reset Tool to insure Relay


Actuator has been properly reset prior to
installation!!
IG71-104, Pneumatic Actuator Assembly
• Used in conjunction with UVO on cylinder banks
with more than 1 cylinder
• Utilizes pneumatic pressure via UVO or Relay
Actuator to operate subsequent cylinders
IG71-104, Pneumatic Actuator Assembly

Pneumatic Actuator Assembly includes:


Part Number Description
IG71-203 Pneumatic Actuator
02-13713 Actuation Hose
Pneumatic Actuator Assembly
Pneumatic Actuator Specs
Pressure Rating 4,400 psi (310 Bar)
Hose Length 22” (559 mm)
Minimum Bend Radius 1.6” (40 mm)
Listings and Approvals UL / ULC / Factory Mutual

IG71-0166, Reset Tool IG71-104, Pneumatic Actuator

• Utilize IG71-0166, Reset Tool to insure Pneumatic


Actuator has been properly reset prior to installation.
Discharge Nozzle Assembly
• Brass Nozzle Body with Factory drilled Nozzle Orifice Plate
as determined by system flow calculations
• Only UL Authorized Drill Stations may drill custom Orifice
Plate and assemble nozzle assembly

Cir-Clip

Nozzle Orifice Plate

Nozzle Body
Discharge Nozzle Assembly
Size Style Part Number • Available in ½” thru 2”
360° IG71-072 NPT sizes
1/2”
180° IG71-209 • 180° & 360° Styles
360° IG71-073
3/4 “
180° IG71-210
360° IG71-074
1”
180° IG71-211
360° IG71-215
1-1/4”
180° IG71-216
360° IG71-075
1-1/2”
180° IG71-212
360° IG71-214
2”
180° IG71-213
IG71-076, Manifold Safety Disc
• Used on closed manifolds to prevent entrapment of
high pressure from accidental release (used behind
check valves & selector valves)
Manifold Safety Disc Specs

1,275, - 1,475 psi


Burst Pressure
(88 – 102 bar)

Material Brass Body / Nickel Disc

Thread Size 1/2” NPT

Listings and Approvals UL / ULC / Factory Mutual


IG71-202, Discharge Pressure Switch
• Used to transmit a positive pressure signal to the control
panel upon agent release
• Reset by pushing plunger back in

Discharge Pressure Switch Specs


Operating Pressure 100 psi (690 kPa) Min.
Switch double-pole, single-throw
Electrical Rating 1/2” NPT
1/4” NPT Female (pneumatic
Connection connection)
1/4” NPT (Conduit inlet)
Listings and Approvals UL / ULC / Factory Mutual
IG71-240, Odorizer
• Injects a small amount of Wintergreen scent into the agent
as it is being discharged
• This is an optional item on most systems

Odorizer Specs
Odorizer Part Number IG71-240
Rebuild Kit Part Number IG71-241
Thread size 3/4” NPT
Material Brass Body
Listings and Approvals UL / ULC / Factory Mutual
Cylinder Mounting Hardware
• Composed of Unistrut, threaded rod and special
clamps
• Available in multiple single, double and triple row
configurations
Front Support

Rear Support

Double-Row Clamp Rod


Configuration
shown
Single Row & Double Row Cylinder Racks
Cylinder Arrangement
Rack Assembly (Cylinder Quantity per row) Total Cylinder
Part Number Back Middle Front Quantity
Row Row Row
IG71-081-001 1 1
IG71-081-002 2 2
IG71-081-003 3 3
IG71-081-004 4 4
IG71-081-005 5 5
IG71-082-001 1 1 2
IG71-082-002 2 2 4
IG71-082-003 3 3 6
IG71-082-004 4 4 8
IG71-082-005 5 5 10
Triple Row and Variable Cylinder Racks
Cylinder Arrangement
Rack Assembly (Cylinder Quantity per row) Total Cylinder
Part Number Back Middle Front Quantity
Row Row Row
IG71-083-001 2 2 2 6
IG71-083-002 3 3 3 9
IG71-083-003 4 4 4 12
IG71-083-004 5 5 5 15
IG71-084-001 4 3 7
IG71-084-002 5 4 9
IG71-085-001 4 4 3 11
IG71-085-002 5 5 3 13
IG71-085-003 5 5 4 14
Aerial View - Cylinder Rack Configurations
Manifold Bracket Hardware

• Manifold support brackets used in


pairs to support heavy manifold
pipe.
• Available in single, double and
triple row deep configurations
• Can span 1 – 5 containers wide per
row
• Floor Mounting hardware also
available
Manifold Brackets
02-11883, Single Row Manifold Bracket
(1 Row Deep)

02-11884, Double Row Manifold Bracket


(2 Rows Deep)

02-11885, Triple Row Manifold Bracket


(3 Rows Deep)
Manifold Floor Mount Support Hardware
Bracket
Floor Mount Bracket included with Additional Hardware
Support Part Support Included
Number
Qty. Part Number Post Base Tee Plate
Tee Plate
IG71-065-1 1 02-11883 1 2

IG71-065-2 1 02-11884 1 2

IG71-065-3 1 02-11885 1 2
Tee Plate

Post Base
Selector Valve Assembly
• Provides a means of diverting agent discharge into a
designated zone
• Allows a cylinder bank to be used to protect one of
several hazards
• Must have a minimum of 2 Selector Valves
Selector Valve Assembly
Selector Valve Assembly Includes:
• Selector Valve w/ Actuator
• Valve Position Monitor
• Relief / pop-off valve
• 3’ long hose with fittings and adapters
• UVO Kit with release fitting (1/4” NPT, Male)

Pop-off relief valve

Selector Valve
UVO Kit

Agent to protected Agent from


hazard Cylinders
Selector Valve Assembly Operation
• UVO operation allows discharge pressure to transfer through hose and
operate the selector valve, opening it and allowing agent to flow to the
affected hazard.
• Venting of excess pressure during discharge is accomplished by pressure
relief valve
• Manual venting through relief valve will allow spring loaded Selector Valve
to return to it’s normal state

Pop-off relief valve

Selector Valve UVO Kit

Agent to protected Agent from


hazard Cylinders
Selector Valve Assembly Post-Operation
Service Requirements!!
• After Selector Valve activation, UVO MUST be reset!!
• Release Fitting Valve Core (02-13887) MUST be replaced after
each activation.
• Failure to reset UVO and replace valve core will result in
unintended Selector Valve activation in the future due to pressure
leak through valve core!
Selector Valve UVO Kit

IG71-111,
Release Fitting
Selector Valve Assembly
Selector Valve Specs
Part Number Valve Size Thread Size
IG71-233-10-CD 1” 1” NPT Female (25 mm)
IG71-233-15-CD 1-1/2” 1-1/2” NPT Female (40 mm)
IG71-233-20-CD 2” 2” NPT Female (50 mm)
IG71-233-30-CD 3” 3” NPT Female (80 mm)
Material Carbon Steel or Stainless Steel (Specify)
Actuation Pressure 116 psi (8 bar) Minimum
Approvals FM Only
Selector Valve System Example
System Signs
02-11776
Caution / Exit Sign
(Black text over white and yellow
background)

02-11777
Caution – Do Not Enter Sign
(Black text over white and yellow
background)

02-11778
Manual Release Station Sign
(Black text over white background)
System Piping
• Schedule 40 or 80, Threaded, Welded or
Grooved(*)Pipe shall be used
• Black or Galvanized Pipe is acceptable
• Cast Iron Pipe, Steel Pipe conforming to ASTM
A120 or Non-Metallic Pipe shall not be used
System Piping
• All pipe shall conform
with the appropriate
code for your
installation (NFPA 2001,
ISO14520 or EN 15004)
• *Minimum piping design
pressure of 870 psi @
68°F (60 bar @ 20°C)
• Refer to table in Manual
System Fittings
• Minimum piping design pressure of 870 psi @ 68°F
(60 bar @ 20°C)
• Class 300 malleable or Ductile Iron acceptable up
to 3”
• 1,000 lb. Ductile or Forged Steel required above 3”
• Class 600 Flanged acceptable for all pipe sizes
• Class 150 Fittings are not acceptable
• Cast Iron Fittings are not acceptable
• Grooved Fittings MUST meet minimum design
pressure
• (*Not all grooved fittings are acceptable for Fire
Protection service. Check UL listing for all grooved
fittings)
2
Features and Benefits – ProInert Fire Suppression System
Warranty:
• Standard 1 Year Warranty
• Available 5 Year Extended Warranty on “Registered” Systems

Recharge / Exchange Program:


• Order before Noon – Ship the same day
• Order after Noon – Ship the next day
• Forms available on Fike Website for 48 Hour Exchange Program*

*Note:
48 Hour Exchange Program is an ADVANCED Replacement program, It allows you to
order replacement tanks before returning existing cylinders. The shipping pallet used
to transport the replacement tanks becomes your return shipping pallet for the empty
cylinders.
END OF EQUIPMENT SECTION
ANY QUESTIONS?

You might also like