Only particulate matter is expressed in annual geometric means; the other two
are annual arithmetic means. For carbon monoxide and ozone, both values are
not to be exceeded more than once a year.
Basements, Kitchen, Toilets , etc
Industrial Ventilation
Industrial processes use chemicals that may produce toxic gases and
particulates, those need to be removed from work zones.
The sensible heat load includes solar heat gain, occupancy, lighting load,
equipment load as well as other particular sources, if any.
The ventilation flow rate can be calculated using the following equation:
where
Qs = air volume flow rate, in m3/h;
Hs = sensible heat load, in kcal/h; and
DT = allowable temperature rise, in °C
Industrial Ventilation- Heat Control
NOTE . The degree of hazard is related to toxicity, dose rate, and individual
susceptibility.
Industrial Ventilation- Heat Control
Local exhaust ventilation normally requires lower air flows than general
(dilution) ventilation.
Industrial Ventilation-
General (Dilution) Ventilation
Dilution ventilation is used to reduce the concentration of vapours from a
given liquid solvent in the air to a safe level known as the threshold limit value
(TLV) of the solvent expressed in ppm (parts per million). For a given solvent,
the volume of air required to dilute its vapour concentration to below TLV can
be calculated
by the following equation:
where
k = constant varying from 3 to 10 depending on the solvent, uniformity of air
distribution, dilution of vapours in air and location of exhaust hood; and
• HEAT
• FOOD & FUEL EFFLUENTS
• SMOKE
• GREASE
• CARBON MONOXIDE
• CARBON DIOXIDE
• NITROGEN OXIDES
SOLUTION
Use of Kitchen Hoods
Commercial Kitchen Ventilation
Hood Exhaust Flow Rate
Kitchen hoods have been classified as two types
• Type I hoods are used to collect and remove grease, smoke, steam and heat .
1. Fitted with Grease Collection devices
2. Grease Filters
3. Baffles
4. Fire Suppression Systems
Appliances such as cooking ranges, fryers, broilers and griddles
• Under a wall canopy hood, pushing the appliance towards the back wall
significantly improves hood performance
• Under a wall canopy hood, pushing the appliance towards the back wall
significantly improves hood performance
• The air exhausted through a kitchen hood shall be replaced 100 percent with clean
outside air.
• Kitchen room pressure should be maintained slightly lower than the adjoining
building space (for example, dining room) to allow conditioned air to transfer into the
kitchen and to contain heat and odours within the kitchen.
• For kitchens adjacent to a building exterior wall, the kitchen pressure should be
slightly higher than the ambient to prevent ingress of dust, heat and insects.
• Replacement air in air conditioned kitchens should be supplied as close to the hood
as possible and this can be best achieved by the use of compensating exhaust hoods,
with supply air forming an integral part of the hood.
Commercial Kitchen Ventilation
Energy Management Considerations
• Hood exhaust flows can result in twenty or more air changes per hour. Installing a
variable volume system is the first step towards energy conservation to allow for the
exhaust and supply units to ramp up and down depending on the cooking load.
• Varying both the exhaust and the supply will vary the amount of air that needs to be
conditioned. In some cases, a variable system can reduce the costs associated
with conditioning make-up air by up to 50%.
• Exhaust and supply air flow rates should be controlled by installing variable
frequency drives (VFD) on the fan motors. The VFDs are controlled by a temperature
sensor mounted in duct collar. The control system varies
• the frequency of the motor drives and thus fan speed, according to the temperature
seen in the duct collar.
• The VFD system varies the flow continuously as per the cooking requirement, as
opposed to the high, medium and low speed settings on the motor controlled
• manually. The energy savings using VFDs result from the fact that the fan power, W is
proportional to the third power of speed, N, that is, W µ N3 .
Underground Car Park Ventilation
Requirement
• Ventilation is essential in enclosed car parking areas to dilute the level of toxic gases
such as carbon monoxide(CO), oxides of nitrogen (NOx), presence of petrol/diesel
fumes and smoke from engine exhaust.
• Carbon monoxide is a colourless, odourless and highly poisonous gas. Even dilute
concentrations of CO in air can cause nausea, headache and vertigo.
• The undesirable health and fire hazard of the above contaminants can be
contained if their levels are maintained within permissible limits by ventilation.
Introduction to AC system
Air-Conditioning - definition
Dew point temperature: is the temperature at which the air can no longer
"hold" all of the water vapour which is mixed with it, and some of the water
vapour must condense into liquid water. The dew point is always lower than
(or equal to) the air temperature.
Air-Conditioning - terms & instruments
Humidity: is the amount of water vapour in the air. Higher humidity reduces
the effectiveness of sweating in cooling the body by reducing the rate of
evaporation of moisture from the skin.
Relative humidity (RH): is the ratio of the partial pressure of water vapour to
the saturation vapour pressure of water at the same temperature. Relative
humidity depends on temperature and the pressure of the system of interest.
On constant
absolute humidity!
Air-Conditioning - types
Active Passive
(forced flow) (Natural Flow)