SUBMITED BY:
Devendra Singh(0806421021) Dhirendra Singh(0806421022) Divyanshu Singh (0806421023) Diwakar Dubey (0806421024)
HCST Mathura
CONTENTS:
Introduction.
Abnormal Operating Condition. Protection Requirements.
CONTENTS:
Phase to Phase Fault Protection.
Stator to Earth-fault Protection. Fault in Rotor Winding.
Reference .
INTRODUCTION
The type of protection used for a particular motor depends upon the switchgear used for its control. Basically two type of protection are provided for every motor, and these are Thermal Overload Protection. AND Short Circuit Protection. The switchgear used for motor control classified as following two category-
CONT....
Contactor starter with HRC fuse and thermal over
current relay. Circuit breaker and associated protective relays. Contactor and fuse are used for motor up to approximately 150kw.Whereas for large motor circuit breakers are used.
Abnormal Supply Conditions.(CAUSES) a) Loss of Supply Voltage b) Unbalanced supply Voltage c) Phase Sequence reversal of Supply Voltage
CONT....
d) e) f)
Fault in Starting Supply/Circuit.(CAUSES) a) Interruption in Phases b) Blowing of fuse/Single Phasing c) Short Circuit in Supply Cable Internal Fault in Motor itself. (CAUSES) a) Phase to Phase Fault b) Phase to Earth Fault c) Failure to Phase (open circuit) d) Mechanical Failure
PROTECTION REQUIREMENTS
The cost of protective system of motor should be within about 5% of motor cost. The choice of motor protection scheme depend upon the followings: Size of motor , rated voltage , kW. Type: squirrel-cage OR wound rotor. Type of starter , switchgear and control gear. Cost of motor and driven equipment. Type of load , starting current , possible abnormal conditions , etc.
CONT....
BIMETAL OVERLOAD DEVICE:
These are very popular. In case of 3-phase motor triple pole bimetal relays are generally employed. The bimetal strips are either heated by current flowing through them or by special heater coil through which motor current flow. Incase of bigger motors they are connected in secondary circuit of CTs. Bimetal strip can be self setting type or hand resetting type.
CONT....
While selecting the bimetal-overload devices for motor protection, the following aspect should be considered-----a)
b)
c) d)
e)
Characteristic of Relay, Characteristic of motor. Nature of loading. Type of Starting, Starting Current. Protection against overload. Protection against single phasing.
CONT....
SHORT CIRCUIT PROTECTION BY HRC FUSES:
Fault current exceeding 10 times the rated current can be considered as short circuit current and these should be covered by Short Circuit Protecting Devices (SCPD). The SCPD may be in one of the following form------a) HRC Fuse
CONT....
Type of relay available for motor protection:
Thermal protection only. 2. Thermal protection, Instantaneous overcurrent protection . 3. Thermal, Instantaneous Three phase Overcurrent, Instantaneous unbalance, single phasing. 4. Thermal, Instantaneous Three phase Overcurrent, Instantaneous unbalance, single phasing and instantaneous Earth fault.
1.
CONT....
In the protection of large IM all the relays are such that the time reduces with increase in current. Such type of protection can be understand by following fig---
OVERLOAD PROTECTION OF IM
The over load protective devices can be grouped as:
Those which respond to motor current. Those which respond to winding temperature.
The current sensing overload protecting devices can sense the following abnormal conditions--Overloads and undervoltage . 2. Single phasing. 3. Locked rotor , stalling.
1.
CONT....
4. Heavy starting.
And the following condition can be sensed only by embedded thermal device----Temperature rise due to various cause like,
CONT....
The characteristic of IM heating and Replica Relay can be understand by following fig..
Single phase load on distribution service line. Blow out fuse in power factor correcting plant. Short circuit within or out side the motor. Phase failure by blown fuse.(single phasing).
Unbalanced voltage cause the flow of Negative Sequence current, this result as the heating the motor winding, which may reach above the safe limit.
CONT....
The unbalanced voltage protection based upon the following method:
Bimetallic relay arranged to trip faster for unbalanced current. 2. Single phase relay sensing overcurrent in heavily loaded phase. 3. Phase unbalanced relay.
1.
CONT....
The connection of single-phasing preventer can be understand by following fig..
CONT....
phase fault. Which is as following
CONT....
by help of following fig..
REFERENCE
Switchgear Protection & Power System.
THANK YOU.