Professional Documents
Culture Documents
John Levine, P.E. Levine Lectronics and Lectric E-mail: John@L-3.com GE Multilin/ Instrument Transformers, Inc.
1
Agenda
Current Transformers Voltage Transformers Required Information for Specifying CTs & VTs Take Home Rules for CTs & VTs Configure Tool for CTs and VTs Products and tour of Plant Applications where used FT Switches Configure Tool for FT Switches
3
Circuit Isolation Reduce voltage and currents to reasonable working levels. Phasor combinations for summing and measuring power
4
Iron Core
Polarity
Direction of Primary Current Primary IEEE Polarity IEC Marks
X1 S1 H1 P1
Polarity
X1 S1 H1 P1
10
11
Accuracy Class - %
0.30
Region
10% 0.30
100%
Rating Factor
CT Metering Accuracy
Actual secondary current
* All accuracy classes defined by IEEE C57.13 or C57.13.6 * Accuracy classes include both ratio & phase angle error
GE Multilin Instrument Transformers, Inc.
E0.04, E0.2
Metering
CT CLASSIFICATION for Metering A current transformer for metering purposes may typically have an accuracy of 0.3%. The C.T. must maintain this accuracy for normal load currents, provided the rated burden on the C.T. is not exceeded. It is quite acceptable, and in fact desirable, for the C.T. to saturate when fault current flows. The accuracy for a typical metering C.T. is specified as: 0.3 M 0.9
O.3%
METERING
This metering C.T. has an accuracy of 0.3% when the GE Multilin connected burden does not exceed 0.9 OHMS. Instrument Transformers, Inc.
(0.15*, 0.15S^)
* Accuracy class is stated at 100% rated current * At 10% rated current, twice the error is allowed (5% for 0.15 class) ^ Accuracy class is stated at 100% to 5% rated current
19
Accuracy Class - %
0.30
10% 0.30
100%
No accuracy guaranteed at current levels less than 10% 0.60 1.0 2.0 3.0 4.0
20
Rating Factor
Accuracy Class - %
0.30 0.15
200%
300%
400%
0.60
1.0
2.0
3.0
4.0
23
Rating Factor
Accuracy Class - %
0.30 0.15 5% 0.15 0.30 No accuracy guaranteed at current levels less than 5% 100%
200%
300%
400%
0.60
1.0
2.0
3.0
4.0
24
Rating Factor
Format
10 C 400
Accuracy
Letter
Voltage at 20 times CT
T = Determined by test C = Calculated K = Calculated L = Low internal secondary impedance H = High internal secondary impedance
27
CT 1200:5 C or T100
Terminal Volts = (20 times rated) (Total external burden) 100 Volts = (100 amps) (1.0 : )
28
CT 1200:5 C or T200
Terminal volts = (20 times rated) (Total external burden) 200 Volts = (100 amps) (2.0 : )
29
Relaying
30
10% ratio error = (20 x 5) (10%) = (100) (0.10) = 10 amps How many terminal volts would you estimate this CT can produce?
31
CT Burden Calculation
How do we calculate this?
Secondary current Burden of Devices (:) CT Total Burden ZT
X1 X2
Primary Current
32
CT Burden Calculation
ZT = RCT + RL + ZB
ZT = Total burden in ohms (vector summation of resistance and inductance components) RCT (DCR) RL = Resistance of leads in ohms (Total loop distance) ZB = Device impedance in ohms Assumption: 3 phase CTs are Y connected
33
100:5 C.T. Secondary Winding Resistance = .062 ohm Resistance of Cable from C.T. to Relay and back = .1 ohms Resistance of Relay Coil = .02 ohms Total Resistance = .182 ohms
.062 .1
.02
If we have a fault of 2,000 amps and the C.T. ratio is 100:5 then the C.T. secondary current is 100 amps. Therefore we must be able to produce a total voltage of 100 amps x .182 ohms = 18.2 Volts. To prevent CT saturation, select a CT with a knee point above 18.2 Volts.
35
780-102 is a 1000 to 5 CT, Class C100 1000:5 C.T. Secondary Winding Resistance = .32 ohm Resistance of Cable from C.T. to Relay and back = .1 ohms Resistance of Relay Coil = .008 ohms Total Resistance = .428 ohms .32 .1 .008
If we have a fault of 20,000 amps and the C.T. ratio is 1000:5 then the C.T. secondary current is 100 amps. Therefore we must be able to produce a total voltage of 100 amps x .428 ohms = 42.8 Volts. To prevent CT saturation, select a CT with a knee point above 42.8 Volts. What happens if the fault current is 35,000 amps?
36
Current Ratio
Low ratio and high accuracy are not friends!!
Burden
High burden and High Accuracy are not friends!!
37
Potential Transformers
39
Definitions
Voltage Transformer (VT) An instrument transformer used to reflect a primary voltage into a secondary voltage through a magnetic medium. Always connected in parallel with primary conductor across a circuit load. Secondary (measuring) voltage is usually 115 or 120 volts nominally. The secondary voltage level is selected for ease of measurement and safety. Control Power Transformer (CPT) Designed to provide power for contractors, relays and devices with high inrush currents, Regulation is not as critical.
40
41
POTENTIAL TRANSFORMERS
VP
Vs
Relay
42
These standard burden designations have no significance at frequencies other than 60 Hz.
46
VT Installation Guidelines
Caution:
Rated voltage: Do not operate above 110% Line to ground rated: Do not connect line to line Do not use on ungrounded systems w/o consulting factory Rated Frequency:
IEEE VT Groups
VT Group 1 2 No. of Bushing 2 2 Connection Method open ( Y-Y possible open ( Y-Y possible 3 1 Y-Y-Y Any Any Neutral Grounding Any Notes Withstand 25% over rated voltage on an emergency basis Withstand 10% over rated voltage continuously. Primary rated for line to line voltage. Outdoor, two secondary windings. Withstand 10% over rated voltage continuously. Withstand 10% over rated voltage continuously & 25% on an emergency basis. For operation at 100% rated voltage. Withstand 10% overvoltage continuously. For operation at 58% rated voltage. Outdoor. Withstand 40% over rated voltage for 1 minute and 10% over rated voltage continuously
48
4A
Y-Y
Effectively
4B
Noneffectively Effectively
Y-Y
VT Typical Connections
Ferroresonance
Possible with Y connected grounded VTs on ungrounded power systems
A VT is an inductive component Capacitance to ground exists in the system When they match ferroresonance may occur May cause higher VT voltages & saturation Possible results -- High VT currents Overheating VT failure
50
Ferroresonance
Recommended reading:
Ferroresonance of Grounded Potential Transformers on Ungrounded Power Systems AIEE Power Apparatus & Systems, Aug 1959, pg 607-618, by Karlicek and Taylor
51
Ferroresonance Damping
Preferred method Non effectively grounded system
52
Ferroresonance Damping
Preferred method
53
Ferroresonance Damping
Ferroresonance damping resistor RFR value
Based on 2 variables: Air core inductance of primary winding (La) VT ratio (N) RFR = 100 La / N2
Power rating (watts) of the resistor is a system related problem. General recommendation is 50% of VA rating of a single VT.
54
55
___Protection ___ mm
Primary
___24 inch leads ___Cotton tape & varnish _____Other ___Polyester tape
___105 0C (Standard)
Other Special Requirements (dimensional constraints, mounting requirements, etc): ______________________________________________________________________________ ______________________________________________________________________________
57
IEEE: ___W ___X ___M ________Other (Enter 0.3, 0.6, 1.2, or leave blank) IEC:
___Y
___Z
___ZZ
___10VA ___25VA ___50VA ___100VA ______Other (Enter 0.2, 0.5, 1.0, or leave blank)
___500VA
58
___120V ___115V ___110V ___100V ___120/3 ___115/3 ___110/3 ___100/3 ___Other _________________ ___1.9 for 8 hours ___Other____________
Rated Voltage Factor (RVF) (1 bushing only): ___1.9 for 30s Fuses: ___Primary ___Primary ___Secondary ___None ___Live parts only (600 720 V)
___Switchgear Style
___Unfused
(2.5kV 15kV)
59
60
QUESTIONS?
66