You are on page 1of 66

Are you using the right CT's and PT's for your application?

John Levine, P.E. Levine Lectronics and Lectric E-mail: John@L-3.com GE Multilin/ Instrument Transformers, Inc.
1

GE Multilin Instrument Transformers, Inc.

Current & Voltage Transformer Basics (IEEE Standards)

GE Multilin Instrument Transformers, Inc.

Agenda
Current Transformers Voltage Transformers Required Information for Specifying CTs & VTs Take Home Rules for CTs & VTs Configure Tool for CTs and VTs Products and tour of Plant Applications where used FT Switches Configure Tool for FT Switches
3

GE Multilin Instrument Transformers, Inc.

Why use Instrument Transformers?

Circuit Isolation Reduce voltage and currents to reasonable working levels. Phasor combinations for summing and measuring power
4

GE Multilin Instrument Transformers, Inc.

CURRENT TRANSFORMERS & VOLTAGE TRANSFORMERS


TYPES OF C.T. AND V.T. CONSTRUCTION The most common type of C.T. construction is the `DOUGHNUT' type. It is constructed of an iron toroid, which forms the core of the transformer, and is wound with secondary turns.
Secondary Winding Primary Conductor

Iron Core

GE Multilin Instrument Transformers, Inc.

Transformer ratio (TR)


Transformer Ratio = Primary Current ___________________ __ Secondary Current
Secondary Current (5 amps) 100 ___ = 100:5 or 20:1 5
6

Primary Current (100 amps)

GE Multilin Instrument Transformers, Inc.

Polarity
Direction of Primary Current Primary IEEE Polarity IEC Marks
X1 S1 H1 P1

Direction of Secondary Current IEEE Secondary IEC Polarity Marks

Remember: Primary current into polarity = Secondary current out of polarity


7

GE Multilin Instrument Transformers, Inc.

Polarity
X1 S1 H1 P1

Direction of Secondary Current IEEE Secondary IEC Polarity Marks

Primary IEEE Polarity IEC Marks

Remember: Primary current into non-polarity = Secondary current out of nonpolarity

Direction of Primary Current

GE Multilin Instrument Transformers, Inc.

G30 typical wiring

GE Multilin Instrument Transformers, Inc.

What is your application?


If your application is metering , how high do I need to go in current? 2 times ? If your application is protective relaying, how high do I need to go in current? 20 times ?

10

GE Multilin Instrument Transformers, Inc.

CT Rating Factor (RF) -- IEEE


Rated current x (RF) = Maximum continuous current carrying capability: Without exceeding temperature limits Without loss of published accuracy class Typical rating factors -- 1.0, 1.33, 1.5, 2.0, 3.0, 4.0

11

GE Multilin Instrument Transformers, Inc.

CT Rating Factor (RF) -- IEEE


0.60

IEEE C57.13 Accuracy 0.3% @ BX.X RF 4.0


0.6% Accuracy

Accuracy Class - %

0.30

Region

0.3% Accuracy Region 200% 300% 400%

10% 0.30

100%

0.60 1.0 2.0 3.0 4.0


12

Rating Factor

GE Multilin Instrument Transformers, Inc.

Short-Time Thermal Current Rating


One (1) second thermal rating Expressed as value of RMS primary current Main influencing factor: CT primary & secondary wire size Can be converted to thermal rating for any time period (t) up to five (5) seconds: I1-sec  t
13

GE Multilin Instrument Transformers, Inc.

CT Metering Accuracy
Actual secondary current

Rated secondary current

Difference in % is known as the Accuracy of the CT


14

GE Multilin Instrument Transformers, Inc.

IEEE CT Metering Accuracy


Accuracy Class ( * ) 0.15 0.15S 0.3 0.6 1.2 Application High Accuracy Metering Special High Accuracy Metering Revenue Metering Indicating Instruments Indicating Instruments
15

* All accuracy classes defined by IEEE C57.13 or C57.13.6 * Accuracy classes include both ratio & phase angle error
GE Multilin Instrument Transformers, Inc.

IEEE CT Metering Accuracy


Burden
Load connected to CT secondary Includes devices & connecting leads Expressed in ohms Standard values = B0.1, B0.2, B0.5, B0.9, B1.8
All burdens defined by IEEE C57.13 or C57.13.6 for 60 Hz only
16

E0.04, E0.2

GE Multilin Instrument Transformers, Inc.

IEEE CT Metering Accuracy


Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993 & C57.13.6)
Application Burden Designation B0.1 B0.2 B0.5 B0.9 B1.8 E0.2 E0.04 Impedance (Ohms) 0.1 0.2 0.5 0.9 1.8 0.2 0.04 VA @ 5 amps 2.5 5 12.5 22.5 45 5 1 Power Factor 0.9 0.9 0.9 0.9 0.9 1.0 1.0
17

Metering

GE Multilin Instrument Transformers, Inc.

CT CLASSIFICATION for Metering A current transformer for metering purposes may typically have an accuracy of 0.3%. The C.T. must maintain this accuracy for normal load currents, provided the rated burden on the C.T. is not exceeded. It is quite acceptable, and in fact desirable, for the C.T. to saturate when fault current flows. The accuracy for a typical metering C.T. is specified as: 0.3 M 0.9

O.3%

METERING

O.9 OHMS BURDEN


18

This metering C.T. has an accuracy of 0.3% when the GE Multilin connected burden does not exceed 0.9 OHMS. Instrument Transformers, Inc.

IEEE CT Metering Accuracy


Accuracy expressed as:
Accuracy Class
(0.3, 0.6, 1.2) (*) (B0.1, B0.2, B0.5, B0.9, B1.8) E0.2, E0.04) Typical Examples

+ Burden (Ohms) = 0.3B0.2


0.6B0.9 1.2B1.8 0.15E0.2

(0.15*, 0.15S^)

* Accuracy class is stated at 100% rated current * At 10% rated current, twice the error is allowed (5% for 0.15 class) ^ Accuracy class is stated at 100% to 5% rated current
19

GE Multilin Instrument Transformers, Inc.

IEEE CT Metering Accuracy


0.60

IEEE C57.13 Accuracy 0.3 @ BX.X; RF 4.0


0.6% Accuracy Region

Accuracy Class - %

0.30

0.3% Accuracy Region 200% 300% 400%

10% 0.30

100%

No accuracy guaranteed at current levels less than 10% 0.60 1.0 2.0 3.0 4.0
20

Rating Factor

GE Multilin Instrument Transformers, Inc.

IEEE CT Metering Accuracy


CT Parallelogram IEEE C57.13
0.3 class parallelogram 100% 10%

0.6 class parallelogram

Note: Burden must be specified

Out of 0.3% Class


21

GE Multilin Instrument Transformers, Inc.

IEEE CT Metering Accuracy


CT Parallelogram IEEE C57.13
0.3 class parallelogram 100% 0.6 class parallelogram Note: Burden must be specified 10%

Corrected to 0.3% Class


22

GE Multilin Instrument Transformers, Inc.

IEEE CT Metering Accuracy


0.60

IEEE C57.13.6 Accuracy 0.15 @ E0.04, E0.20; 0.15 @ BX.X; RF4.0


0.15% Accuracy Region 0.3% Accuracy 5% Region 100%

Accuracy Class - %

0.30 0.15

200%

300%

400%

0.15 0.30 No accuracy guaranteed at current levels less than 5%

0.60

1.0

2.0

3.0

4.0
23

Rating Factor

GE Multilin Instrument Transformers, Inc.

IEEE CT Metering Accuracy


0.60

IEEE C57.13.6 Accuracy 0.15S @ E0.04, E0.20; 0.15S @ BX.X, RF4.0


0.15% Accuracy Region

Accuracy Class - %

0.30 0.15 5% 0.15 0.30 No accuracy guaranteed at current levels less than 5% 100%

200%

300%

400%

0.60

1.0

2.0

3.0

4.0
24

Rating Factor

GE Multilin Instrument Transformers, Inc.

IEEE CT Relay Accuracy


Standard Relay Accuracy Classes
C or T100 C or T200 C or T400 C or T800
25

What do these mean?

GE Multilin Instrument Transformers, Inc.

IEEE CT Relay Accuracy


Relay class (C or T___ ) designates minimum secondary terminal volts At 20 times rated current Without exceeding 10% ratio error Into a maximum specified burden
Now that everyone is totally confused lets look at some simple examples GE Multilin Instrument Transformers, Inc.
26

CT CLASSIFICATION for RELAYING


Protection Class CTs - Must supply 20 times rated current

Format

10 C 400

Accuracy

Letter

Voltage at 20 times CT

T = Determined by test C = Calculated K = Calculated L = Low internal secondary impedance H = High internal secondary impedance

27

GE Multilin Instrument Transformers, Inc.

IEEE CT Relay Accuracy


C or T100 example
Terminal Volts = 100
X1 X2

Secondary current 100 amps (20 x 5) Burden of Devices (:)

Primary current 24,000 amps (20 x 1200)

CT 1200:5 C or T100

Burden of Leads (:)

Total Ext Burden 1.0 :

Terminal Volts = (20 times rated) (Total external burden) 100 Volts = (100 amps) (1.0 : )

28

GE Multilin Instrument Transformers, Inc.

IEEE CT Relay Accuracy


C or T200 example
Terminal Volts = 200
X1 X2

Secondary current 100 amps (20 x 5) Burden of Devices (:)

Primary current 24,000 amps (20 x 1200)

CT 1200:5 C or T200

Burden of Leads (:)

Total Ext Burden 2.0 :

Terminal volts = (20 times rated) (Total external burden) 200 Volts = (100 amps) (2.0 : )
29

GE Multilin Instrument Transformers, Inc.

IEEE CT Relay Accuracy


Standard IEEE CT Burdens (5 Amp)
(Per IEEE Std. C57.13-1993)
Application Burden Designation B1 B2 B4 B8 Impedance (Ohms) 1 2 4 8 VA @ 5 amps 25 50 100 200 Power Factor 0.5 0.5 0.5 0.5

Relaying

30

GE Multilin Instrument Transformers, Inc.

IEEE CT Relay Accuracy


Excitation curve includes voltage required to overcome internal resistance (DCR) of CT. Approximately 32 volts.

10% ratio error = (20 x 5) (10%) = (100) (0.10) = 10 amps How many terminal volts would you estimate this CT can produce?
31

GE Multilin Instrument Transformers, Inc.

CT Burden Calculation
How do we calculate this?
Secondary current Burden of Devices (:) CT Total Burden ZT

X1 X2

Primary Current

Burden of Leads (:)

32

GE Multilin Instrument Transformers, Inc.

CT Burden Calculation
ZT = RCT + RL + ZB
ZT = Total burden in ohms (vector summation of resistance and inductance components) RCT (DCR) RL = Resistance of leads in ohms (Total loop distance) ZB = Device impedance in ohms Assumption: 3 phase CTs are Y connected
33

CT secondary resistance in ohms @75 deg C

GE Multilin Instrument Transformers, Inc.

GE Multilin Electronic Relay Burden

VA = VI. V= IR, So 0.2 = I*I*R. .2/25 = .008 ohms


34

GE Multilin Instrument Transformers, Inc.

100:5 C.T. Secondary Winding Resistance = .062 ohm Resistance of Cable from C.T. to Relay and back = .1 ohms Resistance of Relay Coil = .02 ohms Total Resistance = .182 ohms

.062 .1

.02

If we have a fault of 2,000 amps and the C.T. ratio is 100:5 then the C.T. secondary current is 100 amps. Therefore we must be able to produce a total voltage of 100 amps x .182 ohms = 18.2 Volts. To prevent CT saturation, select a CT with a knee point above 18.2 Volts.

35

GE Multilin Instrument Transformers, Inc.

780-102 is a 1000 to 5 CT, Class C100 1000:5 C.T. Secondary Winding Resistance = .32 ohm Resistance of Cable from C.T. to Relay and back = .1 ohms Resistance of Relay Coil = .008 ohms Total Resistance = .428 ohms .32 .1 .008

If we have a fault of 20,000 amps and the C.T. ratio is 1000:5 then the C.T. secondary current is 100 amps. Therefore we must be able to produce a total voltage of 100 amps x .428 ohms = 42.8 Volts. To prevent CT saturation, select a CT with a knee point above 42.8 Volts. What happens if the fault current is 35,000 amps?
36

GE Multilin Instrument Transformers, Inc.

Factors Influencing CT Accuracy


Frequency
Low frequency and High accuracy are not friends!!

Current Ratio
Low ratio and high accuracy are not friends!!

Burden
High burden and High Accuracy are not friends!!
37

GE Multilin Instrument Transformers, Inc.

Tips for Avoiding CT Saturation


Use higher ratio CTs Use separate set of high ratio CTs for high fault current tripping Reduce secondary burden Select low burden relays & meters Distribute single phase burdens among phases Increase size of secondary leads Reduce length of secondary leads Use step down auxiliary CTs
38

GE Multilin Instrument Transformers, Inc.

Potential Transformers

39

GE Multilin Instrument Transformers, Inc.

Definitions
Voltage Transformer (VT) An instrument transformer used to reflect a primary voltage into a secondary voltage through a magnetic medium. Always connected in parallel with primary conductor across a circuit load. Secondary (measuring) voltage is usually 115 or 120 volts nominally. The secondary voltage level is selected for ease of measurement and safety. Control Power Transformer (CPT) Designed to provide power for contractors, relays and devices with high inrush currents, Regulation is not as critical.

40

GE Multilin Instrument Transformers, Inc.

41

GE Multilin Instrument Transformers, Inc.

POTENTIAL TRANSFORMERS

VP

4200/120 = 35/1 2400/120 = 20/1

Vs

Relay
42

GE Multilin Instrument Transformers, Inc.

IEEE VT Accuracy Class


Metering Accuracy Classes (% error) 0.3 0.6 1.2 0.15 Defined by IEEE C57.13 Applicable from 90% to 110% rated voltage Defined by IEEE C57.13.6
43

GE Multilin Instrument Transformers, Inc.

IEEE VT Accuracy Class


Metering Burden Accuracy Class Burdens
W X M Y Z ZZ VA 12.5 25 35 75 200 400 PF 0.10 0.70 0.20 0.85 0.85 0.85
44

These standard burden designations have no significance at frequencies other than 60 Hz.

GE Multilin Instrument Transformers, Inc.

IEEE VT Accuracy Class


Expressed as:
Accuracy Class + Burden Code 0.3 W,X,Y 0.6 Z 1.2 ZZ
These standard designations have no significance at frequencies other than 60 Hz.
45

GE Multilin Instrument Transformers, Inc.

46

GE Multilin Instrument Transformers, Inc.

VT Installation Guidelines
Caution:
Rated voltage: Do not operate above 110% Line to ground rated: Do not connect line to line Do not use on ungrounded systems w/o consulting factory Rated Frequency:

Do not operate below rate frequency w/o consulting factory


47

GE Multilin Instrument Transformers, Inc.

IEEE VT Groups
VT Group 1 2 No. of Bushing 2 2 Connection Method open ( Y-Y possible open ( Y-Y possible 3 1 Y-Y-Y Any Any Neutral Grounding Any Notes Withstand 25% over rated voltage on an emergency basis Withstand 10% over rated voltage continuously. Primary rated for line to line voltage. Outdoor, two secondary windings. Withstand 10% over rated voltage continuously. Withstand 10% over rated voltage continuously & 25% on an emergency basis. For operation at 100% rated voltage. Withstand 10% overvoltage continuously. For operation at 58% rated voltage. Outdoor. Withstand 40% over rated voltage for 1 minute and 10% over rated voltage continuously
48

4A

Y-Y

Effectively

4B

Y-Y Y-Broken Corner (

Noneffectively Effectively

Y-Y

GE Multilin Instrument Transformers, Inc.

VT Typical Connections

Open Delta Connection (2) Double Bushing VTs

Y Y Connection (3) Single Bushing VTs


49

GE Multilin Instrument Transformers, Inc.

Ferroresonance
Possible with Y connected grounded VTs on ungrounded power systems
A VT is an inductive component Capacitance to ground exists in the system When they match ferroresonance may occur May cause higher VT voltages & saturation Possible results -- High VT currents Overheating VT failure

50

GE Multilin Instrument Transformers, Inc.

Ferroresonance
Recommended reading:
Ferroresonance of Grounded Potential Transformers on Ungrounded Power Systems AIEE Power Apparatus & Systems, Aug 1959, pg 607-618, by Karlicek and Taylor
51

GE Multilin Instrument Transformers, Inc.

Ferroresonance Damping
Preferred method Non effectively grounded system

Y Broken Corner ( VT connection Voltage relay to detect ground fault


0 volts @ normal condition 3 times normal L-N phase voltage @ ground fault

Ferroresonance damping resistor RFR

52

GE Multilin Instrument Transformers, Inc.

Ferroresonance Damping
Preferred method

Y-Y/Broken Corner ( Connection


Double secondary VT (1) Relaying / Metering (1) Ground fault detection and ferroresonance damping

53

GE Multilin Instrument Transformers, Inc.

Ferroresonance Damping
Ferroresonance damping resistor RFR value

Based on 2 variables: Air core inductance of primary winding (La) VT ratio (N) RFR = 100 La / N2
Power rating (watts) of the resistor is a system related problem. General recommendation is 50% of VA rating of a single VT.
54

GE Multilin Instrument Transformers, Inc.

Required Information for Specifying CTs & VTs

55

GE Multilin Instrument Transformers, Inc.

Current Transformer (CT) RFQ Specification


Environment: System Voltage (kV) 0.6 0.72 3.6 5.0 7.2 8.7 12 15 24 25 34.5 34.5 CT Application: Dimensions: Max. Outside: CT Window: Bar: _____ Current Ratio: ___Indoor ___Outdoor Power Frequency (kV) 4 3 10 19 20 26 28 34 50 40 70 70 ___Metering ___ Inches BIL (kV) 10 40 60 60 75 75 110 125 125 150 200 Standard (Check one) IEEE __ IEC __ IEC __ IEEE __ IEC __ IEEE __ IEC __ IEEE __ IEC __ IEEE __ IEEE __ IEEE __

___Protection ___ mm

L ______ x W ______ x D ______ Round: ______ Diameter; _______ : 5 _______ : 1


56

Rectangular: L ______ x W ______ ;

Primary

GE Multilin Continued next slide Instrument Transformers, Inc.

Current Transformer (CT) RFQ Specification (Continued)


Accuracy: Indication Only: _____ %, _____VA (Skip metering & protection selections) Metering Class: IEEE: ___0.3 ___0.6 ___1.2 ___2.4 ________Other IEC: ___0.2 ___0.5 ___1.0 ________Other Metering Burden: IEEE (Ohms): ___B0.1 ___B0.2 ___B0.5 ___B0.9 ___B1.8 ______Other IEC (VA): ___2.5 ___5.0 ___10 ___15 ___30 ______Other Protection Class: Operating Frequency: Rating Factor: C______(IEEE) ___60HZ ___1.0 ___50HZ ___1.33 ___1.5 ___2.0 ______Other ___VA, ___P___(IEC)

Secondary Connections: ___Terminals Outer Insulation: Insulation Class: ___Standard

___24 inch leads ___Cotton tape & varnish _____Other ___Polyester tape

___105 0C (Standard)

Other Special Requirements (dimensional constraints, mounting requirements, etc): ______________________________________________________________________________ ______________________________________________________________________________

57

GE Multilin Instrument Transformers, Inc.

Voltage Transformer (VT) RFQ Specification


Environment: System Voltage (kV) 0.6 0.72 3.6 5.0 7.2 8.7 12 15 24 25 34.5 34.5 ___Indoor ___Outdoor BIL (kV) 10 40 60 60 75 75 110 125 125 150 200 Standard (Check one) IEEE __ IEC __ IEC __ IEEE __ IEC __ IEEE __ IEC __ IEEE __ IEC __ IEEE __ IEEE __ IEEE __ Power Frequency (kV) 4 3 10 19 20 26 28 34 50 40 70 70 ___50HZ

Operating Frequency: ___60HZ Accuracy:

IEEE: ___W ___X ___M ________Other (Enter 0.3, 0.6, 1.2, or leave blank) IEC:

___Y

___Z

___ZZ

___10VA ___25VA ___50VA ___100VA ______Other (Enter 0.2, 0.5, 1.0, or leave blank)

___200VA Continued next slide

___500VA
58

GE Multilin Instrument Transformers, Inc.

Voltage Transformer (VT) RFQ Specification (Continued)


Thermal Rating: Primary Voltage: _______VA (Optional) ___1 bushing ___2 bushing Secondary Voltage: _________VAC - Phase to neutral _________VAC - Phase to phase

___120V ___115V ___110V ___100V ___120/3 ___115/3 ___110/3 ___100/3 ___Other _________________ ___1.9 for 8 hours ___Other____________

Rated Voltage Factor (RVF) (1 bushing only): ___1.9 for 30s Fuses: ___Primary ___Primary ___Secondary ___None ___Live parts only (600 720 V)

___Switchgear Style

___Unfused

(2.5kV 15kV)

Note integral fusing not available above 15kV

59

GE Multilin Instrument Transformers, Inc.

Take Home Rule # 1


Never open circuit a current transformer secondary while the primary is energized
CTs are intended to be proportional current devices. Very high voltages can result from open circuiting the secondary circuit of an energized CT. Even very small primary currents can cause damage Consult the factory if you have questions.

60

GE Multilin Instrument Transformers, Inc.

Take Home Rule # 2


Never short circuit the secondary of an energized VT
VTs are intended to be used as proportional voltage devices. Damaging current will result from short circuiting the secondary circuit of an energized VT.
61

GE Multilin Instrument Transformers, Inc.

Take Home Rule # 3


Metering applications do not require a C class CT
C class ratings are specified for protection purposes only. With some exceptions metering class CTs are typically smaller and less expensive.
62

GE Multilin Instrument Transformers, Inc.

Take Home Rule # 4


CT secondary leads must be added to the CT burden
Electronic relays usually represent very little burden to the CT secondary circuit. In many cases the major burden is caused by the CT secondary leads.
63

GE Multilin Instrument Transformers, Inc.

Take Home Rule # 5


Never use a 60 Hz rated VT on a 50 Hz System
60 Hz VTs may saturate at lower frequencies and exceed temperature limitations. VT failure is likelysevere equipment damage is possible.
64

GE Multilin Instrument Transformers, Inc.

Take Home Rule # 6


Exercise caution when connecting grounded VTs to ungrounded systems
Line to ground voltage on any VT may exceed the primary voltage rating during a fault condition VT must be designed for application.
65

GE Multilin Instrument Transformers, Inc.

QUESTIONS?

66

GE Multilin Instrument Transformers, Inc.

You might also like