Professional Documents
Culture Documents
References
Electrical power ( Dr\ S.L. Uppa ) Elements of power system analysis ( William Stevenson ) Modern power system analysis ( I.J.Nagrath , D.R. Kothari )
TL2
220/66 kV Loads
66/11 kV
11kV/380V
Standard voltages .
1. Generation voltages . 3.3 , 6.6 , 11 , 33 KV 2. Transmission line voltage . 11 , 33 , 66 , 110 , 132 KV 3. Distribution high voltages . 11 , 6.6 KV 4. Distribution low voltages . 380 , 220 KV
Power stations
Types of power stations : 1. Thermal power stations . 2. Hydro power stations . 3. Nuclear power stations . 4. Gas power stations .
Turbine
Generator BB
Coal Burner
Condenser
Cooler
Disadvantages
1. Running costs are high because it uses coal and solar . 2. The response is very low to supply the increasing in load . 3. It is not clean and causes more pollution . 4. It has low efficiency ( 25 : 40 %) .
Disadvantages
1. 2. 3. 4. It has high construction cost . It has high T.L costs . Constructed far from the loads . Takes more time to construct .
Control rots
Turbine CO2
Generator
Advantages and disadvantages are similar to hydro power station added to that it has higher protection cost ands and it is constructed in the desert.
It depends on the outage of gases from the refine petrol factory which produces high pressure gas, (in the Max and Tebein in Egypt) .
Types of conductors .
1.Copper conductor . 2.Aluminum conductor . 3.Aluminum conductor, steel reinforced Aluminum conductors have replaced copper because of the much lower cost and lighter weight.
Resistance
Resistance causes power loss in the T.L. For uniform resistance ,
R ! VL a
( R 2 R 1 ) ! (T t 2 ) (T t 1 )
t
T R
The alternating flux induces higher voltages acting on the interior filaments than are induced on filaments near the surface of the conductor .
La Xa Za Lb Xb Zb
r
Ia % Ib
rrr
Definition of inductance
Induced voltage related to change of flux linkage is :
e ! d ] dt (1)
When the current in a circuit is changing, the induced voltage must be changing as a proportional ratio as :
e w di dt
e ! L (di dt ) (2)
L !] i
where, ( i ) and ( ) is the instantaneous current and flux linkages .
For sinusoidal alternating current, flux linkages are sinusoidal , where is the phasor expression as :
] ! L .I ( phasor flux linkages )
linkages is : V ! J [ LI ! J []
is defined as the flux linkage of one circuit due to the current in the second circuit as :
M 12 ! ] 12 I 2
Where, I2 produces flux linkages 12 with circuit 1.
The phasor voltage drop in circuit 1 caused by flux linkages of circuit 2 is:
V 1 ! J [ M 12 I 2 ! J [] 12
Mutual inductance is important in considering the influence of power lines on telephone lines and the coupling between parallel power lines .
H x ! I x 2T x (3) B x ! Q H x ! Q (I x 2T x )
N x ! B x dx ! Q (I x 2T x ) dx
AT / m
B x ! Q H x ! Q ( xI 2T r 2 )
The flux /meter of length is :
wb / m 2
d N ! Q ( xI 2T r ) dx
2
wb / m
The flux linkages d] of length are the product of the flux per meter of length and the fraction of the current linkage .
d ] ! (T x T r ) d N
2 2
! ( Q Ix 3 2T r 4 ) dx
] int ! ( Q Ix 3 2T r 4 ) dx ! ( Q I 8T )
0 r
wbt / m
wbt / m
Where,
Q ! Qr Q 0
Assuming ,
Qr ! 1
H /m
Flux linkages between two points external to an isolated conductor . In the Fig. P1 and P2 are two points at distance D1 and D2 from the center of the conductor which carries a current of (I) :
H x ! (I 2T x )
@ B x ! Q (I 2T x )
AT / m
wb / m 2
] 12 !
D1
(Q I
2T x ) dx ! ( Q I 2T ) ln( D 2 D1 )
wbt / m
@ ] 12 ! 2 v 10 I ln( D 2 D1 )
7
wbt / m
The inductance due only to the flux included between P1 and P2 is: L12 ! 2 v 107 ln( D 2 D1 ) H /m Using the logarithm to base ( 10 ) :
L 12 ! 0.7411 log(D 2 D1 )
mH / mile
r1
r2
First , consider only the flux linkages of the circuit caused by the current in conductor 1. The current in conductor 2 is equal in value and opposite in direction to the current in conductor 1
The inductance of the circuit due to current in conductor 1 is determined by the following equation:
L 12 ! 2 v 10
7
ln( D 2 D1 )
H /m
With the distance D between conductor 1 and 2 substituted for D2 and the radius r1 of conductor 1 substituted for D1. For external flux only:
H /m
H /m
The total inductance of the current due to the current in conductor ( 1 ) equations :
L 1 ! [(1 2) 2 ln( D r1 )] v 107 = 2 v 107 [( 1 4 ) + ln( D r1 )] = 2 v 107 [ln e 1 4 + ln( D r1 )] = 2 v 107 ln( D r1 e 1 4 ) = 2 v 107 ln( D r1d ) =0.7411 log10 ( D r 1d ) H /m
Where,
d 1 !
r1 e
1 4
H /m
If
r1d r 2d r d ! !
mH / mile
Inductance between two points external one conductor is onehalf the total inductance of a single-phase line and is called the inductance per conductor .
with distance
Let us determine , (] 1 p )1 the flux linkages of conductor, due to I 1 including internal flux linkages and external all the flux beyond point ( p ):
7
wbt / m
The flux linkage (] 1 p )2 with conductor ( 1 ) due to I 2 is equal to the flux produced by I 2 between the point (p) and conductor ( 1 )
(] 1 p )2 ! 2 v 10 I 2 ln( D 2 p D12 )
7
The flux linkage ] 1p with conductor (1 ) due to all the conductors in the group is
] 1 p ! 2 v 10 [I 1 ln( D1 p r1d I 2 ln( D 2 p D12 ) )
7
However , I 1 I 2 I 3 .... I n =0
I n ! (I 1 I 2 I 3 .... I n 1 )
( D1 p $ D 2 p $ ..... $ D np )
p : is infinity for away
] 1 ! 2 v 107 [I 1 ln(1 r1d I 2 ln(1 D12 ) I 3 ln(1 D13 ) .... I n ln(1 D1n ) )
+ ln D1 p (I 1 I 2 I 3 .... I n )] (5)
The figure shows a single-phase line composed of two conductors , each conductor arrangement of an indefinite number of conductors and share the current equally .
Conductor ( x ) is composed of ( n ) identical each of which carries the current I/n . Conductor ( Y ) , which is the return circuit for the current in conductor( x ) , is composed to identical each of which carries the current -I/m. Applying equation ( 5 ) to filaments of conductor ( x ) , the flux linkage at conductor ( a ) is :
] a ! 2 v 107 ( I n )[ ln(1 rad ln(1 Dab ) ln(1 Dac ) .... ln(1 Dan )] )
- 2 v 107 ( I m ) [ ln(1 Daa d ln(1 Dab d ln(1 Dac d .... ln Dam ] ) ) )
Or
] a ! 2 v 107 I ln( m Daa d ab d ac d Dam D D .....
n
ra d ab D ac ..... D an ) D
wbt / m
H /m
H /m
L x ! 2n v 10 ln[
7
( Daa d ab d ac d Dam )( Dba d bb d Dbm )( Dna d Dnm ) D D ... D ... ... ( Daa Dab Dac ...Daa )( Dba Dbb Dbc ...Dbn )( D na ...D n n )
H /m
Where
However , the inductance of conductor ( Y ) can be calculated similar to conductor ( x ) . The total inductance of conductor ( x ) and ( y ) is :
L ! Lx Ly
Example (1) One circuit of a single phase transmission line is composed of three solid wires ( 0.1 in ) . The return circuit is composite of two ( 0.2 in radius ) wires . The arrangement of conductors is shown in fig. . Find the inductance due to the current in each side of the line and the inductance of the complete line . Solution The G.M.D between side ( x ) and ( y ) is :
L y ! 2 v 107
Example (2) A conductor is composed of seven identical strands each having a radius ( r ) . Find the ( G.M.R ) for the conductor. Solution G.M.R of the seven strand conductor is :
Ds !
49
The inductive reactance of one conductor of a singlephase two conductor line is : x L ! 2T fL ! 2T f v 0.7411 v 103 log( D m D s )
;/mile
r a ! r b ! rc ! r
c
b D
Assume that , there is no neutral wire. Assume balanced 3-phase phasor current .
@ Ia Ib Ic ! 0
Since,
I a ! (I b I c )
(7)
From equation ( 7 ) in ( 6 ) ,
@ ] a ! 2 v 107 ln[I a ln(1 r d- I a ln(1 D )] )
=2 v 107 I a ln( D r d )
wbt / m
And Or
L a ! 2 v 107 ln( D r d )
L a ! 0.4711 log( D r d )
H /m
mH / mile
This equation is the same in form as equation for a singlephase line ( between two conductors ) . However ,
L a ! L b ! Lc
A complete transposition cycle is shown as : The flux linkages of ( a ) in position ( 1 ) , when ( b ) is in position ( 2 ) and ( c ) in position ( 3 ) , is :
] a1 ! 2 v 107 ln[I a ln(1 r d+ I b ln(1 D12 ) + I c ln(1 D 31 )] )
1 a D13 D12
wbt / m
c D23
wbt / m
b D23
wbt / m
a D23
] a ! (] a1 ] a2 ] a3 ) 3
2 v 107 ln[3 I a ln(1 r d+ I b ln(1 D12 D 23 D13 ) + I b ln(1 D12 D 23 D13 )] ) @ ]a ! 3
I a ! (I b I c )
2 v 107 ln[3 I a ln(1 r d- I a ln(1 D12 D 23 D13 )] ) @ ]a ! 3 2 v 107 = ln[3 I a ln(1 r d- 3 I a ln(1 3 D12 D 23 D13 )] ) 3 = 2 v 107 I a ln( 3 D12 D 23 D13 r d ) = 2 v 107 I a ln( Deq . r d )
However ,
L a ! L b ! Lc
are the same of equation for equal D12 ! D 23 ! D13 ! D spacing conductor
Example (3) A single circuit 3-phase line operated at ( 60 CPS ) is arranged as shown below . Each conductor has radius ( 0.2 in ) . Find the inductance and inductive reactance per phase per mile ,at frequency equals ( 50 c/s ) . Solution p L a ! 0.7411 log10 ( Deq . D sc )
Deq . ! D D D
3 p ab p ac
p cb
D ! A .B .C
p sc
3
A ! 2 r d aa .D d
B ! 2 r d bb .D d
C ! 2 r d cc .D d
Example (4) Each conductor of a section of the ( 460 KV ) line shown in below is ( 1.5 in ) diameter . Conductor spacing is shown in the figure . Find the inductive reactance in ohm/mile at 60 CPS . Solution
Example (5) A 3-phase double circuit line has diameter ( 0.3 in ) . The line is arranged as shown below and is completely transposed. Find 60 cycle inductive reactance per phase per mile . Solution
Bundled conductors
The trend toward ever higher voltages for T.L has stimulated interest in the use of two or more conductors per phase. Such a line said to be composed of " bundled " conductors.
Usually the spacing of conductors of a phase is about ( 10 ) times the diameter of one conductor , that is about ( 8 to 20 in ). The advantages of bundling are reduced reactance because of increased self SGM and reduce voltage drop and voltage gradient which result in reduced radio interference
D!q 2 x
c m
The electric field intensity is equal to the electric flux density divided by the permittivity of the medium.
I ! q 2 xk
Where
v m
12
k ! k r ko
ko ! 8.854 v 10
F m
@I ! D k
= ( q 2 k ) ln( x r )
V 12 !
dx ! q 2 xk dx ! (q 2 k ) ln( D 2 D1 )
D1
D2
(1)
D1
C !q V
F m
(2)
The voltage between the two conductors of the two wire shown in the fig.(3) can be found by computing the voltage drop due to the charge (qa) on conductor ( a ) and assume that conductor ( b ) is uncharged and then by computing the voltage drop due to the charge (qb) on conductor ( b ) . By the principle of superpose the voltage drop are computed. We obtained:
V ab ! (q a 2 k ) ln( D r a ) (q b 2 k ) ln(rb D )
a r1
r2
F m
If
r a ! rb ! r
C ab ! 2 k 2 ln( D r ) = k ln( D r )
F m
Sometimes it is desirable to know the capacitance between one of the conductors and a neutral point between them . Thus the capacitance to neutral for the two-wire line is twice the line-to-line capacitance ( capacitance between conductors ) . The voltage across the line divided equally between them . Therefore,
C an ! C bn ! 2C ab ! 2 k ln( D r ) F m
c D23
Similarly,
V ac ! (1 2 k ) [q a ln( D r ) q b ln( D D ) q c ln(r D )]
@ V ab V ac ! (1 2 k ) [ 2 q a ln( D r ) (q b q c ) ln(r D )]
V
V
We have assumed that ground is for enough a way to have negligible effect. For,
q a qb qc ! 0
@ qb qc ! qa
@ V ab V ac ! (1 2 k ) [ 2 q a ln( D r ) q a ln(r D )] = (q a 2 k ) ln( D 3 r 3 ) = (3q a 2 k ) ln( D r ) (3)
Fig.(6) is the phasor diagram of voltages where the voltage from line ( a ) to the neutral of the 3phase circuit.
V ab ! ( 3 2) V ab J (1 2) V ab
V ab ! 3 V an
@ V ab ! ( 3 2) 3 V an J ( 3 2) V an ! 3 V an [( 3 2) J (1 2)]
Similarly,
V ac ! 3 V an [( 3 2) J (1 2)]
@ V ab V ac ! 3 V an
From ( 3 ) and ( 4 ) we get:
(4)
3 V an = (3q a 2 k ) ln( D r )
@ V an = (q a 2 k ) ln( D r )
C an ! q a V an
@ C an ! 2 k ln( D r )
F m
Where,
Deq ! 3 D12 D 23 D 31
V ab V ac ! 3 V an
@ 3 V an ! (1 2 k ) [2q a ln( Deq r ) q b ln(r Deq ) q c ln(r Deq )]
And
C n ! q a V an ! 2 k ln( Deq r ) F m (I )
To apply the method of images to the calculation of capacitance for a 3- phase , refer to fig.( 8 ) , we assume that the line is transposed and that conductor ( a ) , ( b ) and ( c ) carry the changes (qa) , (qb) and (qc) and occupy positions ( 1 ) , ( 2 ) and ( 3 ) , in the first part of the transposition cycle . The conductors with the image charges charge (-qa) , (-qb) and (-qc). Equations for 3-parts of the transposition cycle can be written for the voltage drop from conductor (a) to conductor ( b ) as determined by the three charged conductors and their images . With conductor ( a ) in position ( 1 ) , ( b ) position ( 2 ) and ( c ) in position ( 3 ) .
Similar equations for Vab are written for the other parts of the transposition cycle and calculate the average value of Vab. The equation for the average value Vac is found in a similar manner , and (3Van) is obtain by adding the average values of Vab and Vac . Knowing that the sum of charges is zero. We then find:
C n ! 2 k [ln( Deq r ) ln( 3 H 12 H 23 H 31
3
H 1H 2 H 3 )]
F m
( II )
Comparison of equations ( I ) and ( II ) show the effect of the earthed is to increase the capacitance of a line ( subtract from it the term:
log( 3 H 12 H 23 H 31
3
H 1H 2 H 3 )
Deq ! D D D
3 p ab p bc
p ca
D ! A .B .C
p sc 3
p ab p bc
A ! 2 r .D a a d
B ! 2 r .Db b d
C ! 2 r .Dc c d
The equivalent circuit diagram and the vector diagram for a short line are shown in fig.( 6.1 ) in which:
The currents IS and IR will be equal in magnitude but not in phase. Since there is a phase-shift of voltage along the line. R is obtained from a knowledge of the line length ,the size of conductor and the specifics resistance of the conductor material , while XL is calculated from the conductor spacing and radius using the formula derived in Chapter 5 .
IS ! IR
(6.1a )
(6.1b )
V S ! V R ( R jX L )I R !V R Z I R
Hence, if the receiving-end conditions are known the necessary sending-end voltage may be calculated .
It will be noted that ( 6.1a ) and ( 6.1b ) are phasor equations , a more approximate method involving scalar quantities is as follows: Referring to the vector diagram,
V SX !V R I R R cos JR I R X L sin JR
V SY ! I R X L cos JR I R R sin JR
@ V S =[ (V R I R R cos JR I R X L sin JR ) +(I R X L cos JR I R R sin JR ) ]
2 2
12
However (IR XL) and (IR R) are very much less than VR and the small voltage is in quadrate with the much larger VSX ,
@ V S $ V SX $ V R I R R cos JR I R X L sin JR
The voltage regulation of the line is given by the rise in voltage when full loads is removed , or :
V S V R ( R cos JR X L sin JR ) %age voltage regulation ! $ IR VR VR
Example A three-phase line delivers 3 MW at 11 KV for a distance of 15 Km . Line loss is 10 % of power delivered , load power factor is 0.8 lagging . frequency is 50 Hz , 1.7 m equilateral spacing of conductors . Calculate the sending-end voltage and regulation . Solution
Receiving-end phase voltage = 11,000 3 ! 6.360 ! V R
Line current = phase current ( assuming a star connection ) 3,000 v 103 = ! 197 A 3 3 v 11 v 10 v 0.8
Assuming that the conductors are manufactured from copper having a resistance of 0.0137 ohms per meter for a cross-sectional area of 1 mm2 , the conductor cross-section is 80 mm2 corresponding to a radius of 5 mm .
H / metre
@ V S $ V R I R R cos JR I R X L sin JR = 6,350 + ( 197 v 2.58 v 0.8) + ( 197 v 5.75 v 0.6) = 6,350 + 1057 = 7,407 V per phase = 12,780 V line
These methods of calculation give reasonably accurate results for the solution of most transmission-line problems .
Nominal T method .
In a nominal T method the total line capacitance is assumed to be concentrated at the middle point of the line . The T representation of a line is shown in fig.( 6.12 ).
Series impedance of the line Z ! R jX Shunt admittance Y ! j [C
With the usual meanings of the quantities given in fig.( 2 ) , Z Voltage at the mid-point of the line . Vab ! Vr Ir Current in the capacitor , Sending-end current ,
Iab ! Vab Y
Is ! Ir Iab =Ir Vab Y Z =Ir (Vr Ir ) Y 2
Z Y Is =Ir (1 ) Y Vr 2
(6.13.1)
Sending-end voltage ,
Z Vs ! Vab Is 2 Z Z Y Z =Vr Ir [Ir (1 Y Vr )] 2 2 2
Z Y Z Y Vs ! Vr (1 ) Ir ( Z ) 2 4
(6.13.2)
Equations ( 6.13.1 ) and ( 6.13.2 ) give the sending-end current and sending-end voltage respectively. Other quantities , such as phase shift, power input, efficiency, regulation, etc, can be determined in the usual manner .
Phasor diagram The phasor diagram of the nominal T circuit of fig.(6.12) is shown in fig.(6.13). It is drawn for a lagging power factor cos JR
Nominal
method .
This method assumed that one-half of the total line capacitance is concentrated at each end of the line and the total resistance and inductive reactance are concentrated at the center . Fig.( 6.14 ) shows the nominal representation of the line.
Y I=Ir Iab ! Ir Vr 2
Voltage at the sending-end ,
Vs ! Vr I Z Y ! Vr ( Ir Vr ) Z 2 Z Y ! (1 )Vr Z Ir 2
(6.14.1)
Icd
Y ! Vs 2
Is ! I Icd
Z Y Y Y Is ! Ir Vr [(1 )Vr Z Ir ] 2 2 2 Z Y2 Z Y ! ( Y+ ) Vr ( 1 ) Ir 4 2
(6.14.2)
Equations ( 6.14.1 ) and ( 6.14.2 ) give the sending-end voltage and current respectively . The other calculations can be made in the usual manner.
Phasor diagram The phasor diagram of a nominal circuit is shown in fig.( 6.15 ). It is also drawn a lagging power factor of the load.
Example A three-phase, 50 Hz, transmission line, 40 km long delivers 36 Mw at 0.8 power factor lagging at 60 kv (phase). The line constants per conductor are , Shunt leakage may be neglected. Find the sending-end voltage , current , phase angle, and the efficiency . Use (a) nominal T method, (b) nominal method. Solution
Phase voltage at the receiving-end
V r ! 60 kv =60 v 10
v
w
12 v 10 Ir ! ! 250 3 60 v 10 v 0.8
6
Vr ! V r jQ cos Jr ! 0.8 , sin Jr ! 0.6 Ir ! I r cos Jr j I r sin Jr =250 v 0.8 j 250 v 0.6=200 j 150
Reference per phase,
R ! 2.5 ;
! 78.6 v 10 90r
6
! (200 j 150) (-0.2315+j 4.903) =199.8 j 145 ! [(199.8) (145) ] tan ( 145 199.8)
2 2 12 1
Fig.(6.16):Phasor diagram
Vs and Is ,
! 463.2 v 10
Transmission efficiency ,
Power output LT ! Power output Power loss 36 v 10 ! 6 3 36 v 10 463.2 v 10 ! 0.9872 or 98.72 per cent
6
Calculation by nominal
method
The nominal circuit for the line is shown in Fig.( 6.14) Y Iab ! Vr 2 ! j 39.3 v 106 v 60 v 103 =j 2.35
I ! Ir Iab ! (200 j 150) j 2.35 =200 j 147.65 ! [(200) (147.65) ] tan ( 147.65 200) ! 245.6 36r 26d
2 2 12 1
Vs ! Vab I Z ! 60 v 103 5136 j 5910 ! 65136 j 5910 ! [(65136) (5910) ] tan (5910 65136) ! 65390 5r 11d v/phase
2 2 12 1
=65390 3=113.2
kv
Sending-end current ,
Is ! Ir Icd ! (200 j 150) 0.232+j 2.557 =199.8 j 145 ! [(199.8) (145) ] tan ( 145 199.8) ! 247 35r 57d A
2 2 12 1
=3 I R =3 v (248.6) v 2.5
2
=463.6 Kw
Transmission efficiency ,
36 v 10 LT ! 6 3 36 v 10 463.6 v 10 ! 0.9873 or 98.73 per cent
6
Example
A three-phase , 50 Hz , 150 km line operates at 110 Kv between the lines at the sending-end. The total inductance and capacitance per phase are (0.2 H) and (1.5 F) . Neglecting losses calculate the value of receiving-end load having a power factor of unity for which the voltage at the receiving-end will be the same as that at the sending-end . Assume one-half of the total capacitance of the line to be concentrated at each end .
Solution
The circuit for the given line is shown in fig.(6.17) . It is a nominal representation . 110 v 1000 V r !V s ! ! 63510 v 3
Z =jX L ! j 62.8
Shunt admittance per phase ,
6
siemins
Vr !V r j 0
Let the load current be Ir . Since the load power factor is unity ,
Ir ! I s 0r ! I s j 0
Current through the inductive reactance ,
Sending-end voltage ,
Vs ! Vr I Z =V r j 0 ( Ir j 14.96)( j 62.8) =(V r -939.5)+j 62.8 I r
Introduction
A network having two input and two output terminals is known as a two-port network . It may also be called a twoterminal-pair network or quadriple network . In fig.(1 . a,b) represent the input pair terminals and ( c,d ) the output pair terminals . The two pairs of terminals are usually shown to be enclosed in a box .
its
(1.1)
Where A , B , C , D are called the general network constants of the system . These constants are known by other names like transmission parameters , chain parameters and auxiliary network constants .
A C The matrix
Cascaded network
The overall A , B , C , D constants for several 2-port networks connected in cascade ( or chain arrangement ) can be found out easily . Fig.( 2 ) shows two cascaded networks , and one that is the equivalent of both . The constants of the two component networks are A1 , B1 , C1 , D1 and A2 , B2 , C2 , D2 . Let the constants for the equivalent network be A0 , B0 , C0 , D0 .
Let Va and Ia be the voltage and current respectively at the junction (a) of the two networks.
V a ! A2 V r B 2 I r I a ! C 2 V r D2 I r
(2.1)
Substituting the values of Va and Ia from the first set of equations in the second set , we have :
V s ! A1 ( A2 V r B 2 I r ) B 1 (C 2 V r D 2 I r ) ! ( A1 A2 B 1C 2 ) V r ( A1B 2 B 1D 2 ) I r (2.3)
I s ! C 1 ( A2 V r B 2 I r ) D1 (C 2 V r D 2 I r ) ! (C 1 A2 D1C 2 ) V r (C 1B 2 D1 D 2 ) I r (2.4)
The sending-end voltage and current for the equivalent network with constants A0 , B0 , C0 , D0 are given by :
V s ! A0 V a B 0 I a I s ! C 0 V a D0 I a (2.5)
Equating the constants of Vr and Ir , the overall constants for the two networks in cascade are :
A0 ! A1 A2 B 1C 2 B 0 ! A1B 2 B 1 D 2 C 0 ! C 1 A2 D1C 2 D 0 ! C 1B 2 D 1 D 2 (2.6)
But Va and Ia are the input voltage and current respectively of the second network , so that :
V a A2 ! I a C 2
B 2 V r D2 I r
(2.8)
V ! B I rs
(3.1)
I ss ! D I rs
(3.2)
Now , the voltage V is applied to the output terminals and the input terminals are short circuited fig.( 3 ,b ) . The directions of flow of currents at the input and output terminals are reversed and the sending-end voltage Vs becomes zero. Equation ( 1.1 ) become :
0 ! AV BI rd
AV I rd ! B
I sd CV DI rd !
(3.3)
(3.4)
I sd I rs !
(3.5)
Fig.( 3 )
Combining equations ( 3.1 ), ( 3.3 ) , ( 3.4 ) and ( 3.5 ) we get , DAV I rs ! CV B V DAV ! CV B B Dividing both the sides of the above equation by -V/B we get , AD BC ! 1 (3.6) Equation ( 3.6 ) is of one of the required relations between the network constants. This relation may also be put in the determinant form as :
A C
B !1 D
By comparing these equations with the general equations (1.1) and (1.2) the general constants for the series impedance network can be written as :
A !1 C !0
B !Z D=1
(4.3)
V s !V r
I s !Y Vr I r
(5.1)
V s 1 ! I s Y
Hence,
0 V r I 1 r
(5.2)
A !1 C !Y
B ! 0 D=1
(5.3)
Half T network
A half T network is shown in fig.( 6 ) .
V s !V r Z I r !V r (Y V r I r ) Z ! (1 Z Y ) V r Z I r
V s (1 Z Y ) Z V r ! I 1 r Y I s (6.1)
Hence,
A ! 1 Z Y C !Y B !Z D=1 (6.2)
Matrix method , The half T network can be considered as the cascade connection of two sections . One section is a series impedance Z and the other a shunt admittance Y . The overall constants are obtained from the matrix product of the transfer matrices of each section in the correct order.
V s 1 Z 1 ! I s 0 1 Y
0 V r I 1 r
(1 Z Y ) Z V r ! I 1 r Y
Introduction
An overhead line comprises mainly of i ) conductor, ii ) supports , iii ) insulators and pole fittings . The function of overhead lines is to transmit electrical energy , and the important characteristics which the line conductors must have are : a) High electrical conductivity . b) High tensile strength . c) Low density . d) Low cost . The metals which posses the above properties are copper , aluminum and steel , which are used either alone or in combination .
Types of conductors
Copper
The most common conductor used for transmission is hard-drawn copper , because it is twice as strong as soft drawn copper and it stretches to a much lesser extent than soft drawn copper . The merits of this metal as a line conductor are : i ) It has a best conductivity in comparison to other metals . The conductivity of copper , however depends upon the percentage of impurities present in it , the more the impurities the lesser will be the conductivity . The conductivity of copper conductor also depends upon the method by which it has been drawn .
ii )
iii ) iv ) v)
It has higher current density , so for the given current rating , lesser cross-sectional area of conductor is required and hence it provides lesser cross-sectional area to wind loads . The metal is quite homogeneous . It has low specific resistance . It is durable and has a higher scrap value .
Aluminum
Next to copper aluminum is the conductor used in order of performance as far as the conductivity is concerned .Its merits and demerits are : i ) It is cheaper than copper . ii ) It is lighter in weight . iii ) It is second in conductivity ( among the metals used for transmission ) . Commercial hard-down aluminum wire at standard temperature has approximately 60.6 per cent conductivity in comparison to standard annealed copper wire . iv ) For same ohmic resistance , its diameter is about 1.27 times that of copper .
v) vi )
At higher voltages it causes less corona loss . Since the diameter of the conductor is more , so it is subject to greater wind pressure due to which greater is the swing of the conductor and greater is the sag . vii ) Since the conductors are liable to swing, so it requires larger cross arms . viii ) As the melting point of the conductor is low , so the short circuit etc. will damage it . ix ) Joining of aluminum is much more difficult than that of any other material . Because of storage of copper ores in India ,the use of aluminum in transmission and distribution lines has been adopted .
Steel
No doubt it has got the greatest tensile strength , but it is least used for transmission of electrical energy as it has got high resistance .Bare steel conductors are not used since , it deteriorates rapidly owing to rusting . Generally galvanized steel wires are used . It has the following properties : i) It is lowest in conductivity . ii ) It has high internal reactance . iii ) It is much subjected to eddy current and hysterisis loss. iv ) In a damp atmosphere it is rusted . Hence its use is limited .
with
steel
An aluminum conductor having a central core of galvanized steel wires is used for high voltage transmission purposes . This is done to increase the tensile strength of aluminum conductor . the galvanized steel core is covered by one or more strands of aluminum wires . The steel conductors used are galvanized in order to prevent rusting and electrolytic corrosion ( since Zinc is near to aluminum and there is no electro-chemical action between the two metals ) .
The cross-sections of the two metals are in the ratio (1:6) , but in case of high strength conductors their ratio is (1:4) . Thus the steel reinforced aluminum conductor has less sag and longer span than the copper conductor line since it has high tensile strength . The aluminum steel conductor has a larger diameter than any other type of conductor of same resistance . For all calculation purposes , it is assumed that the current is passing only in the aluminum section .
Line supports
i) ii ) iii ) iv ) v) vi ) vii )
The line supports are poles and the chief requirements for such supports are :
They must be mechanically strong with factor of safety of 2.5 to 3 . They must be light in weight without the loss of strength . They must have least number of parts . They must be cheap . Their maintenance cost should be minimum . They must be easily accessible for point and erection of line conductors . They must have longer life .
The different types of poles which can be used as line supports are :
a. Wooden poles . b. Steel tubular poles c. Reinforced concrete poles . d. Steel towers .
Fig.(1):Singlephase single-circuit
Generally the following formulae are used for obtaining spacing between the conductors :
spacing ! 0.01 V kv d 1.24 [ D feet
Where, Vkv : is voltage in kilovolts . d : is diameter of conductor in inches . w : is weight of conductor in lb. per foot run . D : is sag in feet .
Let , ( L ) be the length of the conductor POQ , suspended between the supports P and Q at the same level and having a distance L between them . Let , O be the lowest point of the catenary so formed , D be the maximum sag , and let : w : be the weight of the conductor per unit length . T : be the tension at any point A of the conductor . To : be the tension at point O of the conductor , which is taken as origin . S : be the length of the conductor OA .
W I D! 8 T0
W l TQ ! T 0 8 T0
T d ! 4
T 2 ! (d 2 r ) 4
Sectional area of the ice
T T d2 = (d 2 r )2 4 4 T = [ (d 2 r )2 d 2 ] 4 T = [ d 2 4 r 2 4 d r d 2 ] 4 =T r ( d r )
Density of ice
! 0.915
g / cm 3
The minimum temperature is assumed to be 22oF The effect of wind is allowed for by assuming that the wind is blowing with a velocity of ( 80.45 km ) per hour across the line . It is equivalent to a pressure of ( 33.7 km ) per square meter of the projected surface to the line to ice .
Kg
Fig.(11):Representation of resultant force acting on the conductor . So , the resultant force Wi acting on the conductor from figure , is given as :
W i ! (w w i ) P
2
2 w
Fig.(12)
Let , the different between the supports P and Q be h . The line POQ forms the parts of the catenary , " POP ". Let the horizontal distance between O and support Q be (x). So , distance of support P from O ! l x
l T h x! 2 l w
Example
An overhead line has a span of 220 meters , the lines conductor weights 684 km . per 1,000 meters . Calculate the max. sag in the line , if the maximum allowable tension in the line is 1,450 kg
Solution
W l Maximum sag = 8 T 0
2
l ! 220
T 0 ! 1, 450
m
Kg
Max. sag
0.684 v 220 v 220 ! 8 v 1, 450 ! 2.85 m