Problems of Hot & Humid Climatic Conditions What is a Heat Pipe? Heat Pipes & how they can HELP Conclusion
Safety margin
Health Problems
Mildew Growth
10
20
30
40
50
60
70
80
90
100
% Relative Humidity
35C @ 80% RH
45C @ 30% RH
20C @ 90% RH
35C @ 20% RH
Comfort conditions
35C @ 80% RH
20C @ 90% RH
35C @ 20% RH
Pyramid Centre
Mercato Mall
Decorative features
Recent Practice
Condensation
Recent Practice
Taking a point in this envelope, 42C @ 35% RH, and then cooling to 18C the air becomes saturated and unsuitable for supply.
Recent Practice
If this saturated air with a high moisture content is supplied into the space we will have two major problems:
Problem 1
The building occupants will feel very uncomfortable and health problems may arise.
HOTEL
Dissatisfied, unhappy customers and even potential insurance claims. Reduction in employee efficiency and, at worst, lost working days due to sickness.
OFFICE
Problem 2
The building fabric and fittings will deteriorate due to the high moisture levels creating excessive maintenance costs. This can manifest itself in several ways Discolouration of walls Mould growth Corrosion of metalworks Detachment of tiles etc. from walls/ceilings
Condensation
Reheat Coil
The pay-off
Overcooling means an increased cooling load. = increased running costs. This in turn means a larger chiller unit. = increased capital costs. Re-heating will require energy. = increased running costs. Re-heating also adds equipment and complexity.= increased capital costs.
So, while the theory is very attractive, the economics present a large deterrent. Ideally we would like to cool the air to a comfortable temperature and remove moisture, but without the need for expensive reheat. It sounds impossible, but by using heat pipes it can be achieved.
Heat Pipes
By using the latent capacity of the fluid the heat pipe transfers heat at a very high rate.
Heat out
Heat out
Using the latent capacity of the fluid, we can transfer large amounts of heat very rapidly from a hot point to a cold point on the tube wall.
Heat in
Heat in
Summary of Characteristics
Heat is transferred by latent means giving a heat transfer rate of around 1000 times that of a solid copper rod Vaporisation and condensation take place at the same temperature allowing high heat transfer at low temperature differences Heat pipes without wicks (Thermosyphons) rely on gravity to return the condensed liquid.
42C
36C
12C
42/28.5C
18/14.1C 12/11.8C
36/27.1C
12 / 11.8oC
Airflow
2-Row Horseshoe.
Horseshoe Heat Pipes are used either for original supply or for retrofit applications. The unit will be installed around an existing cooling coil.
In Practice
If the heatpipe is designed for a maximum temperature. What would the off condition be at other conditions?
Economic Design
Base design on commonest conditions not maximum conditions. This in turn means removing need for additional reheat. For close control some additional cooling may be required.
Bin Data
Worked Example
Based on average ambient condition, 32 C @ 58% RH. Cooling load - 51.3kW Heating load - 7.2kW Total load - 58.5kW
Worked Example
Air volume Heat Pipe, Add in the : 4.0 m3/s Air on: 40/27.8C, 40%RH Heat Pipe Pre-cool - 7.2kW Supply air Re-heat - 7.2kW Heat Pipe to room: 20/14.8Cload - 44.1kW New Clg New Htg load - 0kW Saving 14.4kW
Worked Example
At the final airconditions:is If alternative condition Heat Pipeat 18 C, then a required pre-cool : 9.5 kW Heat Pipe re-heat : 9.5 kW secondary cooling unit Cooling load - 54.3kW can trim the temperature. Heating load - 0kW Saving 19kW
FAHU
Air Handling Unit
18 / 14 C (65% RH)
o
Summary
Requires no energy to run, being driven by the cooling coil. Nett energy savings of around 30% compared to standard cooling and reheat. Lower cooling load = smaller chiller/ compressor. Design for average conditions to eliminate reheat. Easy installation. Controlled by the cooling coil.
Used to transfer heat between supply and exhaust air streams where :
The Heat Pipe unit straddles the supply and exhaust ducts A centre tube plate prevents cross contamination between airflows No pump requirement to transfer the heat as with a run around coil system Airstreams must be in counterflow
Orientation
Available in both vertical & horizontal arrangements. The warmer airstream must be at the bottom in the vertical mode.
Exhaust Air
Supply Air
Horizontal orientation
Benefits
Requires no energy to run. No maintenance. No cross contamination. Can be sized to suit the ductwork or AHU. Easy condensation removal.
Conclusion
Heat Pipes are extremely efficient heat transfer devices By installing across supply and exhaust ducts we can recover waste energy. Typical efficiencies 50% to 60 % By wrapping The Heat Pipe around a cooling coil we bypass a certain amount of heat, saving on the cooling load and giving free reheat. Nett energy savings - around 30 %
Completed projects
Contractor
Garmco BAH Al Hamad - Shj. SAS Raddison Muscat Thermo - Dubai Al Hamed Nael Est. - Al Ain Al Hamad - Shj. Al Hamad - Shj. Geco - Sharjah Sensaire - Dubai Majid Al Futtaim Verger Delport Viking Viking Al Futtaim W.S. Atkins RPW RPW Arab Consultants Sharjah Municipality Dubai Municipality Mario & Ass. GHQ Syna dev. Artek
Consultant
AHU Supplier
York Clever Saiver SKM Carrier Clever Clever Clever SKM Clever Saiver York Viking Viking SKM
Qty.
8 4 2 3 4 2 2 6 3 2 145 2 2 1
Type of Project
New Retrofit Retrofit Retrofit New New New New New Retrofit New New New New
Project
Aluminium Store Pyramid shopping center Raddison Crown Plaza MW-1699 Hiltonia Beach Samar Tower- Shj. Al Ansari Bldg. Swimm. Pool Children's City City Center Industrial city - ADH Al Nahdha Shopping Sharjah Mega Mall Sharjah Cricket Stadium
ETA
Carrier Gibca - Sharjah
Spectrum - Delhi
Novair
Carrier Petra
5
37 1
New
Retrofit Retrofit
Consultant
RPW RMJM Cab - Sharjah RMJM Arif & Bintouk
AHU Supplier
York Clever SKM Interklima Carrier Clever York Euroclima Mekar Aftron Carrier SKM
Qty.
8 33 90 6 8 4 24 6 30 1 1 2
Type of Project
New New New New New New New New New New New New
Project
Spinneys - Jumeira World Convention centre Indoor Sports Hall World Convention centre Novotel & Ibis Hotel Coral Beach Resort Royal Mirage hotel Dubai Women's association Exhibition Hall 1 & 2 DPA club Emaar bank pvt. Villa at Jebel Dana
SKM - Sharjah
Dhabi Contracting McQuay FNC Bu-Haleeba Junker
Ian Banhem
Al Turath Mott / EMS Arkiteknik Gemac Artek
SKM
Clever McQuay Dunham Bush Mekar Junker
8
14 6 41 2 8
New
New New New Retrofit New
Kharbash Bldg.
Wedding hall West Side Marina Neighborhood centre Ruler's villa Dawoodi Bohra center
Dehumidification selection
Any Questions ?
For further information or to download latest copies of our selection software, visit our website:
www.spcoils.co.uk
HEAT PIPES:
The Benefits of Heat Pipes in Hot & Humid Climates Allan Westbury Managing Director S & P Coils Ltd. Leicester, UK
Dry bulb temperature Air speed Air humidity Radiation RH 40 - 60 % Temperature 20 - 23C (68 - 75F)